Armorlite® Type MC Multi-Circuit MC35

12/2 AWG Copper THHN/THWN Insulated Singles. Multiple Circuits. Green Insulated Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire Armorlite® Type MC Cable - Multi-Circuit is suitable for use as follows:

  • Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.

Specifications

Select a set of products below for more information:
Conductor Ground Wire Neutral Wire
Size (AWG or kcmil) (mm2) No. of Conductors Stranding Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Size (AWG) Ground Size UOM Size (AWG) Conductor Colors
More Options
12 AWG 12 AWG
4 4
Solid Solid
540 13.73
159 237
12 12
AWG AWG
12 12
BLU, RED, WHT-BLU, WHT-RED, GRN BLU, RED, WHT-BLU, WHT-RED, GRN
More Options
12 AWG 12 AWG
4 4
Stranded Stranded
608 15.44
194 289
12 12
AWG AWG
12 12
RED/BLU/GRN/GRN-YLW/WHT-BLU/WHT-RED RED/BLU/GRN/GRN-YLW/WHT-BLU/WHT-RED
More Options
12 AWG 12 AWG
6 6
Solid Solid
587 14.91
341 507
12 12
AWG AWG
12 12
BLK/RED/BLU/GRN/WHT-BLK/WHT-RED/WHT-BLU BLK/RED/BLU/GRN/WHT-BLK/WHT-RED/WHT-BLU
More Options
12 AWG 12 AWG
8 8
Solid Solid
700 17.79
294 437
12 12
AWG AWG
12 12
BK, RD, BU, OR, GN, GN-YW, WT, WT-BK, WT-RD, WT-BU BK, RD, BU, OR, GN, GN-YW, WT, WT-BK, WT-RD, WT-BU
More Options
12 AWG 12 AWG
8 8
Stranded Stranded
688 17.49
277 412
12 12
AWG AWG
12 12
BLK, BLK-WHT, WHT, WHT-BLK, RED, RED-WHT, BLU, GRN, BLU-WHT BLK, BLK-WHT, WHT, WHT-BLK, RED, RED-WHT, BLU, GRN, BLU-WHT
More Options
12 AWG 12 AWG
9 9
Solid Solid
843 21.42
338 504
12 12
AWG AWG
12 12
BK1, RD1, WE1, BK2, RD2, WE2,BK3, RD3, WE3 BK1, RD1, WE1, BK2, RD2, WE2,BK3, RD3, WE3
More Options
10 AWG 10 AWG
4 4
Solid Solid
624 15.86
232 345
10 10
AWG AWG
10 10
ORG, YLW, GRN, GRY-ORG, GRY-YLW ORG, YLW, GRN, GRY-ORG, GRY-YLW
More Options
10 AWG 10 AWG
4 4
Stranded Stranded
665 16.91
251 373
10 10
AWG AWG
10 10
BLK, BLU, GRN, WHT-BLK, WHT-BLU BLK, BLU, GRN, WHT-BLK, WHT-BLU
More Options
10 AWG 10 AWG
6 6
Solid Solid
670 17.04
310 462
10 10
AWG AWG
10 10
BRN, ORG, YLW, GRY-BRN, GRY-ORG, GRY-YLW, GRN BRN, ORG, YLW, GRY-BRN, GRY-ORG, GRY-YLW, GRN
More Options
10 AWG 10 AWG
6 6
Stranded Stranded
775 19.70
366 544
10 10
AWG AWG
10 10
BLK, RED, BLK-BLU, RED-BLU, WHT, WHT-BLU, GRN BLK, RED, BLK-BLU, RED-BLU, WHT, WHT-BLU, GRN
More Options
10 AWG 10 AWG
8 8
Solid Solid
823 20.92
425 632
10 10
AWG AWG
10 10
BRN, ORG, YLW, PUR, GRY-BRN, GRY-ORG, GRY-YLW, GRY-PUR, GRN BRN, ORG, YLW, PUR, GRY-BRN, GRY-ORG, GRY-YLW, GRY-PUR, GRN
More Options
10 AWG 10 AWG
9 9
Stranded Stranded
944 24.00
505 752
10 10
AWG AWG
10 10
BK, BK, RD, RD, BU, BU, WT-BK, WT-RD, WT-BU, GN BK, BK, RD, RD, BU, BU, WT-BK, WT-RD, WT-BU, GN
More Options
10 AWG 10 AWG
10 10
Solid Solid
883 22.44
506 753
10 10
AWG AWG
10 10
BKWT-BK BKWT-BK
More Options
10 AWG 10 AWG
10 10
Stranded Stranded
944 24.00
545 811
10 10
AWG AWG
10 10
BK, RD, BK-WT, BK-RD, RD-WT, WT, WT-RD, WT-BU, WT-BK, WT-PK, GN BK, RD, BK-WT, BK-RD, RD-WT, WT, WT-RD, WT-BU, WT-BK, WT-PK, GN
More Options
10 AWG 10 AWG
12 12
Solid Solid
946 24.05
626 932
10 10
AWG AWG
10 10
BK, RD, BU, OR, YW, BN, WT-BK, WT-RD, WT-BU, WT-OR, WT-YW, WT-BN, GN, GN-YW BK, RD, BU, OR, YW, BN, WT-BK, WT-RD, WT-BU, WT-OR, WT-YW, WT-BN, GN, GN-YW
More Options
10 AWG 10 AWG
12 12
Stranded Stranded
1014 25.76
633 942
10 10
AWG AWG
10 10
BK, BK, RD, RD, BU, BU, WT, WT, WT, WT, WT, WT, GN BK, BK, RD, RD, BU, BU, WT, WT, WT, WT, WT, WT, GN
More Options
8 AWG 8 AWG
12 12
Stranded Stranded
1206 30.65
947 1409
10 10
AWG AWG
8 8
BK, RD, BU, WT, BK, RD, BU, WT, BK, RD, WT, WT, GN BK, RD, BU, WT, BK, RD, BU, WT, BK, RD, WT, WT, GN
More Options
6 AWG 6 AWG
8 8
Stranded Stranded
1164 29.59
979 1456
8 8
AWG AWG
6 6
1, 1, 1, 1, 2, 2, 2, 2, 8 GRNGND 1, 1, 1, 1, 2, 2, 2, 2, 8 GRNGND

Standards & References

Southwire's Armorlite® Type MC Cable - Multi-Circuit meets or exceeds the following requirements:

  • UL 83
  • UL 1569
  • UL 1685
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Jacketed & Non Jacketed will both pass " UL Test" & "FT4/IEEE 1202" (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire Armorlite® Type MC Cable - Multi-Circuit is constructed with 14 awg through 10 awg softdrawn copper Type THHN/THWN conductors rated 90°C dry, and a green insulated grounding conductor. The conductors are cabled together and a binder tape bearing the print legend is wrapped around the assembly. Aluminum interlocking armor is applied over the assembly. An optional PVC jacket can be applied over the armored assembly.