SPEC: 45262

TCU 600/1000V EPR Insulation Thermoplastic CPE-TP Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free SPEC45262

Type TC-ER Power Cable 600Volt Four Conductor Copper, Ethylene Propylene Rubber (EPR) insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket with 1 Tinned CU Ground. VW-1 rated

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 rated

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
4 4
7 7
0.141 0.36
45 1.14
60 1.52
0.724 1.84
238 354
385 573
More Options
6 AWG 6 AWG
4 4
7 7
0.177 0.45
45 1.14
60 1.52
0.816 2.07
378 563
553 823
More Options
4 AWG 4 AWG
4 4
7 7
0.225 0.57
45 1.14
80 2.03
0.936 2.38
572 851
802 1194
More Options
2 AWG 2 AWG
4 4
7 7
0.282 0.72
45 1.14
80 2.03
1.123 2.85
909 1353
1214 1807
More Options
1 AWG 1 AWG
4 4
19 19
0.322 0.82
55 1.40
80 2.03
1.279 3.25
1125 1674
1527 2272
More Options
1/0 AWG 1/0 AWG
4 4
19 19
0.361 0.92
55 1.40
80 2.03
1.357 3.45
1399 2082
1828 2720
More Options
2/0 AWG 2/0 AWG
4 4
19 19
0.405 1.03
55 1.40
80 2.03
1.464 3.72
1742 2592
2210 3289
More Options
4/0 AWG 4/0 AWG
4 4
19 19
0.512 1.30
55 1.40
110 2.79
1.740 4.42
2769 4121
3369 5014
More Options
250 KCMIL 250 KCMIL
4 4
37 37
0.558 1.42
65 1.65
110 2.79
1.939 4.93
3248 4834
4006 5962
More Options
350 KCMIL 350 KCMIL
4 4
37 37
0.661 1.68
65 1.65
110 2.79
2.202 5.59
4530 6741
5420 8066
More Options
500 KCMIL 500 KCMIL
4 4
37 37
0.789 2.00
65 1.65
110 2.79
2.464 6.26
6443 9588
7386 10992
More Options
600 KCMIL 600 KCMIL
4 4
61 61
0.865 2.20
80 2.03
140 3.56
2.790 7.09
7691 11445
9439 14047
Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
8 AWG 8 AWG
4 4
2.9 7.37
422 191.42
0.653 0.97
0.786 1.17
0.052 0.08
40 40
44 44
More Options
6 AWG 6 AWG
4 4
3.3 8.38
671 304.36
0.411 0.61
0.495 0.74
0.051 0.08
52 52
60 60
More Options
4 AWG 4 AWG
4 4
3.7 9.40
1068 484.44
0.258 0.38
0.310 0.46
0.048 0.07
68 68
76 76
More Options
2 AWG 2 AWG
4 4
5.6 14.22
1698 770.20
0.162 0.24
0.195 0.29
0.045 0.07
92 92
104 104
More Options
1 AWG 1 AWG
4 4
6.4 16.26
2142 971.59
0.128 0.19
0.154 0.23
0.046 0.07
104 104
116 116
More Options
1/0 AWG 1/0 AWG
4 4
6.8 17.27
2703 1226.06
0.102 0.15
0.122 0.18
0.044 0.07
120 120
136 136
More Options
2/0 AWG 2/0 AWG
4 4
7.3 18.54
3407 1545.39
0.081 0.12
0.097 0.14
0.043 0.06
140 140
156 156
More Options
4/0 AWG 4/0 AWG
4 4
8.7 22.10
5416 2456.65
0.051 0.08
0.062 0.09
0.041 0.06
184 184
208 208
More Options
250 KCMIL 250 KCMIL
4 4
9.7 24.64
6400 2902.99
0.043 0.06
0.053 0.08
0.041 0.06
204 204
232 232
More Options
350 KCMIL 350 KCMIL
4 4
13.2 33.53
8960 4064.18
0.031 0.05
0.039 0.06
0.040 0.06
248 248
280 280
More Options
500 KCMIL 500 KCMIL
4 4
14.8 37.59
12800 5805.98
0.022 0.03
0.029 0.04
0.039 0.06
304 304
344 344
More Options
600 KCMIL 600 KCMIL
4 4
16.7 42.42
15360 6967.17
0.018 0.03
0.025 0.04
0.039 0.06
336 336
380 380

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
  2. Insulation: Ethylene Propylene Rubber (EPR) Type XHHW-2
  3. Grounding Conductor: Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
  4. Filler: Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder: Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket: Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket