Southwire’s 2000 Volt Type TC VFD power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC) per NEC 336.10.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
12 AWG
12 AWG
|
3
3
|
7
7
|
0.088
0.22
|
60
1.52
|
0.486
1.23
|
60
1.52
|
0.607
1.54
|
128
190
|
251
374
|
| More Options |
2 AWG
2 AWG
|
3
3
|
7
7
|
0.282
0.72
|
70
1.78
|
0.946
2.40
|
115
2.92
|
1.174
2.98
|
827
1231
|
1209
1799
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
19
19
|
0.405
1.03
|
90
2.29
|
1.311
3.33
|
80
2.03
|
1.531
3.89
|
1641
2442
|
2312
3441
|
| More Options |
4/0 AWG
4/0 AWG
|
3
3
|
19
19
|
0.512
1.30
|
90
2.29
|
1.506
3.83
|
115
2.92
|
1.742
4.42
|
2542
3783
|
3221
4793
|
| More Options |
500 KCMIL
500 KCMIL
|
3
3
|
37
37
|
0.789
2.00
|
105
2.67
|
2.149
5.46
|
115
2.92
|
2.379
6.04
|
5706
8491
|
6779
10088
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
12 AWG
12 AWG
|
3
3
|
7.3
18.54
|
156
70.76
|
1.662
2.47
|
2.002
2.98
|
0.057
0.08
|
0.054
0.08
|
25
25
|
30
30
|
| More Options |
2 AWG
2 AWG
|
3
3
|
14.1
35.81
|
1592
722.12
|
0.162
0.24
|
0.195
0.29
|
0.027
0.04
|
0.045
0.07
|
115
115
|
130
130
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
18.4
46.74
|
3194
1448.77
|
0.081
0.12
|
0.097
0.14
|
0.025
0.04
|
0.043
0.06
|
175
175
|
195
195
|
| More Options |
4/0 AWG
4/0 AWG
|
3
3
|
20.9
53.09
|
5078
2303.34
|
0.051
0.08
|
0.062
0.09
|
0.020
0.03
|
0.041
0.06
|
230
230
|
260
260
|
| More Options |
500 KCMIL
500 KCMIL
|
3
3
|
28.6
72.64
|
12000
5443.10
|
0.022
0.03
|
0.029
0.04
|
0.016
0.02
|
0.039
0.06
|
380
380
|
430
430
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.