Southwire® SIMpull XHHW-2® copper conductors are primarily used in conduit, Cable Tray or other recognized raceways for services, feeders, and branch circuit wiring, as specified in the National Electrical Code. SIMpull XHHW-2® copper conductors may be used in wet or dry locations at temperatures not to exceed 90° C. Voltage rating for XHHW-2 conductors is 600 volts for all sizes and 1000 volts for sizes 8 AWG and larger. Suitable for use in Health Care Facilities per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 maybe specified. This cable is designed to be installed without the application of pulling lubricant.
Conductor | Allowable Ampacities+ | ||||||||
Size (AWG or kcmil) | No. of Conductors | No. of Strands | Nom. OD (mils) (mm) | Insulation Thickness (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 60C | Allowable Ampacity at 75C | Allowable Ampacity at 90C | |
112920 | 14 AWG 14 AWG | 1 1 | 7 7 | 130 3.32 | 30 0.76 | 17 25 | 15 15 | 15 15 | 15 15 |
550220 | 12 AWG 12 AWG | 1 1 | 1 1 | 140 3.58 | 30 0.76 | 24 36 | 20 20 | 20 20 | 20 20 |
112938 | 12 AWG 12 AWG | 1 1 | 7 7 | 147 3.74 | 30 0.76 | 25 38 | 20 20 | 20 20 | 20 20 |
137240 | 10 AWG 10 AWG | 1 1 | 1 1 | 161 4.11 | 30 0.76 | 36 54 | 30 30 | 30 30 | 30 30 |
112946 | 10 AWG 10 AWG | 1 1 | 7 7 | 173 4.39 | 30 0.76 | 38 56 | 30 30 | 30 30 | 30 30 |
112953 | 8 AWG 8 AWG | 1 1 | 7 7 | 238 6.05 | 45 1.14 | 64 96 | 40 40 | 50 50 | 55 55 |
112961 | 6 AWG 6 AWG | 1 1 | 7 7 | 274 6.96 | 45 1.14 | 97 144 | 55 55 | 65 65 | 75 75 |
112979 | 4 AWG 4 AWG | 1 1 | 7 7 | 315 8.00 | 45 1.14 | 148 220 | 70 70 | 85 85 | 95 95 |
267278 | 3 AWG 3 AWG | 1 1 | 7 7 | 342 8.69 | 45 1.14 | 184 273 | 85 85 | 100 100 | 115 115 |
112987 | 2 AWG 2 AWG | 1 1 | 7 7 | 373 9.47 | 45 1.14 | 228 340 | 95 95 | 115 115 | 130 130 |
112995 | 1 AWG 1 AWG | 1 1 | 19 19 | 435 11.05 | 57 1.45 | 292 435 | 110 110 | 130 130 | 145 145 |
113001 | 1/0 AWG 1/0 AWG | 1 1 | 19 19 | 480 12.19 | 57 1.45 | 364 541 | 125 125 | 150 150 | 170 170 |
113019 | 2/0 AWG 2/0 AWG | 1 1 | 19 19 | 524 13.31 | 57 1.45 | 453 674 | 145 145 | 175 175 | 195 195 |
113027 | 3/0 AWG 3/0 AWG | 1 1 | 19 19 | 574 14.58 | 57 1.45 | 565 840 | 165 165 | 200 200 | 225 225 |
113035 | 4/0 AWG 4/0 AWG | 1 1 | 19 19 | 630 16.00 | 57 1.45 | 707 1052 | 195 195 | 230 230 | 260 260 |
113043 | 250 KCMIL 250 KCMIL | 1 1 | 37 37 | 700 17.78 | 67 1.70 | 838 1247 | 215 215 | 255 255 | 290 290 |
113050 | 300 KCMIL 300 KCMIL | 1 1 | 37 37 | 753 19.13 | 67 1.70 | 998 1485 | 240 240 | 285 285 | 320 320 |
113068 | 350 KCMIL 350 KCMIL | 1 1 | 37 37 | 803 20.40 | 67 1.70 | 1158 1723 | 260 260 | 310 310 | 350 350 |
113076 | 400 KCMIL 400 KCMIL | 1 1 | 37 37 | 848 21.54 | 67 1.70 | 1317 1960 | 280 280 | 335 335 | 380 380 |
113084 | 500 KCMIL 500 KCMIL | 1 1 | 37 37 | 908 23.06 | 67 1.70 | 1633 2430 | 320 320 | 380 380 | 430 430 |
113092 | 600 KCMIL 600 KCMIL | 1 1 | 61 61 | 1038 26.37 | 82 2.08 | 1973 2936 | 350 350 | 420 420 | 475 475 |
586272 | 700 KCMIL 700 KCMIL | 1 1 | 61 61 | 1107 28.12 | 82 2.08 | 2291 3409 | 385 385 | 460 460 | 520 520 |
113100 | 750 KCMIL 750 KCMIL | 1 1 | 61 61 | 1140 28.96 | 82 2.08 | 2449 3645 | 400 400 | 475 475 | 535 535 |
113134 | 1000 KCMIL 1000 KCMIL | 1 1 | 61 61 | 1281 32.54 | 82 2.08 | 3233 4812 | 455 455 | 545 545 | 615 615 |
Southwire® SIMpull XHHW-2® copper conductors comply with the following:
Southwire® SIMpull XHHW-2® copper conductors are annealed (soft) copper. Insulation is an abrasion, moisture, and heat resistant thermoset cross-linked polyethylene (XLPE). Conductor sizes 8 AWG and larger are marked sunlight resistant. Colors are available and may be subject to economic order quantity.