SPEC: 80120

AAC SPEC80120

All Aluminum Conductor. Bare.

Download Category Specifications
PDF Excel Table

Application & Features

Classes1 AA and A are used primarily for overhead transmission and primary and secondary distribution, where ampacity must be maintained and a lighter conductor (compared to ACSR) is desired, and when conductor strength is not a critical factor. Classes B and C are used primarily as bus, apparatus connectors and jumpers, where additional flexibility is required.

1Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.

Specifications

Select more options below for part numbers, packaging, and color options:
Codeword Size (AWG or kcmil) (mm2) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
IRIS IRIS
2 AWG 2 AWG
7 7
292 7.42
62 93
More Options
POPPY POPPY
1/0 AWG 1/0 AWG
7 7
368 9.36
99 147
More Options
ASTER ASTER
2/0 AWG 2/0 AWG
7 7
413 10.51
125 186
More Options
PHLOX PHLOX
3/0 AWG 3/0 AWG
7 7
464 11.80
157 234
More Options
OXLIP OXLIP
4/0 AWG 4/0 AWG
7 7
521 13.25
198 295
More Options
DAISY DAISY
266.8 KCMIL 266.8 KCMIL
7 7
585 14.88
250 372
More Options
TULIP TULIP
336.4 KCMIL 336.4 KCMIL
19 19
665 16.90
316 471
More Options
DAFFODIL DAFFODIL
350 KCMIL 350 KCMIL
19 19
678 17.23
328 488
More Options
CANNA CANNA
397.5 KCMIL 397.5 KCMIL
19 19
723 18.37
373 555
More Options
COSMOS COSMOS
477 KCMIL 477 KCMIL
19 19
792 20.12
447 665
More Options
SYRINGA SYRINGA
477 KCMIL 477 KCMIL
37 37
794 20.18
447 665
More Options
DAHLIA DAHLIA
556.5 KCMIL 556.5 KCMIL
19 19
855 21.73
523 778
More Options
MISTLETOE MISTLETOE
556.5 KCMIL 556.5 KCMIL
37 37
858 21.80
521 776
More Options
MEADOWSWEET MEADOWSWEET
600 KCMIL 600 KCMIL
37 37
891 22.63
562 836
More Options
ORCHID ORCHID
636 KCMIL 636 KCMIL
37 37
917 23.31
596 887
More Options
ARBUTUS ARBUTUS
795 KCMIL 795 KCMIL
37 37
1026 26.07
745 1109
More Options
MAGNOLIA MAGNOLIA
954 KCMIL 954 KCMIL
37 37
1124 28.55
894 1331
More Options
GOLDENROD GOLDENROD
954 KCMIL 954 KCMIL
61 61
1125 28.60
895 1332
More Options
MARIGOLD MARIGOLD
1113 KCMIL 1113 KCMIL
61 61
1215 30.88
1044 1553
More Options
HAWTHORN HAWTHORN
1192.5 KCMIL 1192.5 KCMIL
61 61
1258 31.96
1117 1663
More Options
NARCISSUS NARCISSUS
1272 KCMIL 1272 KCMIL
61 61
1299 33.01
1192 1774
More Options
COREOPSIS COREOPSIS
1590 KCMIL 1590 KCMIL
61 61
1452 36.90
1489 2216
More Options
JESSAMINE JESSAMINE
1750 KCMIL 1750 KCMIL
61 61
1524 38.72
1641 2442
More Options
COWSLIP COWSLIP
2000 KCMIL 2000 KCMIL
91 91
1630 41.41
1873 2788
More Options
SAGEBRUSH SAGEBRUSH
2250 KCMIL 2250 KCMIL
91 91
1729 43.92
2128 3167
More Options
LUPINE LUPINE
2500 KCMIL 2500 KCMIL
91 91
1822 46.30
2365 3519
More Options
TRILLIUM TRILLIUM
3000 KCMIL 3000 KCMIL
127 127
1998 50.75
2840 4226
More Options
BLUEBONNET BLUEBONNET
3500 KCMIL 3500 KCMIL
127 127
2158 54.81
3344 4977

