SPEC: 80120

795-37 AAC ARBUTUS 1850 LB SPEC80120 10099003

Southwire #: 10099003

Download Category Specifications
PDF Excel Table
Select Product Specifications
Construction
Packaging

Application & Features

Classes1 AA and A are used primarily for overhead transmission and primary and secondary distribution, where ampacity must be maintained and a lighter conductor (compared to ACSR) is desired, and when conductor strength is not a critical factor. Classes B and C are used primarily as bus, apparatus connectors and jumpers, where additional flexibility is required.

1Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.

Specifications

Codeword ARBUTUS ARBUTUS
Size (AWG or kcmil) (mm2) 795 KCMIL 795 KCMIL
No. of Strands 37 37
Nom. OD (mils) (mm) 1026 26.07 mils mm
Nominal Total Weight (lbs/1000') (kgs/km) 745 1109 lbs/1000' kgs/km

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Standards & References

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors

Construction

  1. Conductor:Aluminum 1350-H19 wires, concentrically stranded.

Resources

There are no downloadable resources for this product.