Alumaflex™ Type MC AL Feeder THHN/THWN-2 Conductors

1/0 AWG through 900 kcmil AlumaFlex™ THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor.

Download Category Specifications
PDF Excel Table

Application & Features

Suitable for use as follows:

  • Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Power, lighting circuits.
  • Fished or embedded in plaster
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations

Specifications

Select a set of products below for more information:
Conductor Ground Wire Neutral Wire
Size (AWG or kcmil) (mm2) No. of Conductors Stranding Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Size (AWG) Ground Size UOM Size (AWG) Conductor Colors
More Options
1 AWG 1 AWG
4 4
Stranded Stranded
1341 34.06
724 1078
4 4
AWG AWG
BRN, ORG, YLW, GRY, 4 GRN GND, 0 BRN, ORG, YLW, GRY, 4 GRN GND, 0
More Options
2/0 AWG 2/0 AWG
3 3
Stranded Stranded
1318 33.48
705 1049
4 4
AWG AWG
BLK/RED/WHT/4 GRN GND BLK/RED/WHT/4 GRN GND
More Options
2/0 AWG 2/0 AWG
4 4
Stranded Stranded
1540 39.12
1043 1552
4 4
AWG AWG
BRN/ORG/YLW/GRY/4 GRN GND 0 BRN/ORG/YLW/GRY/4 GRN GND 0
More Options
3/0 AWG 3/0 AWG
3 3
Stranded Stranded
1469 37.31
898 1336
4 4
AWG AWG
BRN/ORG/YLW/4 GRN GND BRN/ORG/YLW/4 GRN GND
More Options
4/0 AWG 4/0 AWG
3 3
Stranded Stranded
1584 40.23
1130 1682
1 1
AWG AWG
4/0 4/0
BLK/RED/WHT/ 1 BARE GND BLK/RED/WHT/ 1 BARE GND
More Options
4/0 AWG 4/0 AWG
4 4
Stranded Stranded
1786 45.36
1429 2127
2 2
AWG AWG
3/0 3/0
BLK/RED/BLU/WHT/2 GRN GND 0 BLK/RED/BLU/WHT/2 GRN GND 0
More Options
250 KCMIL 250 KCMIL
3 3
Stranded Stranded
1789 45.44
1396 2077
1/0 1/0
AWG AWG
BRN/ORG/YLW/1/0 GRN GND BRN/ORG/YLW/1/0 GRN GND
More Options
250 KCMIL 250 KCMIL
4 4
Stranded Stranded
1962 49.83
1792 2667
3/0 3/0
AWG AWG
250 250
BLK/RED/BLU/WHT/ 3/0 BARE GNDND, 0 BLK/RED/BLU/WHT/ 3/0 BARE GNDND, 0
More Options
300 KCMIL 300 KCMIL
3 3
Stranded Stranded
1842 46.79
1522 2265
2 2
AWG AWG
BRN/ORG/YLW/2 GRN GND BRN/ORG/YLW/2 GRN GND
More Options
350 KCMIL 350 KCMIL
3 3
Stranded Stranded
1929 49.00
1666 2479
2 2
AWG AWG
BRN/ORG/YLW/ 2 BARE GND BRN/ORG/YLW/ 2 BARE GND
More Options
350 KCMIL 350 KCMIL
4 4
Stranded Stranded
2200 55.88
2320 3452
4/0 4/0
AWG AWG
BLK/RED/BLU/WHT/ 4/0 BARE GNDND, 0 BLK/RED/BLU/WHT/ 4/0 BARE GNDND, 0
More Options
400 KCMIL 400 KCMIL
3 3
Stranded Stranded
2041 51.84
1944 2893
3/0 3/0
AWG AWG
BLK/RED/WHT/ 3/0 BARE GND BLK/RED/WHT/ 3/0 BARE GND
More Options
400 KCMIL 400 KCMIL
4 4
Stranded Stranded
2353 59.77
2627 3910
4/0 4/0
AWG AWG
BRN/ORG/YLW/GRY/4/0 GRN GNDD BRN/ORG/YLW/GRY/4/0 GRN GNDD
More Options
500 KCMIL 500 KCMIL
3 3
Stranded Stranded
2188 55.58
2258 3360
2/0 2/0
AWG AWG
BRN/ORG/YLW/ 2/0 BARE GND BRN/ORG/YLW/ 2/0 BARE GND
More Options
500 KCMIL 500 KCMIL
4 4
Stranded Stranded
2487 63.17
3051 4540
250 250
KCMIL KCMIL
500 500
BRN/ORG/YLW/GRY/ 250 BARE GNDND, 0 BRN/ORG/YLW/GRY/ 250 BARE GNDND, 0
More Options
600 KCMIL 600 KCMIL
3 3
Stranded Stranded
2635 66.93
3356 4994
600 600
KCMIL KCMIL
BRN/ORG/YLW/GRN BRN/ORG/YLW/GRN
More Options
600 KCMIL 600 KCMIL
4 4
Stranded Stranded
2912 73.96
4118 6129
600 600
KCMIL KCMIL
600 600
BRN/ORG/YLW/GRY/GRN BRN/ORG/YLW/GRY/GRN
More Options
600 KCMIL 600 KCMIL
4 4
Stranded Stranded
2688 68.28
3634 5408
250 250
KCMIL KCMIL
BLK/RED/BLU/WHT/ 250 BARE GND/0 BLK/RED/BLU/WHT/ 250 BARE GND/0
More Options
750 KCMIL 750 KCMIL
3 3
Stranded Stranded
2608 66.24
3205 4770
1/0 1/0
AWG AWG
BRN/ORG/YLW/1/0 GRN GND BRN/ORG/YLW/1/0 GRN GND
More Options
750 KCMIL 750 KCMIL
4 4
Stranded Stranded
3059 77.70
4658 6932
600 600
KCMIL KCMIL
BLK/RED/BLU/WHT/ 600 BARE GNDND, 0 BLK/RED/BLU/WHT/ 600 BARE GNDND, 0

Standards & References

Southwire AlumaFlex™ Type MC Cable with Triple E™ Aluminum Alloy meets or exceeds these requirements:

  • UL 83
  • UL 1569
  • UL 1685
  • Federal Specification A-A59544 (formerly J-C-30B)
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • NFPA 70 (National Electrical Code), Article 330
  • REACH/RoHS-2 (Chemical Limit) Compliant
  • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Firestop Systems

Construction

Southwire AlumaFlex™ Type MC Cable with Triple E™ Aluminum Alloy is constructed with Type THHN/THWN-2 conductors rated 90˚ C dry, and a bare equipment grounding conductor. Conductors are AlumaFlex™ AA-8000 series aluminum alloy compact stranded. A binder tape is wrapped over the conductors. Aluminum interlocking armor is applied over the assembly. Conductors also available in High Voltage Colors.

Resources

There are no downloadable resources for this product.