For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Voltage 1000V CSA / 600V UL.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Ground Size | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
6 AWG
6 AWG
|
7
7
|
0.169
0.43
|
60
1.52
|
1x6
1x6
|
65
1.65
|
1.089
2.77
|
55
1.40
|
1.199
3.05
|
536
798
|
472
214.10
|
8.3
21.08
|
| More Options |
2 AWG
2 AWG
|
6
6
|
0.268
0.68
|
60
1.52
|
1x6
1x6
|
85
2.16
|
1.345
3.42
|
55
1.40
|
1.455
3.70
|
818
1217
|
1194
541.59
|
10.1
25.65
|
| More Options |
1 AWG
1 AWG
|
8
8
|
0.298
0.76
|
80
2.03
|
1x4
1x4
|
85
2.16
|
1.503
3.82
|
65
1.65
|
1.635
4.15
|
1031
1534
|
1506
683.11
|
11.4
28.96
|
| More Options |
1/0 AWG
1/0 AWG
|
18
18
|
0.336
0.85
|
80
2.03
|
1x4
1x4
|
85
2.16
|
1.583
4.02
|
65
1.65
|
1.715
4.36
|
1144
1702
|
1900
861.82
|
12.0
30.48
|
| More Options |
2/0 AWG
2/0 AWG
|
12
12
|
0.376
0.96
|
80
2.03
|
1x4
1x4
|
85
2.16
|
1.669
4.24
|
65
1.65
|
1.801
4.57
|
1294
1926
|
2395
1086.35
|
12.6
32.00
|
| More Options |
3/0 AWG
3/0 AWG
|
16
16
|
0.422
1.07
|
80
2.03
|
1x4
1x4
|
85
2.16
|
1.771
4.50
|
65
1.65
|
1.903
4.83
|
1459
2171
|
3020
1369.85
|
13.3
33.78
|
| More Options |
4/0 AWG
4/0 AWG
|
18
18
|
0.474
1.20
|
80
2.03
|
1x4
1x4
|
85
2.16
|
1.893
4.81
|
65
1.65
|
2.025
5.14
|
1716
2554
|
3808
1727.28
|
14.1
35.81
|
| More Options |
500 KCMIL
500 KCMIL
|
35
35
|
0.735
1.87
|
90
2.29
|
1x1
1x1
|
115
2.92
|
2.565
6.52
|
80
2.03
|
2.731
6.94
|
3284
4887
|
9000
4082.33
|
19.1
48.51
|
| More Options |
750 KCMIL
750 KCMIL
|
53
53
|
0.908
2.31
|
90
2.29
|
1x1/0
1x1/0
|
115
2.92
|
2.937
7.46
|
80
2.03
|
3.103
7.88
|
4318
6426
|
13500
6123.49
|
21.7
55.12
|
| More Options |
250 KCMIL
250 KCMIL
|
35
35
|
0.520
1.32
|
90
2.29
|
1x2
1x2
|
115
2.92
|
2.099
5.33
|
65
1.65
|
2.231
5.67
|
2104
3131
|
4500
2041.16
|
15.6
39.62
|
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
| More Options |
6 AWG
6 AWG
|
0.674
1.00
|
0.812
1.21
|
0.051
0.08
|
| More Options |
2 AWG
2 AWG
|
0.267
0.40
|
0.321
0.48
|
0.045
0.07
|
| More Options |
1 AWG
1 AWG
|
0.211
0.31
|
0.254
0.38
|
0.046
0.07
|
| More Options |
1/0 AWG
1/0 AWG
|
0.168
0.25
|
0.201
0.30
|
0.044
0.07
|
| More Options |
2/0 AWG
2/0 AWG
|
0.133
0.20
|
0.160
0.24
|
0.043
0.06
|
| More Options |
3/0 AWG
3/0 AWG
|
0.105
0.16
|
0.126
0.19
|
0.042
0.06
|
| More Options |
4/0 AWG
4/0 AWG
|
0.084
0.13
|
0.100
0.15
|
0.041
0.06
|
| More Options |
500 KCMIL
500 KCMIL
|
0.035
0.05
|
0.044
0.07
|
0.039
0.06
|
| More Options |
750 KCMIL
750 KCMIL
|
0.024
0.04
|
0.031
0.05
|
0.038
0.06
|
| More Options |
250 KCMIL
250 KCMIL
|
0.071
0.11
|
0.086
0.13
|
0.041
0.06
|