SPEC: 48203

CU 2000V NL-EPR RHH/RHW-2 Thermoset SOLONON LSZH-TS TRACTION POWER CABLE SPEC48203

Traction Power Cable 2000 Volt Single Conductor Copper, No Lead Ethylene Propylene Rubber (NL-EPR) insulation RHH/RHW-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket

Download Category Specifications
PDF Excel Table

Application & Features

Southwire 2000V No Lead NL-EPR/SOLONON Traction Power Cable is suited for use in mass transit and general industry applications where flexibility, fire resistance, and low smoke generation are a concern. May be installed in wet or dry locations in cable trays or raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Resistance to moisture and most oils, acids, and alkalis with an overall durable LSZH XLPO jacket. Meets Flame Spread and Smoke Release requirements of NFPA 130. Rated for 1000 lb/ft maximum sidewall pressure. Alternate constructions available upon request.

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
1/0 AWG 1/0 AWG
1 1
19 19
0.362 0.92
65 1.65
45 1.14
0.598 1.52
326 485
428 637
More Options
350 KCMIL 350 KCMIL
1 1
37 37
0.641 1.63
75 1.91
65 1.65
0.944 2.40
1081 1609
1296 1929
More Options
500 KCMIL 500 KCMIL
1 1
37 37
0.766 1.95
75 1.91
65 1.65
1.063 2.70
1544 2298
1791 2665
More Options
500 KCMIL 500 KCMIL
1 1
91 91
0.791 2.01
75 1.91
65 1.65
1.088 2.76
1544 2298
1798 2676
More Options
500 KCMIL 500 KCMIL
1 1
259 259
0.850 2.16
75 1.91
65 1.65
1.150 2.92
1548 2304
1820 2708
More Options
500 KCMIL 500 KCMIL
1 1
427 427
0.909 2.31
105 2.67
65 1.65
1.271 3.23
1610 2396
1961 2918
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.968 2.46
90 2.29
65 1.65
1.297 3.29
2316 3447
2650 3944
More Options
750 KCMIL 750 KCMIL
1 1
127 127
0.968 2.46
90 2.29
65 1.65
1.297 3.29
2315 3445
2650 3944
More Options
1000 KCMIL 1000 KCMIL
1 1
61 61
1.118 2.84
90 2.29
65 1.65
1.446 3.67
3088 4595
3498 5206
More Options
1000 KCMIL 1000 KCMIL
1 1
127 127
1.118 2.84
90 2.29
65 1.65
1.450 3.68
3088 4595
3468 5161

* Thicknesses shown as Minimum Average values
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
1/0 AWG 1/0 AWG
1 1
4.8 12.19
854 387.37
0.102 0.15
0.132 0.20
0.033 0.05
150 150
145 145
More Options
350 KCMIL 350 KCMIL
1 1
7.6 19.30
2800 1270.06
0.031 0.05
0.039 0.06
0.040 0.06
310 310
350 350
More Options
500 KCMIL 500 KCMIL
1 1
8.5 21.59
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
500 KCMIL 500 KCMIL
1 1
8.7 22.10
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
500 KCMIL 500 KCMIL
1 1
9.2 23.37
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
500 KCMIL 500 KCMIL
1 1
10.2 25.91
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
750 KCMIL 750 KCMIL
1 1
10.3 26.16
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
More Options
750 KCMIL 750 KCMIL
1 1
10.4 26.42
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
More Options
1000 KCMIL 1000 KCMIL
1 1
11.6 29.46
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615
More Options
1000 KCMIL 1000 KCMIL
1 1
11.6 29.46
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B173 Rope-Lay-Stranded Copper Conductors Having Concentric-Stranded Members
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (250kcmil & Larger)
  • AREMA 10.3.13 Recommended Design Criteria for Low-Smoke Halogen Free (LSHF) Polymeric Cable Jackets

Construction

  1. Conductor:Stranded bare copper per ASTM B3 and B8, B172, or B173. Center strand embossed with “Southwire, Year, Plant” when required.
  2. Binder Tape:Mylar tape
  3. Insulation:No Lead Ethylene Propylene Rubber (NLEPR)
  4. Overall Jacket:Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS)