This specification covers the construction requirements for a limited smoke, non-halogenated power cable insulated with TelcoHyde® 5221. UL listed Type RHH, FT4-ST1 in accordance with the National Electrical Code. Product is for use in Central Office, CATV Head End, Data Center and Cell tower applications. Cable is suitable for UL “CT USE” (Cable Tray rated).
Conductor | Allowable Ampacities+ | |||||||
Size (AWG or kcmil) | No. of Strands | Nom. OD (Conductor) (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity at 75C | Allowable Ampacity at 90C | Insulation Thickness (mils) (mm) | DC Resistance at 25°C | |
588680 | 14 AWG 14 AWG | 41 41 | 26 39 | 20 20 | 25 25 | 45 1.14 | 2.73 2.73 | |
588678 | 12 AWG 12 AWG | 65 65 | 35 52 | 25 25 | 30 30 | 45 1.14 | 1.72 1.72 | |
588676 | 10 AWG 10 AWG | 105 105 | 49 73 | 35 35 | 40 40 | 45 1.14 | 1.08 1.08 | |
569875 | 8 AWG 8 AWG | 41 41 | 82 122 | 50 50 | 55 55 | 60 1.52 | 0.679 0.679 | |
569858 | 6 AWG 6 AWG | 65 65 | 117 174 | 65 65 | 75 75 | 60 1.52 | 0.436 0.436 | |
569817 | 4 AWG 4 AWG | 126 126 | 195 290 | 65 65 | 95 95 | 60 1.52 | 0.274 0.274 | |
569745 | 2 AWG 2 AWG | 168 168 | 244 363 | 115 115 | 130 130 | 60 1.52 | 0.172 0.172 | |
569659 | 1/0 AWG 1/0 AWG | 266 266 | 421 626 | 150 150 | 170 170 | 80 2.03 | 0.109 0.109 | |
569770 | 2/0 AWG 2/0 AWG | 342 342 | 520 773 | 175 175 | 195 195 | 80 2.03 | 0.0565 0.0565 | |
569838 | 4/0 AWG 4/0 AWG | 532 532 | 749 1115 | 230 230 | 260 260 | 80 2.03 | 0.0546 0.0546 | |
569797 | 350 KCMIL 350 KCMIL | 888 888 | 1266 1885 | 310 310 | 350 350 | 95 2.41 | 0.0334 0.0334 | |
569626 | 500 KCMIL 500 KCMIL | 1221 1221 | 1731 2577 | 95 2.41 | ||||
569603 | 750 KCMIL 750 KCMIL | 1850 1850 | 2713 4038 | 475 475 | 535 535 | 110 2.79 | 0.0157 0.0157 |