SPEC: 45262

TCU 600/1000V EPR Insulation XHHW-2 Thermoplastic CPE-TP Jacket. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free SPEC45262

Type TC-ER Power Cable, 600/1000 Volt, Four Conductor, Tinned Copper, Ethylene Propylene Rubber (EPR) Insulation, XHHW-2, Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket with 1 Tinned CU Ground, VW-1 rated

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600/1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 rated

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Ground Size Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
4 4
7 7
0.142 0.36
45 1.14
1x10 1x10
60 1.52
0.724 1.84
238 354
389 579
More Options
6 AWG 6 AWG
4 4
7 7
0.178 0.45
45 1.14
1x8 1x8
60 1.52
0.816 2.07
379 564
553 823
More Options
4 AWG 4 AWG
4 4
7 7
0.225 0.57
45 1.14
1x8 1x8
80 2.03
0.936 2.38
572 851
803 1195
More Options
2 AWG 2 AWG
4 4
7 7
0.283 0.72
45 1.14
1x6 1x6
80 2.03
1.123 2.85
910 1354
1214 1807
More Options
1 AWG 1 AWG
4 4
19 19
0.322 0.82
55 1.40
1x6 1x6
80 2.03
1.279 3.25
1126 1676
1532 2280
More Options
1/0 AWG 1/0 AWG
4 4
19 19
0.362 0.92
55 1.40
1x6 1x6
80 2.03
1.357 3.45
1399 2082
1828 2720
More Options
2/0 AWG 2/0 AWG
4 4
19 19
0.405 1.03
55 1.40
1x6 1x6
80 2.03
1.464 3.72
1742 2592
2216 3298
More Options
4/0 AWG 4/0 AWG
4 4
19 19
0.512 1.30
55 1.40
1x4 1x4
110 2.79
1.74 4.42
2770 4122
3376 5024
More Options
250 KCMIL 250 KCMIL
4 4
37 37
0.558 1.42
65 1.65
1x4 1x4
110 2.79
1.939 4.93
3249 4835
4016 5976
More Options
350 KCMIL 350 KCMIL
4 4
37 37
0.661 1.68
65 1.65
1x3 1x3
110 2.79
2.202 5.59
4530 6741
5421 8067
More Options
500 KCMIL 500 KCMIL
4 4
37 37
0.789 2.00
65 1.65
1x2 1x2
110 2.79
2.464 6.26
6444 9590
7386 10992
More Options
600 KCMIL 600 KCMIL
4 4
61 61
0.866 2.20
80 2.03
1x2 1x2
140 3.56
2.791 7.09
7691 11445
9205 13699

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
8 AWG 8 AWG
4 4
2.9 7.37
528 239.50
0.653 0.97
0.810 1.21
0.052 0.08
40 40
44 44
More Options
6 AWG 6 AWG
4 4
3.3 8.38
839 380.56
0.411 0.61
0.510 0.76
0.051 0.08
52 52
60 60
More Options
4 AWG 4 AWG
4 4
3.7 9.40
1335 605.55
0.258 0.38
0.320 0.48
0.048 0.07
68 68
76 76
More Options
2 AWG 2 AWG
4 4
5.6 14.22
2123 962.98
0.162 0.24
0.201 0.30
0.045 0.07
92 92
104 104
More Options
1 AWG 1 AWG
4 4
6.4 16.26
2678 1214.72
0.128 0.19
0.159 0.24
0.046 0.07
104 104
116 116
More Options
1/0 AWG 1/0 AWG
4 4
6.8 17.27
3379 1532.69
0.102 0.15
0.127 0.19
0.044 0.07
120 120
136 136
More Options
2/0 AWG 2/0 AWG
4 4
7.3 18.54
4259 1931.85
0.082 0.12
0.102 0.15
0.043 0.06
140 140
156 156
More Options
4/0 AWG 4/0 AWG
4 4
8.7 22.10
6771 3071.27
0.051 0.08
0.063 0.09
0.041 0.06
184 184
208 208
More Options
250 KCMIL 250 KCMIL
4 4
9.7 24.64
8000 3628.74
0.043 0.06
0.053 0.08
0.041 0.06
204 204
232 232
More Options
350 KCMIL 350 KCMIL
4 4
13.2 33.53
11200 5080.23
0.031 0.05
0.039 0.06
0.040 0.06
248 248
280 280
More Options
500 KCMIL 500 KCMIL
4 4
14.8 37.59
16000 7257.47
0.021 0.03
0.027 0.04
0.039 0.06
304 304
344 344
More Options
600 KCMIL 600 KCMIL
4 4
16.7 42.42
19200 8708.97
0.018 0.03
0.024 0.04
0.039 0.06
336 336
380 380

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor:Class B compressed stranded tinned copper per ASTM B33 and B8
  2. Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded tinned copper per ASTM B33 and B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)