Southwire’s ACWU 90 cables are primarily intended for exposed and concealed wiring in dry or wet locations and where exposed to the weather. For use in ventilated, non-ventilated, ladder type cable trays and in all hazardous locations; direct earth burial; service entrance above or below ground.
| Cond. Size | Conductor Number | Diameter Over Conductor (in) (cm) | Cond. Strands | Insulation Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
350 AWG
350 AWG
|
3
3
|
0.615
1.56
|
35
35
|
65
1.65
|
1.947
4.95
|
2.137
5.43
|
2025
3014
|
| More Options |
250 AWG
250 AWG
|
4
4
|
0.52
1.32
|
22
22
|
65
1.65
|
1.905
4.84
|
2.095
5.32
|
1988
2958
|
| More Options |
2 AWG
2 AWG
|
3
3
|
0.268
0.68
|
6
6
|
45
1.14
|
1.107
2.81
|
1.267
3.22
|
631
939
|
| More Options |
2 AWG
2 AWG
|
4
4
|
0.268
0.68
|
6
6
|
45
1.14
|
1.204
3.06
|
1.364
3.46
|
747
1112
|
| More Options |
1 AWG
1 AWG
|
3
3
|
0.298
0.76
|
8
8
|
55
1.40
|
1.223
3.11
|
1.383
3.51
|
754
1122
|
| More Options |
1 AWG
1 AWG
|
4
4
|
0.298
0.76
|
8
8
|
55
1.40
|
1.327
3.37
|
1.487
3.78
|
897
1335
|
| More Options |
1/0 AWG
1/0 AWG
|
3
3
|
0.336
0.85
|
10
10
|
55
1.40
|
1.295
3.29
|
1.455
3.70
|
847
1260
|
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
0.336
0.85
|
10
10
|
55
1.40
|
1.408
3.58
|
1.577
4.01
|
1031
1534
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
0.376
0.96
|
12
12
|
55
1.40
|
1.381
3.51
|
1.548
3.93
|
976
1452
|
| More Options |
2/0 AWG
2/0 AWG
|
4
4
|
0.376
0.96
|
12
12
|
55
1.40
|
1.513
3.84
|
1.703
4.33
|
1230
1830
|
| More Options |
3/0 AWG
3/0 AWG
|
3
3
|
0.422
1.07
|
16
16
|
55
1.40
|
1.483
3.77
|
1.65
4.19
|
1122
1670
|
| More Options |
250 KCMIL
250 KCMIL
|
3
3
|
0.52
1.32
|
22
22
|
65
1.65
|
1.73
4.39
|
1.92
4.88
|
1572
2339
|
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
350 AWG
350 AWG
|
3
3
|
12.8
32.51
|
6300
2857.63
|
0.050
0.07
|
0.062
0.09
|
0.040
0.06
|
250
250
|
280
280
|
| More Options |
250 AWG
250 AWG
|
4
4
|
12.5
31.75
|
6000
2721.55
|
0.071
0.11
|
0.086
0.13
|
0.041
0.06
|
164
164
|
184
184
|
| More Options |
2 AWG
2 AWG
|
3
3
|
6.3
16.00
|
1194
541.59
|
0.267
0.40
|
0.321
0.48
|
0.045
0.07
|
90
90
|
100
100
|
| More Options |
2 AWG
2 AWG
|
4
4
|
6.8
17.27
|
1592
722.12
|
0.267
0.40
|
0.321
0.48
|
0.045
0.07
|
72
72
|
80
80
|
| More Options |
1 AWG
1 AWG
|
3
3
|
6.9
17.53
|
1506
683.11
|
0.211
0.31
|
0.254
0.38
|
0.046
0.07
|
100
100
|
115
115
|
| More Options |
1 AWG
1 AWG
|
4
4
|
7.4
18.80
|
2008
910.81
|
0.211
0.31
|
0.254
0.38
|
0.046
0.07
|
80
80
|
92
92
|
| More Options |
1/0 AWG
1/0 AWG
|
3
3
|
7.2
18.29
|
1900
861.82
|
0.168
0.25
|
0.201
0.30
|
0.044
0.07
|
120
120
|
135
135
|
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
7.8
19.81
|
2534
1149.40
|
0.168
0.25
|
0.201
0.30
|
0.044
0.07
|
96
96
|
108
108
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
7.7
19.56
|
2395
1086.35
|
0.133
0.20
|
0.160
0.24
|
0.043
0.06
|
135
135
|
150
150
|
| More Options |
2/0 AWG
2/0 AWG
|
4
4
|
8.5
21.59
|
3194
1448.77
|
0.133
0.20
|
0.160
0.24
|
0.043
0.06
|
108
108
|
120
120
|
| More Options |
3/0 AWG
3/0 AWG
|
3
3
|
8.2
20.83
|
3020
1369.85
|
0.105
0.16
|
0.126
0.19
|
0.042
0.06
|
155
155
|
175
175
|
| More Options |
250 KCMIL
250 KCMIL
|
3
3
|
9.6
24.38
|
4500
2041.16
|
0.071
0.11
|
0.086
0.13
|
0.041
0.06
|
205
205
|
230
230
|
† Ampacities have been adjusted for more than Three Current-Carrying Conductors
† Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.