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Stock Number
Code Word
Conductor Size
AWG or kcmil
No. of Wires
Stranding Class
Ind. Wire Dia
inch
Comp Cable
inch
Cross-Sectional Area
sq. inch
Overall Weight
lb/1000ft
Peachbell Peachbell
6 6
7 7
A A
0.0612 0.0612
0.184 0.184
0.0206 0.0206
25 25
Rose Rose
4 4
7 7
A A
0.0772 0.0772
0.232 0.232
0.0328 0.0328
39 39
100834
Iris Iris
2 2
7 7
AA, A AA, A
0.0974 0.0974
0.292 0.292
0.0522 0.0522
62 62
Pansy Pansy
1 1
7 7
AA AA
0.1093 0.1093
0.328 0.328
0.0657 0.0657
78 78
100859
Poppy Poppy
1/0 1/0
7 7
AA, A AA, A
0.1228 0.1228
0.368 0.368
0.0829 0.0829
99 99
100867
Aster Aster
2/0 2/0
7 7
AA, A AA, A
0.1379 0.1379
0.414 0.414
0.1045 0.1045
125 125
100875
Phlox Phlox
3/0 3/0
7 7
AA, A AA, A
0.1548 0.1548
0.464 0.464
0.1317 0.1317
157 157
100883
Oxlip Oxlip
4/0 4/0
7 7
AA, A AA, A
0.1739 0.1739
0.522 0.522
0.1663 0.1663
198 198
Sneezewort Sneezewort
250 250
7 7
AA AA
0.189 0.189
0.567 0.567
0.1964 0.1964
234 234
Valerian Valerian
250 250
19 19
A A
0.1147 0.1147
0.574 0.574
0.1963 0.1963
234 234
100891
Daisy Daisy
266.8 266.8
7 7
AA AA
0.1952 0.1952
0.586 0.586
0.2095 0.2095
250 250
100909 100909
Laurel Laurel
266.8 266.8
19 19
A A
0.1185 0.1185
0.592 0.592
0.2095 0.2095
250 250
Peony Peony
300 300
19 19
A A
0.1257 0.1257
0.628 0.628
0.2358 0.2358
281 281
100917
Tulip Tulip
336.4 336.4
19 19
A A
0.1331 0.1331
0.665 0.665
0.2644 0.2644
315 315
148122
Daffodil Daffodil
350 350
19 19
A A
0.1357 0.1357
0.679 0.679
0.2748 0.2748
328 328
100925
Canna Canna
397.5 397.5
19 19
AA, A AA, A
0.1446 0.1446
0.723 0.723
0.312 0.312
373 373
Goldentuft Goldentuft
450 450
19 19
AA AA
0.1539 0.1539
0.769 0.769
0.3534 0.3534
422 422
100933
Cosmos Cosmos
477 477
19 19
AA AA
0.1584 0.1584
0.792 0.792
0.3744 0.3744
447 447
100958
Syringa Syringa
477 477
37 37
A A
0.1135 0.1135
0.795 0.795
0.3744 0.3744
447 447
Zinnia Zinnia
500 500
19 19
AA AA
0.1622 0.1622
0.811 0.811
0.3926 0.3926
469 469
Hyacinth Hyacinth
500 500
37 37
AA AA
0.1162 0.1162
0.814 0.814
0.3924 0.3924
469 469
100941
Dahlia Dahlia
556.5 556.5
19 19
AA AA
0.1711 0.1711
0.856 0.856
0.4369 0.4369
522 522
100966
Mistletoe Mistletoe
556.5 556.5
37 37
AA AA
0.1226 0.1226
0.858 0.858
0.4368 0.4368
522 522
157743
Meadowsweet Meadowsweet
600 600
37 37
AA AA
0.1273 0.1273
0.891 0.891
0.4709 0.4709
562 562
100974
Orchid Orchid
636 636
37 37
AA, A AA, A
0.1311 0.1311
0.918 0.918
0.4995 0.4995
596 596
Heuchera Heuchera
650 650
37 37
AA AA
0.1325 0.1325
0.928 0.928
0.5102 0.5102
609 609
Verbena Verbena
700 700
37 37
AA AA
0.1375 0.1375
0.963 0.963
0.5494 0.5494
656 656
Flag Flag
700 700
61 61
A A
0.1071 0.1071
0.964 0.964
0.5495 0.5495
656 656
Violet Violet
715.5 715.5
37 37
AA AA
0.1391 0.1391
0.973 0.973
0.5623 0.5623
671 671
Nasturtium Nasturtium
715.5 715.5
61 61
AA AA
0.1083 0.1083
0.975 0.975
0.5619 0.5619
671 671
182618 182618
Petunia Petunia
750 750
37 37
AA AA
0.1424 0.1424
0.997 0.997
0.5893 0.5893
703 703
Cattail Cattail
750 750
61 61
AA AA
0.1109 0.1109
0.998 0.998
0.5892 0.5892
703 703
100990
Arbutus Arbutus
795 795
37 37
AA AA
0.1466 0.1466
1.026 1.026
0.6245 0.6245
745 745
Lilac Lilac
795 795
61 61
A A
0.1142 0.1142
1.027 1.027
0.6248 0.6248
745 745
Cockscomb Cockscomb
900 900
37 37
AA AA
0.156 0.156
1.092 1.092
0.7072 0.7072
844 844
Snapdragon Snapdragon
900 900
61 61
AA AA
0.1215 0.1215
1.093 1.093
0.7072 0.7072
844 844
101014
Magnolia Magnolia
954 954
37 37
AA AA
0.1606 0.1606
1.124 1.124
0.7495 0.7495
894 894
101063
Goldenrod Goldenrod
954 954
61 61
A A
0.1251 0.1251
1.125 1.125
0.7498 0.7498
894 894
Hawkweed Hawkweed
1000 1000
37 37
AA AA
0.1644 0.1644
1.151 1.151
0.7854 0.7854
937 937
Camellia Camellia
1000 1000
61 61
AA AA
0.128 0.128
1.152 1.152
0.7849 0.7849
937 937
101022 101022
Bluebell Bluebell
1033.5 1033.5
37 37
AA AA
0.1671 0.1671
1.17 1.17
0.8114 0.8114
969 969
Larkspur Larkspur
1033.5 1033.5
61 61
AA AA
0.1302 0.1302
1.171 1.171
0.8122 0.8122
969 969
Marigold Marigold
1113 1113
61 61
AA, A AA, A
0.1351 0.1351
1.216 1.216
0.8744 0.8744
1043 1043
Hawthorn Hawthorn
1192.5 1192.5
61 61
AA, A AA, A
0.1398 0.1398
1.258 1.258
0.9363 0.9363
1118 1118
101105
Narcissus Narcissus
1272 1272
61 61
AA, A AA, A
0.1444 0.1444
1.3 1.3
0.999 0.999
1192 1192
Columbine Columbine
1351.5 1351.5
61 61
AA, A AA, A
0.1488 0.1488
1.34 1.34
1.0608 1.0608
1267 1267
Carnation Carnation
1431 1431
61 61
AA, A AA, A
0.1532 0.1532
1.378 1.378
1.1244 1.1244
1341 1341
Gladiolus Gladiolus
1510.5 1510.5
61 61
A A
0.1574 0.1574
1.416 1.416
1.1869 1.1869
1416 1416
101147
Coreopsis Coreopsis
1590 1590
61 61
AA AA
0.1614 0.1614
1.453 1.453
1.248 1.248
1490 1490
182634
Jessamine Jessamine
1750 1750
61 61
AA AA
0.1694 0.1694
1.524 1.524
1.3748 1.3748
1640 1640
Cowslip Cowslip
2000 2000
91 91
A A
0.1482 0.1482
1.631 1.631
1.5697 1.5697
1875 1875
Sagebrush Sagebrush
2250 2250
91 91
A A
0.1572 0.1572
1.73 1.73
1.7662 1.7662
2130 2130
182675
Lupine Lupine
2500 2500
91 91
A A
0.1657 0.1657
1.823 1.823
1.9623 1.9623
2366 2366
Bitterroot Bitterroot
2750 2750
91 91
A A
0.1738 0.1738
1.912 1.912
2.1589 2.1589
2603 2603
Trillium Trillium
3000 3000
127 127
A A
0.1537 0.1537
1.998 1.998
2.3564 2.3564
2839 2839
Bluebonnet Bluebonnet
3500 3500
127 127
A A
0.166 0.166
2.158 2.158
2.7486 2.7486
3345 3345
Stock Number
Code Word
Size
AWG or kcmil
Rated Strength
lb
DC Resistance @ 20ºC
Ω/1000ft
AC Resistance @ 75ºC
Ω/1000ft
Allowable Ampacity†
amp
Peachbell Peachbell
6 6
563 563
0.658 0.658
0.805 0.805
103 103
Rose Rose
4 4
881 881
0.414 0.414
0.506 0.506
138 138
100834
Iris Iris
2 2
1350 1350
0.26 0.26
0.318 0.318
185 185
Pansy Pansy
1 1
1640 1640
0.207 0.207
0.252 0.252
214 214
100859
Poppy Poppy
1/0 1/0
1990 1990
0.164 0.164
0.2 0.2
247 247
100867
Aster Aster
2/0 2/0
2510 2510
0.13 0.13
0.159 0.159
286 286
100875
Phlox Phlox
3/0 3/0
3040 3040
0.103 0.103
0.126 0.126
331 331
100883
Oxlip Oxlip
4/0 4/0
3830 3830
0.0817 0.0817
0.0999 0.0999
383 383
Sneezewort Sneezewort
250 250
4520 4520
0.0691 0.0691
0.0846 0.0846
425 425
Valerian Valerian
250 250
4660 4660
0.0691 0.0691
0.0846 0.0846
426 426
100891
Daisy Daisy
266.8 266.8
4830 4830
0.0648 0.0648
0.0793 0.0793
443 443
100909 100909
Laurel Laurel
266.8 266.8
4970 4970
0.0648 0.0648
0.0793 0.0793
444 444
Peony Peony
300 300
5480 5480
0.0576 0.0576
0.0706 0.0706
478 478
100917
Tulip Tulip
336.4 336.4
6150 6150
0.0514 0.0514
0.063 0.063
513 513
148122
Daffodil Daffodil
350 350
6390 6390
0.0494 0.0494
0.0605 0.0605
526 526
100925
Canna Canna
397.5 397.5
7110 7110
0.0435 0.0435
0.0534 0.0534
570 570
Goldentuft Goldentuft
450 450
7890 7890
0.0384 0.0384
0.0472 0.0472
616 616
100933
Cosmos Cosmos
477 477
8360 8360
0.0362 0.0362
0.0445 0.0445
639 639
100958
Syringa Syringa
477 477
8690 8690
0.0362 0.0362
0.0445 0.0445
639 639
Zinnia Zinnia
500 500
8760 8760
0.0346 0.0346
0.0425 0.0425
658 658
Hyacinth Hyacinth
500 500
9110 9110
0.0346 0.0346
0.0425 0.0425
658 658
100941
Dahlia Dahlia
556.5 556.5
9750 9750
0.0311 0.0311
0.0382 0.0382
703 703
100966
Mistletoe Mistletoe
556.5 556.5
9940 9940
0.0311 0.0311
0.0382 0.0382
704 704
157743
Meadowsweet Meadowsweet
600 600
10700 10700
0.0288 0.0288
0.0355 0.0355
738 738
100974
Orchid Orchid
636 636
11400 11400
0.0272 0.0272
0.0335 0.0335
765 765
Heuchera Heuchera
650 650
11600 11600
0.0266 0.0266
0.0328 0.0328
775 775
Verbena Verbena
700 700
12500 12500
0.0247 0.0247
0.0305 0.0305
812 812
Flag Flag
700 700
12900 12900
0.0247 0.0247
0.0305 0.0305
812 812
Violet Violet
715.5 715.5
12800 12800
0.0242 0.0242
