Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated. Sunlight Resistant - For Direct Burial - Silicone Free
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
8 AWG
8 AWG
|
3
3
|
7
7
|
0.141
0.36
|
45
1.14
|
60
1.52
|
0.647
1.64
|
186
277
|
307
457
|
| More Options |
6 AWG
6 AWG
|
3
3
|
7
7
|
0.177
0.45
|
45
1.14
|
60
1.52
|
0.724
1.84
|
297
442
|
441
656
|
| More Options |
4 AWG
4 AWG
|
3
3
|
7
7
|
0.225
0.57
|
45
1.14
|
60
1.52
|
0.853
2.17
|
441
656
|
634
943
|
| More Options |
2 AWG
2 AWG
|
3
3
|
7
7
|
0.282
0.72
|
45
1.14
|
80
2.03
|
0.978
2.48
|
702
1045
|
930
1384
|
| More Options |
1 AWG
1 AWG
|
3
3
|
19
19
|
0.322
0.82
|
55
1.40
|
80
2.03
|
1.162
2.95
|
864
1286
|
1198
1783
|
| More Options |
1/0 AWG
1/0 AWG
|
3
3
|
19
19
|
0.361
0.92
|
55
1.40
|
80
2.03
|
1.216
3.09
|
1069
1591
|
1406
2092
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
19
19
|
0.405
1.03
|
55
1.40
|
80
2.03
|
1.329
3.38
|
1326
1973
|
1719
2558
|
| More Options |
3/0 AWG
3/0 AWG
|
3
3
|
19
19
|
0.456
1.16
|
55
1.40
|
80
2.03
|
1.437
3.65
|
1699
2528
|
2127
3165
|
| More Options |
4/0 AWG
4/0 AWG
|
3
3
|
19
19
|
0.512
1.30
|
55
1.40
|
80
2.03
|
1.558
3.96
|
2109
3139
|
2579
3838
|
| More Options |
250 KCMIL
250 KCMIL
|
3
3
|
37
37
|
0.558
1.42
|
65
1.65
|
80
2.03
|
1.755
4.46
|
2469
3674
|
3091
4600
|
| More Options |
350 KCMIL
350 KCMIL
|
3
3
|
37
37
|
0.661
1.68
|
65
1.65
|
110
2.79
|
1.990
5.05
|
3438
5116
|
4167
6201
|
| More Options |
500 KCMIL
500 KCMIL
|
3
3
|
37
37
|
0.789
2.00
|
65
1.65
|
115
2.92
|
2.225
5.65
|
4884
7268
|
5681
8454
|
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
8 AWG
8 AWG
|
3
3
|
2.6
6.60
|
396
179.62
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
50
50
|
55
55
|
| More Options |
6 AWG
6 AWG
|
3
3
|
2.9
7.37
|
629
285.31
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
| More Options |
4 AWG
4 AWG
|
3
3
|
3.4
8.64
|
1001
454.05
|
0.258
0.38
|
0.310
0.46
|
0.048
0.07
|
85
85
|
95
95
|
| More Options |
2 AWG
2 AWG
|
3
3
|
3.9
9.91
|
1592
722.12
|
0.162
0.24
|
0.195
0.29
|
0.045
0.07
|
115
115
|
130
130
|
| More Options |
1 AWG
1 AWG
|
3
3
|
5.8
14.73
|
2008
910.81
|
0.128
0.19
|
0.154
0.23
|
0.046
0.07
|
130
130
|
145
145
|
| More Options |
1/0 AWG
1/0 AWG
|
3
3
|
6.1
15.49
|
2534
1149.40
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
150
150
|
170
170
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
6.6
16.76
|
3194
1448.77
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
| More Options |
3/0 AWG
3/0 AWG
|
3
3
|
7.2
18.29
|
4027
1826.61
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
200
200
|
225
225
|
| More Options |
4/0 AWG
4/0 AWG
|
3
3
|
7.8
19.81
|
5078
2303.34
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
230
230
|
260
260
|
| More Options |
250 KCMIL
250 KCMIL
|
3
3
|
8.8
22.35
|
6000
2721.55
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
255
255
|
290
290
|
| More Options |
350 KCMIL
350 KCMIL
|
3
3
|
10.0
25.40
|
8400
3810.17
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
310
310
|
350
350
|
| More Options |
500 KCMIL
500 KCMIL
|
3
3
|
13.4
34.04
|
12000
5443.10
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
380
380
|
430
430
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.