Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. 16 AWG wire is made in accordance with UL 66 Fixture Wire. Sunlight Resistant - For Direct Burial - Silicone Free
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
561312 |
2
2
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
349
8.87
|
67
100
|
|
890159 |
3
3
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
373
9.50
|
93
139
|
|
561313 |
4
4
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
402
10.23
|
111
166
|
|
563383 |
5
5
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
|
|
443
11.28
|
135
201
|
|
597524 |
10
10
|
14 AWG
14 AWG
|
7
7
|
30
0.76
|
12
12
|
|
649
16.49
|
262
390
|
|
574615 |
2
2
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
384
9.76
|
90
134
|
|
890122 |
3
3
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
412
10.46
|
122
181
|
|
561319 |
4
4
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
445
11.31
|
153
227
|
|
574613 |
7
7
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
567
14.42
|
258
384
|
|
574614 |
12
12
|
12 AWG
12 AWG
|
7
7
|
30
0.76
|
|
|
732
18.60
|
411
612
|
|
577144 |
3
3
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
459
11.67
|
166
248
|
|
566720 |
4
4
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
502
12.77
|
214
319
|
|
574619 |
12
12
|
10 AWG
10 AWG
|
7
7
|
30
0.76
|
|
|
879
22.34
|
630
937
|
|