SPEC: 25066

DURAGROUND™ CU 600V XLPE Insulation. RHH/RHW-2/RW90 UL & CSA

Single Copper Conductors, XLPE Insulation, Sunlight Resistant, 600V, 90°C MAX, -40°C MIN, Gasoline & Oil Resistant

Download Category Specifications
PDF Excel Table

Application & