For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Rated for 1000 lbs./FT maximum sidewall pressure.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
568605 |
2
2
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
10
10
|
|
899
22.83
|
397
591
|
|
568605 |
2
2
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
10
10
|
|
899
22.83
|
397
591
|
|
561963 |
3
3
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
10
10
|
|
936
23.78
|
473
704
|
|
561963 |
3
3
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
10
10
|
|
936
23.78
|
473
704
|
|
561964 |
4
4
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
10
10
|
|
1015
25.80
|
575
856
|
|
573821 |
2
2
|
6 AWG
6 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1031
26.19
|
538
800
|
|
573821 |
2
2
|
6 AWG
6 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1031
26.19
|
538
800
|
|
561965 |
3
3
|
6 AWG
6 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1189
30.20
|
712
1059
|
|
561965 |
3
3
|
6 AWG
6 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1189
30.20
|
712
1059
|
|
561966 |
4
4
|
6 AWG
6 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1306
33.19
|
886
1319
|
|
582005 |
2
2
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1254
31.86
|
757
1127
|
|
582005 |
2
2
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1254
31.86
|
757
1127
|
|
561967 |
3
3
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1332
33.84
|
956
1422
|
|
561967 |
3
3
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1332
33.84
|
956
1422
|
|
561968 |
4
4
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1420
36.08
|
1147
1707
|
|
561968 |
4
4
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
8
8
|
|
1420
36.08
|
1147
1707
|
|
571184 |
2
2
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
6
6
|
|
1408
35.78
|
1046
1557
|
|
561972 |
3
3
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
6
6
|
|
1453
36.91
|
1283
1909
|
|
561972 |
3
3
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
6
6
|
|
1453
36.91
|
1283
1909
|
|
561973 |
4
4
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
6
6
|
|
1555
39.50
|
1562
2324
|
|
561973 |
4
4
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
6
6
|
|
1555
39.50
|
1562
2324
|
|
561974 |
3
3
|
1 AWG
1 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1658
42.13
|
1604
2387
|
|
561974 |
3
3
|
1 AWG
1 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1658
42.13
|
1604
2387
|
|
561975 |
4
4
|
1 AWG
1 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1782
45.28
|
1982
2949
|
|
561976 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1742
44.27
|
1860
2768
|
|
561976 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1742
44.27
|
1860
2768
|
|
561978 |
4
4
|
1/0 AWG
1/0 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1876
47.67
|
2316
3446
|
|
561948 |
3
3
|
2/0 AWG
2/0 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1837
46.68
|
2192
3262
|
|
561948 |
3
3
|
2/0 AWG
2/0 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1837
46.68
|
2192
3262
|
|
561949 |
4
4
|
2/0 AWG
2/0 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1995
50.68
|
2787
4148
|
|
561949 |
4
4
|
2/0 AWG
2/0 AWG
|
19
19
|
80
2.03
|
6
6
|
|
1995
50.68
|
2787
4148
|
|
586400 |
2
2
|
3/0 AWG
3/0 AWG
|
19
19
|
80
2.03
|
4
4
|
|
1870
47.51
|
2043
3040
|
|
561950 |
3
3
|
3/0 AWG
3/0 AWG
|
19
19
|
80
2.03
|
4
4
|
|
1924
48.88
|
2621
3901
|
|
561950 |
3
3
|
3/0 AWG
3/0 AWG
|
19
19
|
80
2.03
|
4
4
|
|
1924
48.88
|
2621
3901
|
|
561952 |
4
4
|
3/0 AWG
3/0 AWG
|
19
19
|
80
2.03
|
4
4
|
|
2099
53.32
|
3342
4974
|
|
561953 |
3
3
|
4/0 AWG
4/0 AWG
|
19
19
|
80
2.03
|
4
4
|
|
2075
52.71
|
3205
4770
|
|
561953 |
3
3
|
4/0 AWG
4/0 AWG
|
19
19
|
80
2.03
|
4
4
|
|
2075
52.71
|
3205
4770
|
|
561954 |
4
4
|
4/0 AWG
4/0 AWG
|
19
19
|
80
2.03
|
4
4
|
|
2307
58.60
|
4149
6175
|
|
561954 |
4
4
|
4/0 AWG
4/0 AWG
|
19
19
|
80
2.03
|
4
4
|
|
2307
58.60
|
4149
6175
|
|
561955 |
3
3
|
250 KCMIL
250 KCMIL
|
37
37
|
90
2.29
|
4
4
|
|
2256
57.31
|
3762
5598
|
|
561955 |
3
3
|
250 KCMIL
250 KCMIL
|
37
37
|
90
2.29
|
4
4
|
|
2256
57.31
|
3762
5598
|
|
561956 |
4
4
|
250 KCMIL
250 KCMIL
|
37
37
|
90
2.29
|
4
4
|
|
2464
62.59
|
4774
7104
|
|
561957 |
3
3
|
300 KCMIL
300 KCMIL
|
37
37
|
90
2.29
|
4
4
|
|
2427
61.66
|
4389
6531
|
|
561957 |
3
3
|
300 KCMIL
300 KCMIL
|
37
37
|
90
2.29
|
4
4
|
|
2427
61.66
|
4389
6531
|
|
561958 |
4
4
|
300 KCMIL
300 KCMIL
|
37
37
|
90
2.29
|
4
4
|
|
2630
66.82
|
5528
8227
|
|
561959 |
3
3
|
350 KCMIL
350 KCMIL
|
37
37
|
90
2.29
|
3
3
|
|
2492
63.30
|
4939
7350
|
|
561960 |
4
4
|
350 KCMIL
350 KCMIL
|
37
37
|
90
2.29
|
3
3
|
|
2703
68.66
|
6243
9290
|
|
561961 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
90
2.29
|
3
3
|
|
2762
70.16
|
6545
9741
|
|
561961 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
90
2.29
|
3
3
|
|
2762
70.16
|
6545
9741
|
|
561962 |
4
4
|
500 KCMIL
500 KCMIL
|
37
37
|
90
2.29
|
3
3
|
|
3004
76.32
|
8351
12428
|
|
592314 |
3
3
|
600 KCMIL
600 KCMIL
|
61
61
|
90
2.29
|
2
2
|
|
2956
75.08
|
7713
11479
|
|
568478 |
3
3
|
750 KCMIL
750 KCMIL
|
61
61
|
90
2.29
|
2
2
|
|
3283
83.40
|
9513
14156
|
|
568479 |
4
4
|
750 KCMIL
750 KCMIL
|
61
61
|
90
2.29
|
2
2
|
|
3591
91.22
|
12223
18190
|
|
641155 |
3
3
|
1000 KCMIL
1000 KCMIL
|
61
61
|
90
2.29
|
1
1
|
|
3619
91.93
|
12221
18187
|
|