Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated. Sunlight Resistant - For Direct Burial - Silicone Free
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
591981 |
3
3
|
8 AWG
8 AWG
|
7
7
|
45
1.14
|
10
10
|
|
647
16.43
|
308
458
|
|
591983 |
3
3
|
6 AWG
6 AWG
|
7
7
|
45
1.14
|
8
8
|
|
724
18.39
|
442
657
|
|
591985 |
3
3
|
4 AWG
4 AWG
|
7
7
|
45
1.14
|
8
8
|
|
853
21.67
|
634
944
|
|
591987 |
3
3
|
2 AWG
2 AWG
|
7
7
|
45
1.14
|
6
6
|
|
978
24.84
|
930
1384
|
|
591989 |
3
3
|
1 AWG
1 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1162
29.51
|
1199
1784
|
|
591991 |
3
3
|
1/0 AWG
1/0 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1216
30.89
|
1407
2094
|
|
591993 |
3
3
|
2/0 AWG
2/0 AWG
|
19
19
|
55
1.40
|
6
6
|
|
1329
33.76
|
1720
2559
|
|
591995 |
3
3
|
3/0 AWG
3/0 AWG
|
19
19
|
55
1.40
|
4
4
|
|
1437
36.50
|
2128
3166
|
|
591996 |
3
3
|
4/0 AWG
4/0 AWG
|
19
19
|
55
1.40
|
4
4
|
|
1558
39.57
|
2580
3839
|
|
591998 |
3
3
|
250 KCMIL
250 KCMIL
|
37
37
|
65
1.65
|
4
4
|
|
1755
44.58
|
3092
4601
|
|
592000 |
3
3
|
350 KCMIL
350 KCMIL
|
37
37
|
65
1.65
|
3
3
|
|
1990
50.55
|
4168
6202
|
|
592002 |
3
3
|
500 KCMIL
500 KCMIL
|
37
37
|
65
1.65
|
2
2
|
|
2225
56.53
|
5681
8455
|
|