SPEC: 13008

Southwire CL4SS™ Class 4 Shielded Outdoor / General Purpose SPEC13008

Download Category Specifications
PDF Excel Table

Application & Features

Intended for use in Fault Managed Power Systems (FMPS), remote powering, indoor Class 4 circuits per 2023 National Electrical Code (NEC) article 726. For use, primarily, in Agriculture, Intelligent Buildings, and Wireless Densification. The power source (transmitter) for Class 4 circuits shall be supplied from a power source that has a voltage output of 450 volts (peak or DC) or less. The CL4Z cables are considered for outdoor use only and are not to be attached to or used within a building structure. Type CL4Z cables comply with the applicable requirements for CL4. The CMG cables can be installed in buildings according to NEC article 722.135 and table 722.135(B).

Ratings:
Normal operating temperature: 90°C
Temperature Range: -40°C to 90°C
Rated Use: Dry or wet locations

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm)
More Options
18 AWG 18 AWG
2 2
19 19
0.045 0.11
17 0.43
25 0.64
0.349 0.89
26 39
6.669 9.92
1.4 3.56
More Options
18 AWG 18 AWG
4 4
19 19
0.045 0.11
17 0.43
25 0.64
0.376 0.96
50 74
6.669 9.92
1.5 3.81
More Options
18 AWG 18 AWG
8 8
19 19
0.045 0.11
17 0.43
37 0.94
0.417 1.06
88 131
6.669 9.92
1.7 4.32
More Options
16 AWG 16 AWG
2 2
19 19
0.056 0.14
17 0.43
25 0.64
0.376 0.96
70 104
4.181 6.22
1.5 3.81
More Options
16 AWG 16 AWG
4 4
19 19
0.056 0.14
17 0.43
32 0.81
0.403 1.02
113 168
4.181 6.22
1.6 4.06
More Options
16 AWG 16 AWG
8 8
19 19
0.056 0.14
17 0.43
37 0.94
0.481 1.22
125 186
4.181 6.22
1.9 4.83
More Options
14 AWG 14 AWG
2 2
7 7
0.070 0.18
22 0.56
32 0.81
0.467 1.19
112 167
2.631 3.92
1.9 4.83
More Options
14 AWG 14 AWG
4 4
7 7
0.070 0.18
22 0.56
37 0.94
0.543 1.38
183 272
2.631 3.92
2.2 5.59
More Options
14 AWG 14 AWG
8 8
7 7
0.070 0.18
22 0.56
37 0.94
0.780 1.98
370 551
2.631 3.92
3.1 7.87

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Size
AWG
Capacitance
pF/ft
18 18
<30 <30
16 16
<30 <30
14 14
<30 <30
2 Pair
1 Black & Red
4 Pair
1 Black & Red
8 Pair
1 Black & Red
2 Black & White 2 Black & White
2 Black & White 2 Black & White
2 Black & White 2 Black & White
3 Black & Green 3 Black & Green
3 Black & Green 3 Black & Green
4 Black & Blue 4 Black & Blue
4 Black & Blue 4 Black & Blue
5 Black & Yellow 5 Black & Yellow
6 Black & Brown 6 Black & Brown
7 Black & Orange 7 Black & Orange
8 Black & White 8 Black & White

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1400-2 Fault-Managed Power Systems - Part 2: Requirements for Cables
  • UL 444 Communications Cables

Construction

  1. Conductor:Class B or C stranded soft-drawn bare copper per ASTM B3 and B8
  2. Insulation:Twisted pair(s) with premium grade, lead-free, flame-retardant, Polyvinyl Chloride (PVC). See Table 4 for pair(s) numbers and colors.
  3. ShieldAluminum foil shield
  4. Jacket: Lead-free, flame-retardant, LS, Polyvinyl Chloride (PVC). See Table 5 for available jacket colors.