SPEC: 10026

SIMpull Barrel™ Cable Drum THHN/THWN-2 Copper SPEC10026

The SIMpull Barrel™ Cable Drum Cable Drum is ideal for job sites with longer runs and home-run pulls. Designed to simplify branch circuit installations, the SIMpull BARREL™ Cable Drum contains up to 7 paralleled conductors per BARREL, increasing productivity and reducing the potential for injury while avoiding broken spools, excess material handling, and scrap. Easy payoff directly out of the package, requiring less setup and effort to pull vs conventional wire-pulling methods. Copper 600 Volt THHN/THWN-2

Download Category Specifications
PDF Excel Table

Application & Features

The SIMpull BARREL™ Cable Drum reduces the physical effort associated with material handling, setup, and pulling when compared to conventional wire pulling methods. Designed to simplify branch circuit installations, the SIMpull BARREL™ Cable Drum contains up to 7 paralleled conductors per BARREL (homerun), increasing productivity and reducing the potential for injury while avoiding broken spools, excess material handling and scrap. SIMpull BARREL™ THHN/THWN-2 copper conductors are primarily used in conduit for branch circuits in commercial or industrial applications as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. SIMpull BARREL™ THHN/THWN-2 copper conductors are designed to be installed without the application of a pulling lubricant. These conductors have multiple ratings depending upon the product application. Allowable temperatures are as follows:
- THHN or T90 Nylon- Dry locations not to exceed 90°C
- THWN-2- Wet or dry locations not to exceed 90° C or locations not to exceed 75°C when exposed to oil
- TWN75- Wet locations not to exceed 75°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
- AWM- Dry locations not to exceed 105°C only when rated and used as appliance wiring material
FEATURES

  • Easier pulling with SIMpull NoLube® wire jacket.
  • Stationary package design to further reduce pulling tension.
  • Designed to help lower potential for lifting/handling/pulling injuries.
  • Patented parallel construction to reduce material handling and setup.
  • Avoid broken spools and spool over-turn.
  • Specifications

