SPEC: 45410

AL 2000V XLPE Insulation. RHH/RHW-2 PV SPEC45410

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Aluminum Conductor XLPE Insulation. Sizes 6 AWG through 1000 kcmil. Heat, Moisture, and Sunlight Resistant RoHS. 90°C

Download Category Specifications
PDF Excel Table

Application & Features

The cable is available in sizes 6 AWG through 1000 kcmil. The product is approved for use in solar power applications per the NEC article 690 and is rated 90°C for exposed or concealed wiring in wet or dry locations. Individual conductors are stranded aluminum alloy covered with a cross-linked polyethylene (XLPE) insulation and is rated for direct burial. The cable is sunlight resistant, oil resistant PRI and PRII, RoHS compliant, passes -40°C cold bend. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Approx. OD (inches) (cm) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
6 AWG 6 AWG
1 1
7 7
0.169 0.43
85 2.16
0.349 0.89
24 36
59 88
More Options
4 AWG 4 AWG
1 1
7 7
0.212 0.54
85 2.16
0.383 0.97
39 58
77 115
More Options
2 AWG 2 AWG
1 1
6 6
0.268 0.68
85 2.16
0.438 1.11
62 92
104 155
More Options
1 AWG 1 AWG
1 1
8 8
0.298 0.76
105 2.67
0.519 1.32
78 116
146 217
More Options
1/0 AWG 1/0 AWG
1 1
10 10
0.336 0.85
105 2.67
0.546 1.39
99 147
164 244
More Options
2/0 AWG 2/0 AWG
1 1
12 12
0.376 0.96
105 2.67
0.586 1.49
125 186
195 290
More Options
3/0 AWG 3/0 AWG
1 1
16 16
0.422 1.07
105 2.67
0.633 1.61
158 235
235 350
More Options
4/0 AWG 4/0 AWG
1 1
19 19
0.474 1.20
105 2.67
0.685 1.74
199 296
284 423
More Options
250 KCMIL 250 KCMIL
1 1
22 22
0.520 1.32
120 3.05
0.760 1.93
235 350
350 521
More Options
300 KCMIL 300 KCMIL
1 1
21 21
0.569 1.45
120 3.05
0.810 2.06
282 420
397 591
More Options
350 KCMIL 350 KCMIL
1 1
35 35
0.615 1.56
120 3.05
0.856 2.17
329 490
462 688
More Options
400 KCMIL 400 KCMIL
1 1
35 35
0.659 1.67
120 3.05
0.899 2.28
376 560
518 771
More Options
500 KCMIL 500 KCMIL
1 1
34 34
0.735 1.87
120 3.05
0.978 2.48
471 701
615 915
More Options
600 KCMIL 600 KCMIL
1 1
37 37
0.812 2.06
135 3.43
1.083 2.75
565 841
745 1109
More Options
700 KCMIL 700 KCMIL
1 1
58 58
0.877 2.23
135 3.43
1.147 2.91
659 981
851 1266
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.908 2.31
135 3.43
1.178 2.99
706 1051
904 1345
More Options
1000 KCMIL 1000 KCMIL
1 1
58 58
1.060 2.69
135 3.43
1.330 3.38
942 1402
1168 1738

* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
6 AWG 6 AWG
1 1
1.4 3.56
157 71.21
0.674 1.00
0.812 1.21
0.051 0.08
50 50
55 55
More Options
4 AWG 4 AWG
1 1
1.5 3.81
250 113.40
0.424 0.63
0.510 0.76
0.048 0.07
65 65
75 75
More Options
2 AWG 2 AWG
1 1
1.8 4.57
398 180.53
0.267 0.40
0.321 0.48
0.045 0.07
90 90
100 100
More Options
1 AWG 1 AWG
1 1
2.1 5.33
502 227.70
0.211 0.31
0.254 0.38
0.046 0.07
100 100
115 115
More Options
1/0 AWG 1/0 AWG
1 1
2.2 5.59
633 287.12
0.168 0.25
0.201 0.30
0.044 0.07
120 120
135 135
More Options
2/0 AWG 2/0 AWG
1 1
2.3 5.84
798 361.97
0.133 0.20
0.160 0.24
0.043 0.06
135 135
150 150
More Options
3/0 AWG 3/0 AWG
1 1
2.5 6.35
1006 456.31
0.105 0.16
0.126 0.19
0.042 0.06
155 155
175 175
More Options
4/0 AWG 4/0 AWG
1 1
2.7 6.86
1269 575.61
0.084 0.13
0.100 0.15
0.041 0.06
180 180
205 205
More Options
250 KCMIL 250 KCMIL
1 1
3.0 7.62
1500 680.39
0.071 0.11
0.086 0.13
0.041 0.06
205 205
230 230
More Options
300 KCMIL 300 KCMIL
1 1
3.2 8.13
1800 816.47
0.059 0.09
0.071 0.11
0.041 0.06
230 230
260 260
More Options
350 KCMIL 350 KCMIL
1 1
3.4 8.64
2100 952.54
0.050 0.07
0.062 0.09
0.040 0.06
250 250
280 280
More Options
400 KCMIL 400 KCMIL
1 1
3.6 9.14
2400 1088.62
0.044 0.07
0.054 0.08
0.040 0.06
270 270
305 305
More Options
500 KCMIL 500 KCMIL
1 1
3.9 9.91
3000 1360.78
0.035 0.05
0.044 0.07
0.039 0.06
310 310
350 350
More Options
600 KCMIL 600 KCMIL
1 1
5.4 13.72
3600 1632.93
0.029 0.04
0.037 0.06
0.039 0.06
340 340
385 385
More Options
700 KCMIL 700 KCMIL
1 1
5.7 14.48
4200 1905.09
0.025 0.04
0.033 0.05
0.038 0.06
375 375
425 425
More Options
750 KCMIL 750 KCMIL
1 1
5.9 14.99
4500 2041.16
0.024 0.04
0.031 0.05
0.038 0.06
385 385
435 435
More Options
1000 KCMIL 1000 KCMIL
1 1
6.7 17.02
6000 2721.55
0.018 0.03
0.025 0.04
0.037 0.06
445 445
500 500

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size Black Brown Orange Yellow White Red Green
AWG/Kcmil AWG/Kcmil
6 6
585843
4 4
586673
2 2
586672
589171
1 1
619879
589051
1/0 1/0
591256
591241
2/0 2/0
583673
3/0 3/0
577100
669515
669516
669517
577843
669518
4/0 4/0
583678
597698
607400
591242
250 250
577101
577844
668535
300 300
584290
589170
675225
350 350
582174
597996
592618
400 400
584291
596689
652801
500 500
582267
591243
591244
591245
586671
588797
591246
600 600
585499
591247
588799
700 700
607592 607592
591248
591249
591250
750 750
592619
1000 1000
641387
641386

Standards & References

  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 4703 Standard for Photovoltaic Wire
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • VW-1 Vertical-Wire Flame Test (Optional)
  • AA 8176 Stranded Aluminum Alloy Conductors

Construction

  1. Conductor:AlumaFlex® Compact Stranded Aluminum Alloy (AA-8176)
  2. Insulation:Cross-linked Polyethylene (XLPE)

Resources

There are no downloadable resources for this product.