This specification covers the construction requirements for a limited smoke, non-halogenated power cable insulated with TelcoHyde® 5221. UL listed Type RHH, FT4-ST1 in accordance with the National Electrical Code. Product is for use in Central Office, CATV Head End, Data Center and Cell tower applications. Cable is suitable for UL “CT USE” (Cable Tray rated).
Conductor | Allowable Ampacities+ | ||||||
Size (AWG or kcmil) (mm2) | No. of Strands | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 75C | Allowable Ampacity at 90C | Insulation Thickness (mils) (mm) | DC Resistance at 25°C | |
More Options |
14 AWG
14 AWG
|
41
41
|
26
39
|
20
20
|
25
25
|
45
1.14
|
2.73
2.73
|
More Options |
12 AWG
12 AWG
|
65
65
|
35
52
|
25
25
|
30
30
|
45
1.14
|
1.72
1.72
|
More Options |
10 AWG
10 AWG
|
104
104
|
49
74
|
35
35
|
40
40
|
45
1.14
|
1.08
1.08
|
More Options |
8 AWG
8 AWG
|
41
41
|
83
123
|
50
50
|
55
55
|
60
1.52
|
0.679
0.679
|
More Options |
6 AWG
6 AWG
|
65
65
|
117
174
|
65
65
|
75
75
|
60
1.52
|
0.436
0.436
|
More Options |
4 AWG
4 AWG
|
126
126
|
198
294
|
65
65
|
95
95
|
60
1.52
|
0.274
0.274
|
More Options |
2 AWG
2 AWG
|
168
168
|
252
375
|
115
115
|
130
130
|
60
1.52
|
0.172
0.172
|
More Options |
1/0 AWG
1/0 AWG
|
266
266
|
417
621
|
150
150
|
170
170
|
80
2.03
|
0.109
0.109
|
More Options |
2/0 AWG
2/0 AWG
|
342
342
|
525
782
|
175
175
|
195
195
|
80
2.03
|
0.0565
0.0565
|
More Options |
4/0 AWG
4/0 AWG
|
532
532
|
759
1130
|
230
230
|
260
260
|
80
2.03
|
0.0546
0.0546
|
More Options |
350 KCMIL
350 KCMIL
|
888
888
|
1265
1883
|
310
310
|
350
350
|
95
2.41
|
0.0334
0.0334
|
More Options |
500 KCMIL
500 KCMIL
|
1221
1221
|
1733
2579
|
|
|
95
2.41
|
|
More Options |
750 KCMIL
750 KCMIL
|
1850
1850
|
2713
4038
|
475
475
|
535
535
|
110
2.79
|
0.0157
0.0157
|