    Select a set of products below for more information:
    Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
    More Options
    12 AWG 12 AWG
    1 1
    Solid Solid
    0.080 0.20
    15 0.38
    5 0.13
    0.368 0.93
    59 88
    70 104
    More Options
    12 AWG 12 AWG
    1 1
    19 19
    0.090 0.23
    20 0.51
    5 0.13
    0.390 0.99
    60 89
    72 107
    More Options
    12 AWG 12 AWG
    1 1
    Solid Solid
    0.080 0.20
    15 0.38
    5 0.13
    0.368 0.93
    59 88
    70 104
    More Options
    12 AWG 12 AWG
    1 1
    19 19
    0.090 0.23
    20 0.51
    5 0.13
    0.390 0.99
    60 89
    72 107
    More Options
    12 AWG 12 AWG
    2 2
    Solid Solid
    0.080 0.20
    20 0.51
    5 0.13
    0.245 0.62
    39 58
    47 70
    More Options
    12 AWG 12 AWG
    2 2
    19 19
    0.090 0.23
    20 0.51
    5 0.13
    0.260 0.66
    40 60
    48 71
    More Options
    12 AWG 12 AWG
    3 3
    Solid Solid
    0.080 0.20
    20 0.51
    5 0.13
    0.368 0.93
    59 88
    70 104
    More Options
    12 AWG 12 AWG
    3 3
    19 19
    0.090 0.23
    20 0.51
    5 0.13
    0.390 0.99
    60 89
    72 107
    More Options
    12 AWG 12 AWG
    4 4
    Solid Solid
    0.080 0.20
    15 0.38
    5 0.13
    0.491 1.25
    79 118
    94 140
    More Options
    12 AWG 12 AWG
    4 4
    19 19
    0.090 0.23
    20 0.51
    5 0.13
    0.390 0.99
    60 89
    72 107
    More Options
    12 AWG 12 AWG
    5 5
    Solid Solid
    0.080 0.20
    20 0.51
    5 0.13
    0.614 1.56
    98 146
    117 174
    More Options
    12 AWG 12 AWG
    5 5
    19 19
    0.090 0.23
    20 0.51
    5 0.13
    0.650 1.65
    100 149
    121 180
    More Options
    12 AWG 12 AWG
    6 6
    Solid Solid
    0.080 0.20
    20 0.51
    5 0.13
    0.736 1.87
    118 176
    141 210
    More Options
    12 AWG 12 AWG
    7 7
    Solid Solid
    0.080 0.20
    20 0.51
    5 0.13
    0.859 2.18
    138 205
    164 244
    More Options
    12 AWG 12 AWG
    7 7
    19 19
    0.090 0.23
    20 0.51
    5 0.13
    0.910 2.31
    141 210
    170 253
    More Options
    10 AWG 10 AWG
    1 1
    Solid Solid
    0.101 0.26
    25 0.64
    5 0.13
    0.307 0.78
    61 91
    73 109
    More Options
    10 AWG 10 AWG
    1 1
    19 19
    0.117 0.30
    25 0.64
    5 0.13
    0.489 1.24
    96 143
    115 171
    More Options
    10 AWG 10 AWG
    2 2
    Solid Solid
    0.101 0.26
    20 0.51
    5 0.13
    0.303 0.77
    61 91
    72 107
    More Options
    10 AWG 10 AWG
    2 2
    19 19
    0.117 0.30
    20 0.51
    5 0.13
    0.330 0.84
    64 95
    77 115
    More Options
    10 AWG 10 AWG
    3 3
    Solid Solid
    0.101 0.26
    20 0.51
    5 0.13
    0.449 1.14
    94 140
    110 164
    More Options
    10 AWG 10 AWG
    3 3
    19 19
    0.117 0.30
    20 0.51
    5 0.13
    0.489 1.24
    96 143
    115 171
    More Options
    10 AWG 10 AWG
    4 4
    Solid Solid
    0.101 0.26
    20 0.51
    5 0.13
    0.607 1.54
    122 182
    145 216
    More Options
    10 AWG 10 AWG
    4 4
    19 19
    0.117 0.30
    25 0.64
    5 0.13
    0.652 1.66
    128 190
    153 228
    More Options
    10 AWG 10 AWG
    5 5
    Solid Solid
    0.101 0.26
    25 0.64
    5 0.13
    0.759 1.93
    153 228
    181 269
    More Options
    10 AWG 10 AWG
    5 5
    19 19
    0.117 0.30
    25 0.64
    5 0.13
    0.815 2.07
    160 238
    192 286
    More Options
    10 AWG 10 AWG
    6 6
    Solid Solid
    0.101 0.26
    25 0.64
    5 0.13
    0.911 2.31
    183 272
    218 324
    More Options
    10 AWG 10 AWG
    6 6
    19 19
    0.117 0.30
    25 0.64
    5 0.13
    0.978 2.48
    192 286
    230 342
    More Options
    10 AWG 10 AWG
    7 7
    Solid Solid
    0.101 0.26
    25 0.64
    5 0.13
    1.063 2.70
    214 318
    254 378
    More Options
    10 AWG 10 AWG
    7 7
    19 19
    0.117 0.30
    25 0.64
    5 0.13
    1.141 2.90
    224 333
    269 400
    More Options
    10 AWG 10 AWG
    1 1
    Solid Solid
    0.101 0.26
    25 0.64
    5 0.13
    0.307 0.78
    61 91
    73 109
    More Options
    10 AWG 10 AWG
    1 1
    19 19
    0.117 0.30
    25 0.64
    5 0.13
    0.489 1.24
    96 143
    115 171