0.0299 0.0299
823 823
Nasturtium Nasturtium
715.5 715.5
13100 13100
0.0242 0.0242
0.0299 0.0299
823 823
182618 182618
Petunia Petunia
750 750
13100 13100
0.023 0.023
0.0286 0.0286
847 847
Cattail Cattail
750 750
13500 13500
0.023 0.023
0.0286 0.0286
847 847
100990
Arbutus Arbutus
795 795
13900 13900
0.0217 0.0217
0.027 0.027
878 878
Lilac Lilac
795 795
14300 14300
0.0217 0.0217
0.027 0.027
879 879
Cockscomb Cockscomb
900 900
15400 15400
0.0192 0.0192
0.0239 0.0239
948 948
Snapdragon Snapdragon
900 900
15900 15900
0.0192 0.0192
0.0239 0.0239
948 948
101014
Magnolia Magnolia
954 954
16400 16400
0.0181 0.0181
0.0226 0.0226
982 982
101063
Goldenrod Goldenrod
954 954
16900 16900
0.0181 0.0181
0.0226 0.0226
983 983
Hawkweed Hawkweed
1000 1000
17200 17200
0.0173 0.0173
0.0216 0.0216
1010 1010
Camellia Camellia
1000 1000
17700 17700
0.0713 0.0713
0.0216 0.0216
1011 1011
101022 101022
Bluebell Bluebell
1033.5 1033.5
17700 17700
0.0167 0.0167
0.021 0.021
1031 1031
Larkspur Larkspur
1033.5 1033.5
18300 18300
0.0167 0.0167
0.021 0.021
1032 1032
Marigold Marigold
1113 1113
19700 19700
0.0155 0.0155
0.0195 0.0195
1079 1079
Hawthorn Hawthorn
1192.5 1192.5
21100 21100
0.0145 0.0145
0.0183 0.0183
1124 1124
101105
Narcissus Narcissus
1272 1272
22000 22000
0.0136 0.0136
0.0173 0.0173
1169 1169
Columbine Columbine
1351.5 1351.5
23400 23400
0.0128 0.0128
0.0163 0.0163
1212 1212
Carnation Carnation
1431 1431
24300 24300
0.0121 0.0121
0.0155 0.0155
1253 1253
Gladiolus Gladiolus
1510.5 1510.5
25600 25600
0.0114 0.0114
0.0147 0.0147
1294 1294
101147
Coreopsis Coreopsis
1590 1590
27000 27000
0.0109 0.0109
0.0141 0.0141
1333 1333
182634
Jessamine Jessamine
1750 1750
29700 29700
0.00988 0.00988
0.0129 0.0129
1408 1408
Cowslip Cowslip
2000 2000
34200 34200
0.00864 0.00864
0.0115 0.0115
1518 1518
Sagebrush Sagebrush
2250 2250
37500 37500
0.00776 0.00776
0.0105 0.0105
1612 1612
182675
Lupine Lupine
2500 2500
41900 41900
0.00698 0.00698
0.00969 0.00969
1706 1706
Bitterroot Bitterroot
2750 2750
46100 46100
0.00635 0.00635
0.009 0.009
1793 1793
Trillium Trillium
3000 3000
50300 50300
0.00582 0.00582
0.00834 0.00834
1874 1874
Bluebonnet Bluebonnet
3500 3500
58700 58700
0.005 0.005
0.00756 0.00756
2024 2024

† Conductor temperature of 75ºC, ambient temperature 25ºC, emissivity 0.5, wind 2 ft./sec. in sun.

Standards & References

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors

Construction

  1. Conductor:Aluminum 1350-H19 wires, concentrically stranded.

Resources