SIMpull® THHN, THWN-2, MTW - (UL)- Suitable for dry locations not exceeding 90°C. For Gasoline and Oil Resistant II applications not to exceed 75°C. MTW (UL) - suitable for dry locations not exceeding 90°C. For wet locations, Gasoline and Oil Resistant II applications not to exceed 60°C. T90 Nylon c(UL) - cables are primarily intended for installation in conduit (raceways) as exposed wiring in dry locations not exceeding 90°C. TWN75 c(UL) - suitable for wet or dry locations at not more than 75°C. The maximum voltage rating for all intended applications is 600 volts. Minimum installation handling temperature is limited to -25°C. Minimum operating temperature limited to -40°C. Non-SIMpull Silicone Free size 14, 12, 10.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
14 AWG
14 AWG
|
0
0
|
Solid
Solid
|
0.064
0.16
|
15
0.38
|
5
0.13
|
0.106
0.27
|
12
18
|
15
22
|
| More Options |
14 AWG
14 AWG
|
1
1
|
19
19
|
0.070
0.18
|
15
0.38
|
5
0.13
|
0.113
0.29
|
12
18
|
16
24
|
| More Options |
12 AWG
12 AWG
|
1
1
|
Solid
Solid
|
0.080
0.20
|
15
0.38
|
5
0.13
|
0.122
0.31
|
19
28
|
23
34
|
| More Options |
12 AWG
12 AWG
|
1
1
|
19
19
|
0.088
0.22
|
15
0.38
|
5
0.13
|
0.132
0.34
|
20
30
|
24
36
|
| More Options |
10 AWG
10 AWG
|
1
1
|
Solid
Solid
|
0.101
0.26
|
20
0.51
|
5
0.13
|
0.153
0.39
|
31
46
|
37
55
|
| More Options |
10 AWG
10 AWG
|
1
1
|
19
19
|
0.113
0.29
|
20
0.51
|
5
0.13
|
0.165
0.42
|
32
48
|
38
57
|
| More Options |
8 AWG
8 AWG
|
1
1
|
19
19
|
0.141
0.36
|
30
0.76
|
6
0.15
|
0.217
0.55
|
50
74
|
63
94
|
| More Options |
6 AWG
6 AWG
|
1
1
|
19
19
|
0.177
0.45
|
30
0.76
|
6
0.15
|
0.253
0.64
|
81
121
|
95
141
|
| More Options |
4 AWG
4 AWG
|
1
1
|
19
19
|
0.225
0.57
|
40
1.02
|
7
0.18
|
0.322
0.82
|
128
190
|
153
228
|
| More Options |
3 AWG
3 AWG
|
1
1
|
19
19
|
0.252
0.64
|
40
1.02
|
7
0.18
|
0.350
0.89
|
162
241
|
190
283
|
| More Options |
2 AWG
2 AWG
|
1
1
|
19
19
|
0.282
0.72
|
40
1.02
|
7
0.18
|
0.382
0.97
|
204
304
|
235
350
|
| More Options |
1 AWG
1 AWG
|
1
1
|
19
19
|
0.322
0.82
|
50
1.27
|
8
0.20
|
0.439
1.12
|
258
384
|
301
448
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
19
19
|
0.361
0.92
|
50
1.27
|
8
0.20
|
0.480
1.22
|
326
485
|
374
557
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
19
19
|
0.420
1.07
|
50
1.27
|
5
0.13
|
0.524
1.33
|
410
610
|
464
691
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
19
19
|
0.456
1.16
|
50
1.27
|
8
0.20
|
0.574
1.46
|
518
771
|
579
862
|
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
14 AWG
14 AWG
|
0
0
|
0.400
1.02
|
32
14.51
|
2.631
3.92
|
3.170
4.72
|
0.058
0.09
|
20
20
|
25
25
|
| More Options |
14 AWG
14 AWG
|
1
1
|
0.400
1.02
|
32
14.51
|
2.631
3.92
|
3.170
4.72
|
0.058
0.09
|
20
20
|
25
25
|
| More Options |
12 AWG
12 AWG
|
1
1
|
0.400
1.02
|
52
23.59
|
1.662
2.47
|
2.002
2.98
|
0.054
0.08
|
25
25
|
30
30
|
| More Options |
12 AWG
12 AWG
|
1
1
|
0.500
1.27
|
52
23.59
|
1.662
2.47
|
2.002
2.98
|
0.054
0.08
|
25
25
|
30
30
|
| More Options |
10 AWG
10 AWG
|
1
1
|
0.600
1.52
|
83
37.65
|
1.040
1.55
|
1.253
1.86
|
0.050
0.07
|
35
35
|
40
40
|
| More Options |
10 AWG
10 AWG
|
1
1
|
0.600
1.52
|
83
37.65
|
1.040
1.55
|
1.253
1.86
|
0.050
0.07
|
35
35
|
40
40
|
| More Options |
8 AWG
8 AWG
|
1
1
|
0.800
2.03
|
132
59.87
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
50
50
|
55
55
|
| More Options |
6 AWG
6 AWG
|
1
1
|
1.000
2.54
|
209
94.80
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
| More Options |
4 AWG
4 AWG
|
1
1
|
1.200
3.05
|
333
151.05
|
0.258
0.38
|
0.310
0.46
|
0.048
0.07
|
85
85
|
95
95
|
| More Options |
3 AWG
3 AWG
|
1
1
|
1.400
3.56
|
420
190.51
|
0.205
0.31
|
0.246
0.37
|
0.047
0.07
|
100
100
|
115
115
|
| More Options |
2 AWG
2 AWG
|
1
1
|
1.500
3.81
|
530
240.40
|
0.162
0.24
|
0.195
0.29
|
0.045
0.07
|
115
115
|
130
130
|
| More Options |
1 AWG
1 AWG
|
1
1
|
1.700
4.32
|
669
303.45
|
0.128
0.19
|
0.154
0.23
|
0.046
0.07
|
130
130
|
145
145
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
1.900
4.83
|
844
382.83
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
150
150
|
170
170
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
2.100
5.33
|
1064
482.62
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
2.200
5.59
|
1342
608.72
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
200
200
|
225
225
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Non-SIMpull Silicone Free sizes: 14, 12, 10.