    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
    More Options
    12 AWG 12 AWG
    1 1
    1.5 3.81
    156 70.76
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    1 1
    1.6 4.06
    156 70.76
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    1 1
    1.5 3.81
    156 70.76
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    1 1
    1.6 4.06
    156 70.76
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    2 2
    1.0 2.54
    104 47.17
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    2 2
    1.0 2.54
    104 47.17
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    3 3
    1.5 3.81
    156 70.76
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    3 3
    1.6 4.06
    156 70.76
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    4 4
    2.0 5.08
    167 75.75
    1.662 2.47
    2.002 2.98
    0.054 0.08
    20 20
    24 24
    More Options
    12 AWG 12 AWG
    4 4
    1.6 4.06
    156 70.76
    1.662 2.47
    2.002 2.98
    0.054 0.08
    25 25
    30 30
    More Options
    12 AWG 12 AWG
    5 5
    2.5 6.35
    208 94.35
    1.662 2.47
    2.002 2.98
    0.054 0.08
    20 20
    24 24
    More Options
    12 AWG 12 AWG
    5 5
    2.6 6.60
    208 94.35
    1.662 2.47
    2.002 2.98
    0.054 0.08
    20 20
    24 24
    More Options
    12 AWG 12 AWG
    6 6
    2.9 7.37
    250 113.40
    1.662 2.47
    2.002 2.98
    0.054 0.08
    20 20
    24 24
    More Options
    12 AWG 12 AWG
    7 7
    3.4 8.64
    292 132.45
    1.662 2.47
    2.002 2.98
    0.054 0.08
    17 17
    21 21
    More Options
    12 AWG 12 AWG
    7 7
    3.6 9.14
    292 132.45
    1.662 2.47
    2.002 2.98
    0.054 0.08
    17 17
    21 21
    More Options
    10 AWG 10 AWG
    1 1
    1.2 3.05
    166 75.30
    1.040 1.55
    1.253 1.86
    0.050 0.07
    35 35
    40 40
    More Options
    10 AWG 10 AWG
    1 1
    2.0 5.08
    249 112.94
    1.040 1.55
    1.253 1.86
    0.050 0.07
    35 35
    40 40
    More Options
    10 AWG 10 AWG
    2 2
    1.2 3.05
    166 75.30
    1.040 1.55
    1.253 1.86
    0.050 0.07
    35 35
    40 40
    More Options
    10 AWG 10 AWG
    2 2
    1.3 3.30
    166 75.30
    1.040 1.55
    1.253 1.86
    0.050 0.07
    35 35
    40 40
    More Options
    10 AWG 10 AWG
    3 3
    1.8 4.57
    249 112.94
    1.040 1.55
    1.253 1.86
    0.050 0.07
    35 35
    40 40
    More Options
    10 AWG 10 AWG
    3 3
    2.0 5.08
    249 112.94
    1.040 1.55
    1.253 1.86
    0.050 0.07
    35 35
    40 40
    More Options
    10 AWG 10 AWG
    4 4
    2.4 6.10
    265 120.20
    1.040 1.55
    1.253 1.86
    0.050 0.07
    28 28
    32 32
    More Options
    10 AWG 10 AWG
    4 4
    2.6 6.60
    265 120.20
    1.040 1.55
    1.253 1.86
    0.050 0.07
    28 28
    32 32
    More Options
    10 AWG 10 AWG
    5 5
    3.0 7.62
    332 150.59
    1.040 1.55
    1.253 1.86
    0.050 0.07
    28 28
    32 32
    More Options
    10 AWG 10 AWG
    5 5
    3.3 8.38
    332 150.59
    1.040 1.55
    1.253 1.86
    0.050 0.07
    28 28
    32 32
    More Options
    10 AWG 10 AWG
    6 6
    3.6 9.14
    398 180.53
    1.040 1.55
    1.253 1.86
    0.050 0.07
    28 28
    32 32
    More Options
    10 AWG 10 AWG
    6 6
    3.9 9.91
    398 180.53
    1.040 1.55
    1.253 1.86
    0.050 0.07
    28 28
    32 32
    More Options
    10 AWG 10 AWG
    7 7
    5.3 13.46
    465 210.92
    1.040 1.55
    1.253 1.86
    0.050 0.07
    24 24
    28 28
    More Options
    10 AWG 10 AWG
    7 7
    5.7 14.48
    465 210.92
    1.040 1.55
    1.253 1.86
    0.050 0.07
    24 24
    28 28
    More Options
    10 AWG 10 AWG
    1 1
    1.2 3.05
    166 75.30
    1.040 1.55
    1.253 1.86
    0.050 0.07
    35 35
    40 40
    More Options
    10 AWG 10 AWG
    1 1
    2.0 5.08
    249 112.94
    1.040 1.55
    1.253 1.86
    0.050 0.07
    35 35
    40 40

