Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Only UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
625934 |
2
2
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
357
9.07
|
70
104
|
|
625838 |
3
3
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
377
9.60
|
87
130
|
|
625833 |
4
4
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
410
10.44
|
110
163
|
|
625828 |
5
5
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
447
11.38
|
128
191
|
|
625824 |
7
7
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
486
12.36
|
168
249
|
|
625819 |
9
9
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
595
15.14
|
227
338
|
|
625815 |
12
12
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
667
16.94
|
291
433
|
|
625781 |
15
15
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
738
18.76
|
354
527
|
|
625807 |
19
19
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
776
19.71
|
432
643
|
|
607513 |
4
4
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
461
11.72
|
147
219
|
|
607521 |
9
9
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
667
16.95
|
315
469
|
|
622186 |
12
12
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
740
18.81
|
402
598
|
|
607514 |
15
15
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
869
22.08
|
535
796
|
|
622195 |
2
2
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
448
11.38
|
121
180
|
|
607512 |
4
4
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
562
14.27
|
228
339
|
|
662067 |
12
12
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
879
22.34
|
607
904
|
|