ACSS/TW ALBARE10

Aluminum Conductor, Steel Supported. Trapezoidal Shaped Aluminum Strands. Bare.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire's ACSS/TW is designed for overhead distribution and transmission lines. It is designed to operate continuously at elevated temperatures up to 250°C without loss of strength, it sags less under emergency electrical loadings than ACSR/TW, excellent self-damping properties, and its final sags are not affected by long-term creep of aluminum. Southwire's ACSS/TW is available in equal area and equal diameter design. The equal area design allows equal ampacity in a smaller diameter conductor when compared with a standard ACSS conductor. The equal diameter design allows more ampacity in an equal diameter conductor when compared with a standard ACSS conductor. ACSS/TW also provides many design opportunities for new line construction: i.e., reduced tower cost, decreased sag, increased self-damping properties, increased operating temperature and improved corrosion resistance.

Specifications

Select a set of products below for more information:
Codeword Size (AWG or kcmil) (mm2) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
ORIOLE ORIOLE
336.4 KCMIL 336.4 KCMIL
16 16
693 17.60
542 807
More Options
HAWK HAWK
477 KCMIL 477 KCMIL
18 18
790 20.07
656 976
More Options
DOVE DOVE
556.5 KCMIL 556.5 KCMIL
20 20
850 21.60
765 1138
More Options
GROSBEAK GROSBEAK
636 KCMIL 636 KCMIL
20 20
910 23.11
887 1321
More Options
OSWEGO OSWEGO
664.8 KCMIL 664.8 KCMIL
20 20
930 23.62
935 1392
More Options
WABASH WABASH
762.8 KCMIL 762.8 KCMIL
20 20
990 25.15
1047 1557
More Options
MAUMEE MAUMEE
768.2 KCMIL 768.2 KCMIL
20 20
977 24.82
987 1469
More Options
DRAKE DRAKE
795 KCMIL 795 KCMIL
20 20
1010 25.65
1091 1624
More Options
CARDINAL CARDINAL
954 KCMIL 954 KCMIL
20 20
1080 27.43
1224 1822
More Options
SUWANNEE SUWANNEE
959.6 KCMIL 959.6 KCMIL
22 22
1110 28.20
1317 1959
More Options
CURLEW CURLEW
1033.5 KCMIL 1033.5 KCMIL
22 22
1130 28.72
1326 1974
More Options
HUDSON HUDSON
1158.4 KCMIL 1158.4 KCMIL
24 24
1196 30.38
1488 2214
More Options
GRACKLE GRACKLE
1192.5 KCMIL 1192.5 KCMIL
38 38
1225 31.12
1531 2278
More Options
YUKON YUKON
1233.6 KCMIL 1233.6 KCMIL
38 38
1245 31.62
1583 2357
More Options
PHEASANT PHEASANT
1272 KCMIL 1272 KCMIL
39 39
1260 32.00
1630 2426
More Options
MERRIMACK MERRIMACK
1433.6 KCMIL 1433.6 KCMIL
39 39
1340 34.04
1840 2738
More Options
LAPWING LAPWING
1590 KCMIL 1590 KCMIL
36 36
1358 34.49
1790 2664
More Options
PECOS PECOS
1622 KCMIL 1622 KCMIL
39 39
1420 36.07
2107 3135
More Options
1926.9 KCMIL 1926.9 KCMIL
42 42
1549 39.37
2471 3677
More Options
SANTEE SANTEE
2627.3 KCMIL 2627.3 KCMIL
64 64
1760 44.71
3062 4557
More Options
null null null null
0 0
1110 28.19
1316 1958

Standards & References

Southwire's ACSS/TW conductor meets or exceeds the following ASTM specifications:

  • B500 Metallic Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced.
  • B609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • B802 Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced.
  • B803 High-Strength Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum and Aluminum-Alloy Conductors, Steel Reinforced.
  • B857 Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Supported (ACSS/TW).

Construction

ACSS is a composite concentric-lay-stranded conductor. Steel strands form the central core of the conductor with one or more layers of 63% minimum average conductivity aluminum 1350-0 wire stranded around it. The steel core carries most or all of the mechanical load of the conductor due to the "0" (fully annealed or soft) temper aluminum. Steel core wires are protected from corrosion by Galfan® , zinc-5% aluminum-mischmetal alloy coating. Southwire's ACSS is batch annealed to ensure superior sag and installation performance. High strength steel core, aluminized, and aluminum clad steel core is also available.