SPEC: 48004

CU 600V LSZH XHHW-2 SOLONONplus™ FT4, VW-1 SPEC48004

SOLONONplus™ 600Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type XHHW-2

Download Category Specifications
PDF Excel Table

Application & Features

APPLICATION
Southwire’s 600 Volt SOLONONplus™ Type XHHW-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

FEATURES

  • The conductors are available in tinned and flexible copper stranding upon request.
  • NEC compliant
  • The halogen content is less than 0.2% and Acid gas less than 2.0%
  • UL listed VW-1
  • UL listed FT4/IEEE 1202 and ST-1
  • UL listed for CT use on 1/0 and Larger
  • -40°C Cold impact and cold bend
  • Oil Resistant I and II
  • Gasoline Resistance I and II
  • Sunlight Resistant
  • Specifications

    Select more options below for part numbers, packaging, and color options:
    Cond. Size Cond. Strands Strand Class Conductor Number Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Color Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) Max Pull Tension (lbs) (kg)
    More Options
    14 AWG 14 AWG
    7 7
    B B
    1 1
    0.070 0.18
    30 0.76
    BE BE
    0.133 0.34
    20 30
    2.631 3.92
    33 14.97
    More Options
    12 AWG 12 AWG
    7 7
    B B
    1 1
    0.088 0.22
    30 0.76
    BE BE
    0.151 0.38
    29 43
    1.662 2.47
    52 23.59
    More Options
    10 AWG 10 AWG
    7 7
    B B
    1 1
    0.113 0.29
    30 0.76
    BE BE
    0.177 0.45
    43 64
    1.040 1.55
    83 37.65
    More Options
    8 AWG 8 AWG
    7 7
    B B
    1 1
    0.141 0.36
    45 1.14
    BE BE
    0.236 0.60
    72 107
    0.653 0.97
    132 59.87
    More Options
    6 AWG 6 AWG
    7 7
    B B
    1 1
    0.177 0.45
    45 1.14
    BE BE
    0.272 0.69
    106 158
    0.411 0.61
    209 94.80
    More Options
    4 AWG 4 AWG
    7 7
    B B
    1 1
    0.225 0.57
    45 1.14
    BE BE
    0.319 0.81
    160 238
    0.258 0.38
    333 151.05
    More Options
    3 AWG 3 AWG
    7 7
    B B
    1 1
    0.252 0.64
    45 1.14
    BK BK
    0.346 0.88
    197 293
    0.205 0.31
    421 190.96
    More Options
    2 AWG 2 AWG
    7 7
    B B
    1 1
    0.282 0.72
    45 1.14
    BE BE
    0.371 0.94
    242 360
    0.162 0.24
    530 240.40
    More Options
    1 AWG 1 AWG
    19 19
    B B
    1 1
    0.322 0.82
    55 1.40
    GN GN
    0.438 1.11
    311 463
    0.128 0.19
    669 303.45
    More Options
    1/0 AWG 1/0 AWG
    19 19
    B B
    1 1
    0.361 0.92
    55 1.40
    WE WE
    0.478 1.21
    385 573
    0.102 0.15
    844 382.83
    More Options
    2/0 AWG 2/0 AWG
    19 19
    B B
    1 1
    0.406 1.03
    55 1.40
    BK BK
    0.522 1.33
    476 708
    0.081 0.12
    1065 483.08
    More Options
    3/0 AWG 3/0 AWG
    19 19
    B B
    1 1
    0.456 1.16
    55 1.40
    BK BK
    0.572 1.45
    591 880
    0.064 0.10
    1342 608.72
    More Options
    4/0 AWG 4/0 AWG
    19 19
    B B
    1 1
    0.512 1.30
    55 1.40
    WE WE
    0.614 1.56
    732 1089
    0.051 0.08
    1692 767.48
    More Options
    250 KCMIL 250 KCMIL
    37 37
    B B
    1 1
    0.542 1.38
    65 1.65
    BK BK
    0.678 1.72
    871 1296
    0.043 0.06
    2000 907.18
    More Options
    300 KCMIL 300 KCMIL
    37 37
    B B
    1 1
    0.594 1.51
    65 1.65
    BK BK
    0.730 1.85
    1034 1539
    0.036 0.05
    2400 1088.62
    More Options
    350 KCMIL 350 KCMIL
    37 37
    B B
    1 1
    0.641 1.63
    65 1.65
    BK BK
    0.777 1.97
    1197 1781
    0.031 0.05
    2800 1270.06
    More Options
    400 KCMIL 400 KCMIL
    37 37
    B B
    1 1
    0.685 1.74
    65 1.65
    BK BK
    0.821 2.09
    1359 2022
    0.027 0.04
    3200 1451.49
    More Options
    500 KCMIL 500 KCMIL
    37 37
    B B
    1 1
    0.789 2.00
    65 1.65
    GY GY
    0.902 2.29
    1681 2502
    0.022 0.03
    4000 1814.37
    More Options
    600 KCMIL 600 KCMIL
    61 61
    B B
    1 1
    0.840 2.13
    80 2.03
    BK BK
    1.008 2.56
    2038 3033
    0.018 0.03
    4800 2177.24
    More Options
    750 KCMIL 750 KCMIL
    61 61
    B B
    1 1
    0.968 2.46
    80 2.03
    BK BK
    1.136 2.89
    2527 3761
    0.014 0.02
    6000 2721.55

    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Size (Strand) Black Red Blue White Brown Orange Yellow Gray Green Purple
    14 (7) 14 (7)
    666081
    666084
    666076
    666078
    666079
    666083
    666077
    666082
    666080
    666085
    12 (7) 12 (7)
    666087
    666092
    666086
    666093
    666088
    666091
    666094
    666090
    666089
    10 (7) 10 (7)
    139436
    139441
    139435
    139442
    139437
    139440
    139443
    139439
    139438
    8 (7) 8 (7)
    139488
    139493
    139487
    139494
    139489
    139492
    139495
    139491
    139490
    6 (7) 6 (7)
    139477
    139482
    139476
    139483
    139478
    139481
    139484
    139480
    139479
    4 (7) 4 (7)
    139459
    139464
    139458
    139465
    139460
    139463
    139466
    139462
    139461
    3 (7) 3 (7)
    139454
    2 (7) 2 (7)
    139445
    139449
    139444
    139450
    139446
    139448
    139451
    139447
    1 (19) 1 (19)
    139430
    139429
    139428
    1/0 (19) 1/0 (19)
    139434
    139433
    139431
    139432
    2/0 (19) 2/0 (19)
    139452
    3/0 (19) 3/0 (19)
    139455
    4/0 (19) 4/0 (19)
    139469
    139467
    139468
    250 (37) 250 (37)
    139453
    300 (37) 300 (37)
    139456
    350 (37) 350 (37)
    139457
    400 (37) 400 (37)
    139470
    500 (37) 500 (37)
    139475
    139472
    139473
    139471
    139474
    600 (61) 600 (61)
    139485
    750 (61) 750 (61)
    139486

    Standards & References

    • ASTM B3 Soft or Annealed Copper Wire
    • ASTM B8 Concentric-Lay-Stranded Copper Conductors
    • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
    • UL 44 Thermoset-Insulated Wires and Cables
    • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
    • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
    • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
    • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
    • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
    • RoHS-2 (European Directive 2011/65/EU)
    • ISO 9001 Quality management
    • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
    • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways (non-emergency circuits only)

    Construction

    1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8; Tinned copper per ASTM B33 available upon request
    2. Insulation:SOLONONplus™ Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type XHHW-2