SPEC: 45503

TCU 2000V NLEPR Insulation Thermoset LSZH-TS Jacket. RHH/RHW-2 SPEC45503

Power Cable 2000 Volt Single Conductor Copper or Tinned Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 Thermoset SOLONON® (LSZH-TS) Jacket

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
1/0 AWG 1/0 AWG
1 1
19 19
0.362 0.92
65 1.65
45 1.14
0.598 1.52
326 485
428 637
More Options
250 KCMIL 250 KCMIL
1 1
259 259
0.610 1.55
105 2.67
65 1.65
0.972 2.47
811 1207
1069 1591
More Options
500 KCMIL 500 KCMIL
1 1
259 259
0.890 2.26
105 2.67
65 1.65
1.252 3.18
1579 2350
1924 2863
More Options
750 KCMIL 750 KCMIL
1 1
61 61
0.968 2.46
90 2.29
65 1.65
1.297 3.29
2316 3447
2650 3944
More Options
750 KCMIL 750 KCMIL
1 1
127 127
0.968 2.46
90 2.29
65 1.65
1.300 3.30
2315 3445
2652 3947
More Options
1000 KCMIL 1000 KCMIL
1 1
127 127
1.118 2.84
90 2.29
65 1.65
1.450 3.68
3088 4595
3468 5161
More Options
2000 KCMIL 2000 KCMIL
1 1
127 127
1.583 4.02
115 2.92
95 2.41
2.031 5.16
6175 9189
6903 10273

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
1/0 AWG 1/0 AWG
1 1
4.7 11.94
845 383.29
0.102 0.15
0.122 0.18
0.044 0.07
150 150
170 170
More Options
250 KCMIL 250 KCMIL
1 1
7.8 19.81
2000 907.18
0.043 0.06
0.053 0.08
0.041 0.06
255 255
290 290
More Options
500 KCMIL 500 KCMIL
1 1
10.0 25.40
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
750 KCMIL 750 KCMIL
1 1
10.2 25.91
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
More Options
750 KCMIL 750 KCMIL
1 1
10.4 26.42
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
More Options
1000 KCMIL 1000 KCMIL
1 1
11.6 29.46
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615
More Options
2000 KCMIL 2000 KCMIL
1 1
16.0 40.64
10000 4535.92
0.005 0.01
0.016 0.02
0.034 0.05
665 665
750 750

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B173 Rope-Lay-Stranded Copper Conductors Having Concentric-Stranded Members
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (250kcmil & Larger)
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways (non-emergency circuits only)
  • AREMA 10.3.13 Recommended Design Criteria for Low-Smoke Halogen Free (LSHF) Polymeric Cable Jackets

Construction

  1. Conductor:Stranded tinned copper per ASTM B33 and B8, B172, or B173
  2. Binder Tape:Mylar tape
  3. Insulation:Ethylene Propylene Rubber (EPR)
  4. Overall Jacket:Cross-linked/Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS)