SPEC: 25084

CU 2000V EPR/LSZH RW90 Traction Cable SPEC25084

2000 Volt Single Conductor Copper, No Lead Ethylene Propylene Rubber (NLEPR) insulation RW90 SOLONON® Low Smoke Zero Halogen (LSZH) Jacket

Download Category Specifications
PDF Excel Table

Application & Features

Southwire 2000V EPR/SOLONON Power Cable is suited for use in mass transit and general industry applications where flexibility, fire resistance, and low smoke generation are a concern. May be installed in wet or dry locations in cable trays or raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Resistance to moisture and most oils, acids, and alkalis with an overall durable LSZH XLPO jacket. Meets Flame Spread and Smoke Release requirements of NFPA 130. Alternate constructions available upon request.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
500 KCMIL 500 KCMIL
1 1
37 37
0.789 2.00
75 1.91
65 1.65
1.068 2.71
1543 2296
1796 2673
More Options
535.3 KCMIL 535.3 KCMIL
1 1
1349 1349
0.830 2.11
120 3.05
95 2.41
1.288 3.27
1560 2322
2010 2991
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.968 2.46
90 2.29
65 1.65
1.302 3.31
2315 3445
2656 3953
More Options
1000 KCMIL 1000 KCMIL
1 1
61 61
1.117 2.84
120 3.05
65 1.65
1.513 3.84
3087 4594
3536 5262
More Options
1000 KCMIL 1000 KCMIL
1 1
427 427
1.117 2.84
90 2.29
65 1.65
1.493 3.79
3150 4688
3543 5273
More Options
1500 KCMIL 1500 KCMIL
1 1
91 91
1.37 3.48
140 3.56
125 3.18
1.934 4.91
4631 6892
5481 8157

¹Thicknesses reported as minimum average
* Bare copper
! Class G stranding per ASTM B173: Standard Specification for Rope-Lay-Stranded Copper Conductors * Having Concentric-Stranded Members, for Electrical Conductors
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
500 KCMIL 500 KCMIL
1 1
5.3 13.46
4000 1814.37
0.022 0.03
0.029 0.04
0.033 0.05
380 380
430 430
More Options
535.3 KCMIL 535.3 KCMIL
1 1
6.4 16.26
4282 1942.28
0.021 0.03
0.032 0.05
0.028 0.04
394 394
446 446
More Options
750 KCMIL 750 KCMIL
1 1
6.5 16.51
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
More Options
1000 KCMIL 1000 KCMIL
1 1
7.5 19.05
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615
More Options
1000 KCMIL 1000 KCMIL
1 1
7.4 18.80
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615
More Options
1500 KCMIL 1500 KCMIL
1 1
9.6 24.38
12000 5443.10
0.007 0.01
0.016 0.02
0.035 0.05
625 625
705 705

* Ampacities derived from the Canadian Electrical Code - Table 2 - for Cable in Conduit. Not more than 3 copper conductors in a conduit and based on an ambient temperature of 30°C.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors (As Applicable)
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - marked FT4-ST1 (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Oil Res I & Sun Res - AWG 8 & Larger
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)

Construction

  1. Conductor:Stranded bare or tinned copper per ASTM B3 or B33. Center strand embossed with “Southwire, Year, Plant” when required
  2. Binder Tape:Mylar Tape
  3. Insulation:No Lead Ethylene Propylene Rubber (EPR) Type RW90
  4. Overall Jacket:SOLONON® Low Smoke Zero Halogen (LSZH) Jacket