Bare Copper Conductor. Solid or Stranded.
Solid and stranded (classes AA and A) bare copper are suitable for overhead transmission and distribution applications. Stranded conductor of greater flexibility (classes B and C) are suitable for uninsulated hook up, jumpers, and grounds in electrical construction. Soft Drawn copper is unilay construction.
Conductor | ||||||||||
Size (AWG or kcmil) | No. of Strands | Stranding Class | Strand Type | Temper | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | Rated Strength (lbs) (kg) | DC Resistance at 20°C (ohms/1000') (ohms/km) | |
106146 |
14 AWG
14 AWG
|
1
1
|
A
A
|
SOL
SOL
|
SD
SD
|
64
1.63
|
12
19
|
|
124.2
56.34
|
2.525
3.76
|
106203 |
12 AWG
12 AWG
|
1
1
|
A
A
|
SOL
SOL
|
SD
SD
|
80
2.05
|
20
29
|
|
197.5
89.58
|
1.588
2.36
|
106260 |
10 AWG
10 AWG
|
1
1
|
A
A
|
SOL
SOL
|
SD
SD
|
101
2.59
|
31
47
|
|
314
142.43
|
0.999
1.49
|
106328 |
8 AWG
8 AWG
|
1
1
|
A
A
|
SOL
SOL
|
SD
SD
|
128
3.26
|
50
74
|
95
95
|
479.8
217.63
|
0.628
0.93
|
106567 |
8 AWG
8 AWG
|
7
7
|
B
B
|
CONV
CONV
|
SD
SD
|
148
3.77
|
51
76
|
95
95
|
499
226.34
|
0.6408
0.95
|
106385 |
6 AWG
6 AWG
|
1
1
|
A
A
|
SOL
SOL
|
SD
SD
|
161
4.11
|
79
118
|
125
125
|
762.9
346.05
|
0.395
0.59
|
106658 |
6 AWG
6 AWG
|
7
7
|
B
B
|
CONV
CONV
|
SD
SD
|
183
4.66
|
81
121
|
130
130
|
794
360.15
|
0.403
0.60
|
106443 |
4 AWG
4 AWG
|
1
1
|
A
A
|
SOL
SOL
|
SD
SD
|
204
5.19
|
126
188
|
170
170
|
1213
550.21
|
0.249
0.37
|
106740 |
4 AWG
4 AWG
|
7
7
|
B
B
|
CONV
CONV
|
SD
SD
|
231
5.88
|
129
192
|
170
170
|
1320
598.74
|
0.2534
0.38
|
106476 |
3 AWG
3 AWG
|
1
1
|
A
A
|
SOL
SOL
|
SD
SD
|
229
5.83
|
159
237
|
195
195
|
1530
694.00
|
0.197
0.29
|
106807 |
3 AWG
3 AWG
|
7
7
|
B
B
|
CONV
CONV
|
SD
SD
|
260
6.61
|
162
242
|
200
200
|
1670
757.50
|
0.201
0.30
|
106500 |
2 AWG
2 AWG
|
1
1
|
A
A
|
SOL
SOL
|
SD
SD
|
257
6.54
|
201
299
|
225
225
|
1929
874.98
|
0.156
0.23
|
106864 |
2 AWG
2 AWG
|
7
7
|
B
B
|
CONV
CONV
|
SD
SD
|
292
7.42
|
205
305
|
230
230
|
2110
957.08
|
0.1578
0.23
|
106955 |
1/0 AWG
1/0 AWG
|
7
7
|
A
A
|
CONV
CONV
|
SD
SD
|
368
9.36
|
326
485
|
310
310
|
3221
1461.02
|
0.1002
0.15
|
136168 |
1/0 AWG
1/0 AWG
|
19
19
|
B
B
|
COMBUL
COMBUL
|
SD
SD
|
360
9.14
|
338
503
|
355
355
|
4024
1825.25
|
0.07949
0.12
|
106989 |
2/0 AWG
2/0 AWG
|
7
7
|
A
A
|
CONV
CONV
|
SD
SD
|
413
10.51
|
411
612
|
355
355
|
4062
1842.49
|
0.07949
0.12
|
144519 |
2/0 AWG
2/0 AWG
|
19
19
|
B
B
|
COMBUL
COMBUL
|
SD
SD
|
404
10.26
|
411
612
|
355
355
|
4024
1825.25
|
0.07949
0.12
|
107011 |
3/0 AWG
3/0 AWG
|
7
7
|
A
A
|
CONV
CONV
|
SD
SD
|
473
12.03
|
518
771
|
410
410
|
5118
2321.48
|
0.06304
0.09
|
144527 |
3/0 AWG
3/0 AWG
|
19
19
|
B
B
|
COMBUL
COMBUL
|
SD
SD
|
454
11.53
|
520
774
|
410
410
|
|
0.06431
0.10
|
107045 |
4/0 AWG
4/0 AWG
|
7
7
|
A
A
|
CONV
CONV
|
SD
SD
|
521
13.25
|
653
972
|
480
480
|
6459
2929.75
|
0.04999
0.07
|
136739 |
4/0 AWG
4/0 AWG
|
19
19
|
B
B
|
COMBUL
COMBUL
|
SD
SD
|
510
12.95
|
653
972
|
480
480
|
6453
2927.03
|
0.04999
0.07
|
107078 |
250 KCMIL
250 KCMIL
|
19
19
|
A
A
|
CONV
CONV
|
SD
SD
|
573
14.57
|
772
1149
|
530
530
|
7627
3459.55
|
0.04231
0.06
|
148353 |
300 KCMIL
300 KCMIL
|
37
37
|
B
B
|
CONV
CONV
|
SD
SD
|
630
16.00
|
926
1378
|
590
590
|
9160
4154.90
|
0.03526
0.05
|
107136 |
350 KCMIL
350 KCMIL
|
19
19
|
A
A
|
CONV
CONV
|
SD
SD
|
678
17.23
|
1081
1608
|
650
650
|
10680
4844.36
|
0.03022
0.04
|
107193 |
500 KCMIL
500 KCMIL
|
37
37
|
B
B
|
CONV
CONV
|
SD
SD
|
813
20.66
|
1544
2297
|
810
810
|
15240
6912.74
|
0.02116
0.03
|
107284 |
1000 KCMIL
1000 KCMIL
|
61
61
|
B
B
|
CONV
CONV
|
SD
SD
|
1152
29.26
|
3087
4595
|
1240
1240
|
30500
13834.56
|
0.1058
0.16
|
Southwire's bare copper wire and cable meets or exceeds the following ASTM specifications:
Bare copper, solid or stranded. Available in tempers hard, medium-hard, or soft. Stranded conductors are concentrically stranded in hard and medium-hard tempers and are Combination Unilay stranded in the soft-drawn temper.