SPEC: 25251

AL XLPE Type RPVU90 2KV SPEC25251

Single Aluminum Conductors, 1000V/2000V, 90°C MAX - 40°C MIN, Sunlight Resistant and FT4 Flame Test Rated

Download Category Specifications
PDF Excel Table

Application & Features

Single aluminum conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Sunlight Resistant. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Approx. OD (in) (cm) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
300 KCMIL 300 KCMIL
1 1
35 35
0.569 1.45
110 2.79
0.802 2.04
282 420
423 629
More Options
350 KCMIL 350 KCMIL
1 1
35 35
0.615 1.56
110 2.79
0.836 2.12
329 490
471 701
More Options
500 KCMIL 500 KCMIL
1 1
34 34
0.735 1.87
110 2.79
0.966 2.45
471 701
644 958
More Options
600 KCMIL 600 KCMIL
1 1
41 41
0.812 2.06
125 3.18
1.055 2.68
565 841
770 1146
More Options
750 KCMIL 750 KCMIL
1 1
53 53
0.908 2.31
125 3.18
1.170 2.97
706 1051
947 1409

* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
300 KCMIL 300 KCMIL
1 1
3.2 8.13
1800 816.47
0.059 0.09
0.071 0.11
0.041 0.06
230 230
260 260
More Options
350 KCMIL 350 KCMIL
1 1
3.3 8.38
2100 952.54
0.050 0.07
0.062 0.09
0.040 0.06
250 250
280 280
More Options
500 KCMIL 500 KCMIL
1 1
3.8 9.65
3000 1360.78
0.035 0.05
0.044 0.07
0.039 0.06
310 310
350 350
More Options
600 KCMIL 600 KCMIL
1 1
5.2 13.21
3600 1632.93
0.029 0.04
0.037 0.06
0.039 0.06
340 340
385 385
More Options
750 KCMIL 750 KCMIL
1 1
5.8 14.73
4500 2041.16
0.024 0.04
0.031 0.05
0.038 0.06
385 385
435 435

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Stock Code Size AWG Color
672572 672572
350 350
Red Red
663032 663032
600 600
Red Red
669289 669289
750 750
Red Red

Standards & References

  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • RoHS Compliant Lead-Free, Silicone-Free, Halogen Free
  • AA 8176 Stranded Aluminum Alloy Conductors
  • CSA Standard C22.2 No. 271 Photovoltaic Cables

Construction

  1. Conductor:AlumaFlex® Compact Stranded Aluminum Alloy (AA-8176)
  2. Insulation:Cross Linked Polyethylene (XLPE)

Resources

There are no downloadable resources for this product.