| Size (Strand) | Color | Stock Number |
|
Size (Strand)
Size (Strand)
|
Color
Color
|
Stock Number
Stock Number
|
|
14 (Solid)
14 (Solid)
|
BK
BK
|
|
|
14 (Solid)
14 (Solid)
|
RD
RD
|
|
|
14 (Solid)
14 (Solid)
|
WE
WE
|
|
|
14 (Solid)
14 (Solid)
|
YW
YW
|
|
|
14 (Solid)
14 (Solid)
|
OE
OE
|
|
|
14 (Solid)
14 (Solid)
|
BE
BE
|
|
|
14 (Solid)
14 (Solid)
|
BN
BN
|
|
|
14 (Solid)
14 (Solid)
|
GN
GN
|
|
|
14 (19)
14 (19)
|
BK
BK
|
|
|
14 (19)
14 (19)
|
YW
YW
|
|
|
14 (19)
14 (19)
|
WE
WE
|
|
|
14 (19)
14 (19)
|
RD
RD
|
|
|
14 (19)
14 (19)
|
OE
OE
|
|
|
14 (19)
14 (19)
|
BE
BE
|
|
|
14 (19)
14 (19)
|
GN
GN
|
|
|
14 (19)
14 (19)
|
BN
BN
|
|
|
12 (Solid)
12 (Solid)
|
BK
BK
|
|
|
12 (Solid)
12 (Solid)
|
OE
OE
|
|
|
12 (Solid)
12 (Solid)
|
BE
BE
|
|
|
12 (Solid)
12 (Solid)
|
GN
GN
|
|
|
12 (Solid)
12 (Solid)
|
BN
BN
|
|
|
12 (Solid)
12 (Solid)
|
WE
WE
|
|
|
12 (Solid)
12 (Solid)
|
RD
RD
|
|
|
12 (Solid)
12 (Solid)
|
YW
YW
|
|
|
12 (19)
12 (19)
|
BK
BK
|
|
|
12 (19)
12 (19)
|
WE
WE
|
|
|
12 (19)
12 (19)
|
YW
YW
|
|
|
12 (19)
12 (19)
|
BE
BE
|
|
|
12 (19)
12 (19)
|
RD
RD
|
|
|
12 (19)
12 (19)
|
GN
GN
|
|
|
12 (19)
12 (19)
|
OE
OE
|
|
|
12 (19)
12 (19)
|
BN
BN
|
|
|
10 (Solid)
10 (Solid)
|
RD
RD
|
|
|
10 (Solid)
10 (Solid)
|
BE
BE
|
|
|
10 (Solid)
10 (Solid)
|
BK
BK
|
|
|
10 (Solid)
10 (Solid)
|
GN
GN
|
|
|
10 (Solid)
10 (Solid)
|
WE
WE
|
|
|
10 (19)
10 (19)
|
BK
BK
|
|
|
10 (19)
10 (19)
|
YW
YW
|
|
|
10 (19)
10 (19)
|
OE
OE
|
|
|
10 (19)
10 (19)
|
GN
GN
|
|
|
10 (19)
10 (19)
|
WE
WE
|
|
|
10 (19)
10 (19)
|
BN
BN
|
|
|
10 (19)
10 (19)
|
RD
RD
|
|
|
10 (19)
10 (19)
|
BE
BE
|
|
|
8 (19)
8 (19)
|
BK
BK
|
|
|
8 (19)
8 (19)
|
RD
RD
|
|
|
8 (19)
8 (19)
|
RD
RD
|
|
|
8 (19)
8 (19)
|
WE
WE
|
|
|
8 (19)
8 (19)
|
BE
BE
|
|
|
8 (19)
8 (19)
|
GN
GN
|
|
|
6 (19)
6 (19)
|
BK
BK
|
|
|
6 (19)
6 (19)
|
WE
WE
|
|
|
6 (19)
6 (19)
|
RD
RD
|
|
|
6 (19)
6 (19)
|
BE
BE
|
|
|
6 (19)
6 (19)
|
GN
GN
|
|
|
4 (19)
4 (19)
|
BK
BK
|
|
|
4 (19)
4 (19)
|
GN
GN
|
|
|
3 (19)
3 (19)
|
WE
WE
|
|
|
3 (19)
3 (19)
|
GN
GN
|
|
|
3 (19)
3 (19)
|
BK
BK
|
|
|
2 (19)
2 (19)
|
BK
BK
|
|
|
2 (19)
2 (19)
|
GN
GN
|
|
|
2 (19)
2 (19)
|
WE
WE
|
|
|
1 (19)
1 (19)
|
BK
BK
|
|
|
1/0 (19)
1/0 (19)
|
BK
BK
|
|
|
2/0 (19)
2/0 (19)
|
GN
GN
|
|
|
2/0 (19)
2/0 (19)
|
BK
BK
|
|
|
3/0 (19)
3/0 (19)
|
WE
WE
|
|
|
3/0 (19)
3/0 (19)
|
BK
BK
|
|
|
4/0 (19)
4/0 (19)
|
WE
WE
|
677820
677820
|