Single aluminum conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Sunlight Resistant. This product meets the current RoHS requirements. No lead is added or used in manufacturing.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Approx. OD (in) (cm) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
600 KCMIL
600 KCMIL
|
1
1
|
41
41
|
0.812
2.06
|
125
3.18
|
1.055
2.68
|
565
841
|
770
1146
|
| More Options |
300 KCMIL
300 KCMIL
|
1
1
|
35
35
|
0.569
1.45
|
110
2.79
|
0.802
2.04
|
282
420
|
423
629
|
* Strand count meets minimum number per ASTM
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
600 KCMIL
600 KCMIL
|
1
1
|
5.2
13.21
|
3600
1632.93
|
0.029
0.04
|
0.037
0.06
|
0.039
0.06
|
340
340
|
385
385
|
| More Options |
300 KCMIL
300 KCMIL
|
1
1
|
3.2
8.13
|
1800
816.47
|
0.059
0.09
|
0.071
0.11
|
0.041
0.06
|
230
230
|
260
260
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
| Stock Code | Size AWG | Color |
|
672572
672572
|
350
350
|
Red
Red
|
|
663032
663032
|
600
600
|
Red
Red
|
|
669289
669289
|
750
750
|
Red
Red
|