SPEC: 48002

CU 600V LSZH RHH/RHW-2 SOLONONplus™ SPEC48002

SOLONONplus™ 600Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type RHH/RHW-2 USE-2

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 Volt SOLONONplus™ Type RHH/RHW-2 USE-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

a. The conductors are available in tinned and flexible copper stranding upon request.
b. NEC compliant
c. The halogen content is less than 0.2% and Acid gas less than 2.0%
d. 70,000 BTU/Hr. Vertical Flame Test
e. UL listed for CT use on 1/0 and Larger
f. UL listed FT4 and ST-1 (limited smoke)
g. -40°C Cold impact and cold bend
h. Gasoline and Oil Resistant GRI and GRII
i. UV/Sunlight resistant all colors
j. Color available upon request
k. Rated for direct burial

Specifications

Select a set of products below for more information:
Cond. Size Cond. Strands Strand Class Conductor Number Insulation Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) Max Pull Tension (lbs) (kg)
More Options
14 AWG 14 AWG
7 7
B B
1 1
45 1.14
0.164 0.42
24 36
2.631 3.92
32 14.51
More Options
12 AWG 12 AWG
7 7
B B
1 1
45 1.14
0.183 0.46
33 49
1.662 2.47
52 23.59
More Options
10 AWG 10 AWG
7 7
B B
1 1
45 1.14
0.207 0.53
47 70
1.040 1.55
83 37.65
More Options
8 AWG 8 AWG
7 7
B B
1 1
60 1.52
0.268 0.68
77 115
0.653 0.97
132 59.87
More Options
6 AWG 6 AWG
7 7
B B
1 1
60 1.52
0.304 0.77
112 167
0.411 0.61
209 94.80
More Options
4 AWG 4 AWG
7 7
B B
1 1
60 1.52
0.351 0.89
167 249
0.258 0.38
333 151.05
More Options
3 AWG 3 AWG
7 7
B B
1 1
60 1.52
0.378 0.96
204 304
0.205 0.31
420 190.51
More Options
2 AWG 2 AWG
7 7
B B
1 1
60 1.52
0.409 1.04
251 374
0.162 0.24
530 240.40
More Options
1 AWG 1 AWG
19 19
B B
1 1
80 2.03
0.490 1.24
329 490
0.128 0.19
669 303.45
More Options
1/0 AWG 1/0 AWG
19 19
B B
1 1
80 2.03
0.530 1.35
404 601
0.102 0.15
844 382.83
More Options
2/0 AWG 2/0 AWG
19 19
B B
1 1
80 2.03
0.574 1.46
497 740
0.081 0.12
1064 482.62
More Options
3/0 AWG 3/0 AWG
19 19
B B
1 1
80 2.03
0.624 1.58
614 914
0.064 0.10
1342 608.72
More Options
4/0 AWG 4/0 AWG
19 19
B B
1 1
80 2.03
0.680 1.73
759 1130
0.051 0.08
1692 767.48
More Options
250 KCMIL 250 KCMIL
37 37
B B
1 1
95 2.41
0.758 1.93
909 1353
0.043 0.06
2000 907.18
More Options
350 KCMIL 350 KCMIL
37 37
B B
1 1
95 2.41
0.841 2.14
1236 1839
0.031 0.05
2800 1270.06
More Options
500 KCMIL 500 KCMIL
37 37
B B
1 1
95 2.41
0.989 2.51
1733 2579
0.022 0.03
4000 1814.37
More Options
600 KCMIL 600 KCMIL
61 61
B B
1 1
110 2.79
1.098 2.79
2090 3110
0.018 0.03
4800 2177.24
More Options
750 KCMIL 750 KCMIL
61 61
B B
1 1
110 2.79
1.200 3.05
2579 3838
0.014 0.02
6000 2721.55
More Options
1000 KCMIL 1000 KCMIL
61 61
B B
1 1
110 2.79
1.349 3.43
3388 5042
0.011 0.02
8000 3628.74

Tinned Copper Conductor

Size (Strand) Black Red Blue White Brown Orange Yellow Gray Green
14 (7) 14 (7)
643665
646600 646600
677498 677498
677499 677499
12 (7) 12 (7)
643666
644382 644382
644383 644383
644389 644389
644384 644384
644386 644386
644387 644387
644388 644388
644381 644381
10 (7) 10 (7)
643667
644391 644391
644392 644392
644396 644396
644394 644394
644395 644395
646493 646493
646492 646492
644390 644390
8 (7) 8 (7)
643668
646602 646602
646603 646603
646605 646605
647101 647101
647102 647102
647103 647103
647104 647104
646601 646601
6 (7) 6 (7)
643669
646581 646581
646582 646582
646587 646587
646583 646583
646584 646584
646585 646585
646586 646586
644257 644257
4 (7) 4 (7)
643670
647105 647105
647106 647106
647108 647108
646595 646595
646597 646597
646598 646598
646599 646599
646594 646594
3 (7) 3 (7)
646618
647109 647109
647111 647111
647112 647112
646614 646614
646615 646615
646616 646616
646617 646617
646613 646613
2 (7) 2 (7)
643671
646590 646590
646591 646591
646592 646592
646593 646593
646589 646589
1 (19) 1 (19)
643672
647114 647114
647116 647116
647117 647117
646624 646624
646625 646625
646626 646626
646627 646627
647113 647113
1/0 (19) 1/0 (19)
643673
644398 644398
644399 644399
644400 644400
647118 647118
647119 647119
647120 647120
647121 647121
644397 644397
2/0 (19) 2/0 (19)
643674
647122 647122
647124 647124
647129 647129
647125 647125
647126 647126
647127 647127
647128 647128
649622 649622
3/0 (19) 3/0 (19)
643675
647130 647130
647132 647132
647133 647133
646619 646619
646621 646621
646622 646622
646623 646623
648905 648905
4/0 (19) 4/0 (19)
643677
647134 647134
647135 647135
647572 647572
647136 647136
647569 647569
647570 647570
647571 647571
644380 644380
250 (37) 250 (37)
643678
646606 646606
647573 647573
646607 646607
647574 647574
647575 647575
647576 647576
647577 647577
350 (37) 350 (37)
643679
647588 647588
647583 647583
647584 647584
647585 647585
647587 647587
500 (37) 500 (37)
643680
647589 647589
646608 646608
646609 646609
646610 646610
646611 646611
600 (61) 600 (61)
647653
647590 647590
647591 647591
647592 647592
647593 647593
750 (61) 750 (61)
643826
1000 (61) 1000 (61)
643827

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • ISO 14001 Environmental management systems standard
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways

Construction

  1. Conductor: Class B compressed stranded bare or tinned copper per ASTM B3, ASTM B8 and ASTM B33.
  2. Insulation: SOLONONplus™ Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type RHH/RHW-2 USE-2

Resources

There are no downloadable resources for this product.