SPEC: 22060

SIMpull® T90 Copper SPEC22060

SIMpull® THHN THWN-2 MTW / c(UL) T90 Nylon TWN75 Copper Conductor, 600V, Thermoplastic-Insulated Cable, All Sizes Rated TWN75

Download Category Specifications
PDF Excel Table

Application & Features

• SIMpull® THHN, THWN-2, and MTW (UL): Suitable for dry locations not exceeding 90°C. For Gasoline and Oil Resistant II applications not to exceed 75°C.
• MTW (UL): suitable for dry locations not exceeding 90°C. For wet locations, Gasoline and Oil Resistant II applications not to exceed 60°C.
• T90 Nylon c(UL): cables are primarily intended for installation in conduit (raceways) as exposed wiring in dry locations not exceeding 90°C.
• TWN75 c(UL): suitable for wet or dry locations at not more than 75°C.

The maximum voltage rating for all intended applications is 600 volts. Minimum installation handling temperature is limited to -25°C. Minimum operating temperature limited to -40°C. Non-SIMpull Silicone Free sizes 14, 12, and 10 AWG.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
14 AWG 14 AWG
1 1
Solid Solid
0.064 0.16
15 0.38
5 0.13
0.106 0.27
12 18
15 22
More Options
14 AWG 14 AWG
1 1
19 19
0.070 0.18
15 0.38
5 0.13
0.113 0.29
12 18
16 24
More Options
12 AWG 12 AWG
1 1
Solid Solid
0.080 0.20
15 0.38
5 0.13
0.122 0.31
19 28
23 34
More Options
12 AWG 12 AWG
1 1
19 19
0.088 0.22
15 0.38
5 0.13
0.132 0.34
20 30
24 36
More Options
10 AWG 10 AWG
1 1
Solid Solid
0.101 0.26
20 0.51
5 0.13
0.153 0.39
31 46
37 55
More Options
10 AWG 10 AWG
1 1
19 19
0.113 0.29
20 0.51
5 0.13
0.165 0.42
32 48
38 57
More Options
8 AWG 8 AWG
1 1
19 19
0.141 0.36
30 0.76
6 0.15
0.217 0.55
50 74
63 94
More Options
6 AWG 6 AWG
1 1
19 19
0.177 0.45
30 0.76
6 0.15
0.253 0.64
81 121
95 141
More Options
4 AWG 4 AWG
1 1
19 19
0.225 0.57
40 1.02
7 0.18
0.322 0.82
128 190
153 228
More Options
3 AWG 3 AWG
1 1
19 19
0.252 0.64
40 1.02
7 0.18
0.350 0.89
162 241
190 283
More Options
2 AWG 2 AWG
1 1
19 19
0.282 0.72
40 1.02
7 0.18
0.382 0.97
204 304
235 350
More Options
1 AWG 1 AWG
1 1
19 19
0.322 0.82
50 1.27
8 0.20
0.439 1.12
258 384
301 448
More Options
1/0 AWG 1/0 AWG
1 1
19 19
0.361 0.92
50 1.27
8 0.20
0.480 1.22
326 485
374 557
More Options
2/0 AWG 2/0 AWG
1 1
19 19
0.420 1.07
50 1.27
5 0.13
0.524 1.33
410 610
464 691
More Options
3/0 AWG 3/0 AWG
1 1
19 19
0.456 1.16
50 1.27
8 0.20
0.574 1.46
518 771
579 862

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
14 AWG 14 AWG
1 1
0.400 1.02
32 14.51
2.631 3.92
3.170 4.72
0.058 0.09
20 20
25 25
More Options
14 AWG 14 AWG
1 1
0.400 1.02
32 14.51
2.631 3.92
3.170 4.72
0.058 0.09
20 20
25 25
More Options
12 AWG 12 AWG
1 1
0.400 1.02
52 23.59
1.662 2.47
2.002 2.98
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
1 1
0.500 1.27
52 23.59
1.662 2.47
2.002 2.98
0.054 0.08
25 25
30 30
More Options
10 AWG 10 AWG
1 1
0.600 1.52
83 37.65
1.040 1.55
1.253 1.86
0.050 0.07
35 35
40 40
More Options
10 AWG 10 AWG
1 1
0.600 1.52
83 37.65
1.040 1.55
1.253 1.86
0.050 0.07
35 35
40 40
More Options
8 AWG 8 AWG
1 1
0.800 2.03
132 59.87
0.653 0.97
0.786 1.17
0.052 0.08
50 50
55 55
More Options
6 AWG 6 AWG
1 1
1.000 2.54
209 94.80
0.411 0.61
0.495 0.74
0.051 0.08
65 65
75 75
More Options
4 AWG 4 AWG
1 1
1.200 3.05
333 151.05
0.258 0.38
0.310 0.46
0.048 0.07
85 85
95 95
More Options
3 AWG 3 AWG
1 1
1.400 3.56
420 190.51
0.205 0.31
0.246 0.37
0.047 0.07
100 100
115 115
More Options
2 AWG 2 AWG
1 1
1.500 3.81
530 240.40
0.162 0.24
0.195 0.29
0.045 0.07
115 115
130 130
More Options
1 AWG 1 AWG
1 1
1.700 4.32
669 303.45
0.128 0.19
0.154 0.23
0.046 0.07
130 130
145 145
More Options
1/0 AWG 1/0 AWG
1 1
1.900 4.83
844 382.83
0.102 0.15
0.122 0.18
0.044 0.07
150 150
170 170
More Options
2/0 AWG 2/0 AWG
1 1
2.100 5.33
1064 482.62
0.081 0.12
0.097 0.14
0.043 0.06
175 175
195 195
More Options
3/0 AWG 3/0 AWG
1 1
2.200 5.59
1342 608.72
0.064 0.10
0.078 0.12
0.042 0.06
200 200
225 225

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Non-SIMpull Silicone Free sizes: 14, 12, and 10 AWG.

Cond. Size
Brown
Stranding
Green
Color
White/Blue
AWG num Black Red White Yellow Orange Blue
14 14
1 (solid) 1 (solid)
507665
507699
507673
507723
610483
507707
553096
507681
14 14
19 19
472001
472027
472019
672659
687517
472043
507715
472035
678050
12 12
1 (solid) 1 (solid)
495770
495796
495788
507657
507632
495812
507640
495804
12 12
19 19
472050
472076
472068
672675
552660
472092
672667
472084
10 10
1 (solid) 1 (solid)
507731
484626
507749
507756
672683
10 10
19 19
472100
472126
472118
552663
610486
472142
552662
472134
8 8
19 19
472159
611462 or 472175 611462 or 472175
472167
472191
472183
6 6
19 19
472209
472225
472217
472241
472233
4 4
19 19
472258
472282
3 3
19 19
484675
484667
684068
2 2
19 19
672386
672394
684076
1 1
19 19
684084
1/0 1/0
19 19
471979
2/0 2/0
19 19
672402
688051
3/0 3/0
19 19
471995
471987
4/0 4/0
19 19
677820 677820

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material
  • UL 1063 Machine Tool Wiring (MTW)
  • CSA Certified LL90458
  • CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
  • Canadian Electrical Code
  • CSA FT-1 Flame Test

Construction

  1. Conductor:Solid soft drawn copper per ASTM B3 or Combination unilay-stranded copper conductors per ASTM B3 and B787
  2. Insulation:Colored Polyvinyl Chloride (PVC)
  3. Sheath:Nylon sheath utilizing SIMpull® technology