SPEC: 48002

CU 600V LSZH RHH/RHW-2/RW90 SOLONONplus™ SPEC48002

SOLONONplus™ 600Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type RHH/RHW-2/RW90

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 Volt SOLONONplus™ Type RHH/RHW-2/RW90 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and as otherwise permitted by the NEC® for Type RHH/RHW-2 or the CE Code for Type RW90. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

a. The conductors are available in tinned and flexible copper stranding upon request.
b. NEC compliant
c. The halogen content is less than 0.2% and Acid gas less than 2.0%
d. 70,000 BTU/Hr. Vertical Flame Test
e. UL listed for CT use on 1/0 and Larger
f. UL listed FT4 and ST-1 (limited smoke)
g. -40°C Cold impact and cold bend
h. Gasoline and Oil Resistant GRI and GRII
i. UV/Sunlight resistant all colors
j. Color available upon request

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
14 AWG 14 AWG
1 1
7 7
0.070 0.18
45 1.14
0.165 0.42
12 18
24 36
More Options
12 AWG 12 AWG
1 1
7 7
0.088 0.22
45 1.14
0.183 0.46
20 30
33 49
More Options
10 AWG 10 AWG
1 1
7 7
0.113 0.29
45 1.14
0.207 0.53
32 48
47 70
More Options
8 AWG 8 AWG
1 1
7 7
0.141 0.36
60 1.52
0.268 0.68
50 74
77 115
More Options
6 AWG 6 AWG
1 1
7 7
0.177 0.45
60 1.52
0.304 0.77
81 121
112 167
More Options
4 AWG 4 AWG
1 1
7 7
0.225 0.57
60 1.52
0.351 0.89
128 190
167 249
More Options
3 AWG 3 AWG
1 1
7 7
0.252 0.64
60 1.52
0.378 0.96
162 241
204 304
More Options
2 AWG 2 AWG
1 1
7 7
0.282 0.72
60 1.52
0.409 1.04
204 304
251 374
More Options
1 AWG 1 AWG
1 1
19 19
0.322 0.82
80 2.03
0.490 1.24
258 384
329 490
More Options
1/0 AWG 1/0 AWG
1 1
19 19
0.361 0.92
80 2.03
0.530 1.35
326 485
404 601
More Options
2/0 AWG 2/0 AWG
1 1
19 19
0.405 1.03
80 2.03
0.574 1.46
410 610
497 740
More Options
3/0 AWG 3/0 AWG
1 1
19 19
0.456 1.16
80 2.03
0.624 1.58
518 771
614 914
More Options
4/0 AWG 4/0 AWG
1 1
19 19
0.512 1.30
80 2.03
0.680 1.73
653 972
759 1130
More Options
250 KCMIL 250 KCMIL
1 1
37 37
0.558 1.42
95 2.41
0.758 1.93
771 1147
909 1353
More Options
350 KCMIL 350 KCMIL
1 1
37 37
0.661 1.68
95 2.41
0.841 2.14
1080 1607
1236 1839
More Options
500 KCMIL 500 KCMIL
1 1
37 37
0.789 2.00
95 2.41
0.995 2.53
1543 2296
1733 2579
More Options
600 KCMIL 600 KCMIL
1 1
61 61
0.865 2.20
110 2.79
1.072 2.72
1852 2756
2084 3101
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.968 2.46
110 2.79
1.200 3.05
2315 3445
2579 3838
More Options
1000 KCMIL 1000 KCMIL
1 1
61 61
1.117 2.84
110 2.79
1.349 3.43
3087 4594
3388 5042

Tinned Copper Conductor
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
14 AWG 14 AWG
1 1
0.7 1.78
32 14.51
2.631 3.92
3.170 4.72
0.058 0.09
20 20
25 25
More Options
12 AWG 12 AWG
1 1
0.7 1.78
52 23.59
1.662 2.47
2.002 2.98
0.054 0.08
25 25
30 30
More Options
10 AWG 10 AWG
1 1
0.8 2.03
83 37.65
1.040 1.55
1.253 1.86
0.050 0.07
35 35
40 40
More Options
8 AWG 8 AWG
1 1
1.1 2.79
132 59.87
0.653 0.97
0.786 1.17
0.052 0.08
50 50
55 55
More Options
6 AWG 6 AWG
1 1
1.2 3.05
209 94.80
0.411 0.61
0.495 0.74
0.051 0.08
65 65
75 75
More Options
4 AWG 4 AWG
1 1
1.4 3.56
333 151.05
0.258 0.38
0.310 0.46
0.048 0.07
85 85
95 95
More Options
3 AWG 3 AWG
1 1
1.5 3.81
420 190.51
0.205 0.31
0.246 0.37
0.047 0.07
100 100
115 115
More Options
2 AWG 2 AWG
1 1
1.6 4.06
530 240.40
0.162 0.24
0.195 0.29
0.045 0.07
115 115
130 130
More Options
1 AWG 1 AWG
1 1
2.0 5.08
669 303.45
0.128 0.19
0.154 0.23
0.046 0.07
130 130
145 145
More Options
1/0 AWG 1/0 AWG
1 1
2.1 5.33
844 382.83
0.102 0.15
0.122 0.18
0.044 0.07
150 150
170 170
More Options
2/0 AWG 2/0 AWG
1 1
2.3 5.84
1064 482.62
0.081 0.12
0.097 0.14
0.043 0.06
175 175
195 195
More Options
3/0 AWG 3/0 AWG
1 1
2.5 6.35
1342 608.72
0.064 0.10
0.078 0.12
0.042 0.06
200 200
225 225
More Options
4/0 AWG 4/0 AWG
1 1
2.7 6.86
1692 767.48
0.051 0.08
0.062 0.09
0.041 0.06
230 230
260 260
More Options
250 KCMIL 250 KCMIL
1 1
3.0 7.62
2000 907.18
0.043 0.06
0.053 0.08
0.041 0.06
255 255
290 290
More Options
350 KCMIL 350 KCMIL
1 1
3.4 8.64
2800 1270.06
0.031 0.05
0.039 0.06
0.040 0.06
310 310
350 350
More Options
500 KCMIL 500 KCMIL
1 1
4.0 10.16
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
600 KCMIL 600 KCMIL
1 1
5.4 13.72
4800 2177.24
0.018 0.03
0.025 0.04
0.039 0.06
420 420
475 475
More Options
750 KCMIL 750 KCMIL
1 1
6.0 15.24
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
More Options
1000 KCMIL 1000 KCMIL
1 1
6.7 17.02
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615

† Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
† Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • ISO 14001 Environmental management systems standard
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways (non-emergency circuits only)

Construction

  1. Conductor:Class B compressed stranded bare or tinned copper per ASTM B3, ASTM B8 and ASTM B33.
  2. Insulation:SOLONONplus™ Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type RHH/RHW-2/RW90

Resources

There are no downloadable resources for this product.