    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Size (Strand) Cond. Number Blue Blue/Brown Black Brown Green Gray Gray/Brown Gray/Orange Gray/Yellow
    12 (Solid) 12 (Solid)
    1 1
    58026701
    58026501
    58026801
    58027101
    58026901 58026901
    12 (19) 12 (19)
    1 1
    58018401
    58018201
    58018501
    58019501
    58018601
    10 (Solid) 10 (Solid)
    1 1
    58020401
    58020301
    58020501
    58021101
    58022601
    58020801
    58021001
    10 (19) 10 (19)
    1 1
    58022201
    65312201
    58022101
    58022301
    58025001
    58020701
    58025701
    58025901
    Size (Strand) Cond. Number Orange Purple Pink Red Red/Yellow White White/Blue White/Black White/Red Yellow
    14 (Solid) 14 (Solid)
    1 1
    58029405 58029405
    14 (19) 14 (19)
    1 1
    58017801 58017801
    12 (Solid) 12 (Solid)
    1 1
    58027201
    58026401 58026401
    58193101 58193101
    58027301
    58028158 58028158
    58028058 58028058
    58028358 58028358
    58027601
    12 (19) 12 (19)
    1 1
    58019601
    58019701
    58019801
    58019901
    58020001
    10 (Solid) 10 (Solid)
    1 1
    58021301
    58021401
    58021801
    58021601
    58021901
    58022001
    10 (19) 10 (19)
    1 1
    58025201
    58025301
    58025401
    59917901
    58025501
    58026107
    58026007
    58026207
    Size (Strand) Cond. Number Black, White Blue, White/Blue Black, White/Black Brown, Gray/Brown Orange, Gray/Orange Red, White/Red Yellow, Gray/Yellow
    12 (Solid) 12 (Solid)
    2 2
    58614502
    58619402
    58110302
    58110502
    58614402
    58111002
    12 (19) 12 (19)
    2 2
    58111202
    58260302
    58612002
    58610002
    58111802
    58610102
    10 (Solid) 10 (Solid)
    2 2
    58105002
    58029702
    58105502
    10 (19) 10 (19)
    2 2
    58725102
    58725702
    58725502
    58109903 58109903
    58725602
    8 (19) 8 (19)
    2 2
    58526001 58526001
    Size (Strand) Cond. Number Blue, White/Blue, Green Black, White/Black, Green Brown, Gray/Brown, Green Brown, Orange, Yellow Orange, Gray/Orange, Green Purple, Gray/Purple, Green Red, White/Red, Green
    12 (Solid) 12 (Solid)
    3 3
    58536102
    58536002
    58536202
    58536302
    58536502
    12 (19) 12 (19)
    3 3
    58536702
    58724302
    10 (Solid) 10 (Solid)
    3 3
    58449901
    58317001
    58379601
    58379701
    58449801
    10 (19) 10 (19)
    3 3
    58620501
    58318301
    58710901
    58114301 58114301
    58711001
    67188501 67188501
    58620401
    8 (19) 8 (19)
    3 3
    58524803 58524803
    Size (Strand) Cond. Number Black, Red, Blue, White Black, White, Red, Blue Brown, Orange, Yellow, GN Brown, Orange, Yellow, Gray Black, Red, Blue, White, Green Brown, Orange, Yellow, Gray, Green
    12 (Solid) 12 (Solid)
    4 4
    58150601
    12 (19) 12 (19)
    4 4
    58103401 58103401
    58139401
    10 (Solid) 10 (Solid)
    4 4
    58150701
    10 (19) 10 (19)
    4 4
    58031101
    58138501
    58115501
    8 (19) 8 (19)
    4 4
    58384801 58384801
    12 (Solid) 12 (Solid)
    5 5
    58103901
    12 (19) 12 (19)
    5 5
    58104001
    58117401
    10 (Solid) 10 (Solid)
    5 5
    58103701
    58116701
    10 (19) 10 (19)
    5 5
    58103801
    Size (Strand) Cond. Number Black, Red, Blue, White/Black, White/Red, White/Blue Black, Red, Blue, White/Black, White/Red, White/Blue, Green Brown, Orange, Yellow, Gray/Brown, Gray/OE, Gray/Yellow Brown, Orange, Yellow, Gray/Brown, Gray/OE, Gray/Yellow, Green Red, Red, Red, Red, Red, Red
    14 (19) 14 (19)
    6 6
    58735001 58735001
    12 (Solid) 12 (Solid)
    6 6
    58120301
    58120401 58120401
    12 (19) 12 (19)
    6 6
    58120801 58120801
    10 (Solid) 10 (Solid)
    6 6
    58119601
    58119701
    10 (19) 10 (19)
    6 6
    58120101
    58120001
    12 (Solid) 12 (Solid)
    7 7
    58104601
    58118501
    12 (19) 12 (19)
    7 7
    58118701
    58104701
    10 (Solid) 10 (Solid)
    7 7
    58104401
    58118001
    10 (19) 10 (19)
    7 7
    58118301
    58104501

    Standards & References

    • ASTM B3 Soft or Annealed Copper Wire
    • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
    • UL 83 Thermoplastic Insulated Wires and Cables
    • NMX-J-010-ANCE Thermoplastic insulated wires and cables
    • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
    • NEMA 70901-2-2024 Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable

    Construction

    1. Conductor:Solid soft drawn annealed bare copper per ASTM B3 or combination-unilay Class C stranded soft drawn annealed bare copper per ASTM B787
    2. Insulation:Heat and moisture resistant PVC insulation in various colors
    3. Sheath:Nylon jacket utilizing SIMpull® Technology

    4. For information about our SIMpull Barrel™ Cable Drum please visit us at:   SIMpull Barrel™