Alumaflex™ Type MC AL Feeder THHN/THWN-2 Conductors MC26

1/0 AWG through 900 kcmil AlumaFlex™ THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor.

Download Category Specifications
PDF Excel Table

Application & Features

Suitable for use as follows:

  • Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Power, lighting circuits.
  • Fished or embedded in plaster
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations

Specifications

Select a set of products below for more information:
Conductor Ground Wire Neutral Wire
Size (AWG or kcmil) (mm2) No. of Conductors Stranding Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Size (AWG) Ground Size UOM Size (AWG) Conductor Colors
More Options
1 AWG 1 AWG
4 4
Stranded Stranded
1341 34.06
724 1078
4 4
AWG AWG
BRN, ORG, YLW, GRY, 4 GRN GND, 0 BRN, ORG, YLW, GRY, 4 GRN GND, 0
More Options
2/0 AWG 2/0 AWG
3 3
Stranded Stranded
1318 33.48
705 1049
4 4
AWG AWG
BLK/RED/WHT/4 GRN GND BLK/RED/WHT/4 GRN GND
More Options
2/0 AWG 2/0 AWG
4 4
Stranded Stranded
1540 39.12
1043 1552
4 4
AWG AWG
BRN/ORG/YLW/GRY/4 GRN GND 0 BRN/ORG/YLW/GRY/4 GRN GND 0
More Options
3/0 AWG 3/0 AWG
3 3
Stranded Stranded
1469 37.31
898 1336
4 4
AWG AWG
BRN/ORG/YLW/4 GRN GND BRN/ORG/YLW/4 GRN GND
More Options
4/0 AWG 4/0 AWG
3 3
Stranded Stranded
1584 40.23
1130 1682
1 1
AWG AWG
4/0 4/0
BLK/RED/WHT/ 1 BARE GND BLK/RED/WHT/ 1 BARE GND
More Options
250 KCMIL 250 KCMIL
3 3
Stranded Stranded
1789 45.44
1396 2077
1/0 1/0
AWG AWG
BRN/ORG/YLW/1/0 GRN GND BRN/ORG/YLW/1/0 GRN GND
More Options
250 KCMIL 250 KCMIL
4 4
Stranded Stranded
1962 49.83
1792 2667
3/0 3/0
AWG AWG
250 250
BLK/RED/BLU/WHT/ 3/0 BARE GNDND, 0 BLK/RED/BLU/WHT/ 3/0 BARE GNDND, 0
More Options
300 KCMIL 300 KCMIL
3 3
Stranded Stranded
1842 46.79
1522 2265
2 2
AWG AWG
BRN/ORG/YLW/2 GRN GND BRN/ORG/YLW/2 GRN GND
More Options
350 KCMIL 350 KCMIL
3 3
Stranded Stranded
1929 49.00
1666 2479
2 2
AWG AWG
BRN/ORG/YLW/ 2 BARE GND BRN/ORG/YLW/ 2 BARE GND
More Options
350 KCMIL 350 KCMIL
4 4
Stranded Stranded
2200 55.88
2320 3452
4/0 4/0
AWG AWG
BLK/RED/BLU/WHT/ 4/0 BARE GNDND, 0 BLK/RED/BLU/WHT/ 4/0 BARE GNDND, 0
More Options
400 KCMIL 400 KCMIL
3 3
Stranded Stranded
2041 51.84
1944 2893
3/0 3/0
AWG AWG
BLK/RED/WHT/ 3/0 BARE GND BLK/RED/WHT/ 3/0 BARE GND
More Options
400 KCMIL 400 KCMIL
4 4
Stranded Stranded
2353 59.77
2627 3910
4/0 4/0
AWG AWG
BRN/ORG/YLW/GRY/4/0 GRN GNDD BRN/ORG/YLW/GRY/4/0 GRN GNDD
More Options
500 KCMIL 500 KCMIL
3 3
Stranded Stranded
2188 55.58
2258 3360
2/0 2/0
AWG AWG
BRN/ORG/YLW/ 2/0 BARE GND BRN/ORG/YLW/ 2/0 BARE GND
More Options
500 KCMIL 500 KCMIL
4 4
Stranded Stranded
2487 63.17
3051 4540
250 250
KCMIL KCMIL
500 500
BRN/ORG/YLW/GRY/ 250 BARE GNDND, 0 BRN/ORG/YLW/GRY/ 250 BARE GNDND, 0
More Options
600 KCMIL 600 KCMIL
3 3
Stranded Stranded
2635 66.93
3356 4994
600 600
KCMIL KCMIL
BRN/ORG/YLW/GRN BRN/ORG/YLW/GRN
More Options
600 KCMIL 600 KCMIL
4 4
Stranded Stranded
2912 73.96
4118 6129
600 600
KCMIL KCMIL
600 600
BRN/ORG/YLW/GRY/GRN BRN/ORG/YLW/GRY/GRN
More Options
600 KCMIL 600 KCMIL
4 4
Stranded Stranded
2688 68.28
3634 5408
250 250
KCMIL KCMIL
BLK/RED/BLU/WHT/ 250 BARE GND/0 BLK/RED/BLU/WHT/ 250 BARE GND/0
More Options
750 KCMIL 750 KCMIL
3 3
Stranded Stranded
2608 66.24
3205 4770
1/0 1/0
AWG AWG
BRN/ORG/YLW/1/0 GRN GND BRN/ORG/YLW/1/0 GRN GND
More Options
750 KCMIL 750 KCMIL
4 4
Stranded Stranded
3059 77.70
4658 6932
600 600
KCMIL KCMIL
BLK/RED/BLU/WHT/ 600 BARE GNDND, 0 BLK/RED/BLU/WHT/ 600 BARE GNDND, 0

Standards & References

Southwire AlumaFlex™ Type MC Cable with Triple E™ Aluminum Alloy meets or exceeds these requirements:

  • UL 83
  • UL 1569
  • UL 1685
  • Federal Specification A-A59544 (formerly J-C-30B)
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • NFPA 70 (National Electrical Code), Article 330
  • REACH/RoHS-2 (Chemical Limit) Compliant
  • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Firestop Systems

Construction

Southwire AlumaFlex™ Type MC Cable with Triple E™ Aluminum Alloy is constructed with Type THHN/THWN-2 conductors rated 90˚ C dry, and a bare equipment grounding conductor. Conductors are AlumaFlex™ AA-8000 series aluminum alloy compact stranded. A binder tape is wrapped over the conductors. Aluminum interlocking armor is applied over the assembly. Conductors also available in High Voltage Colors.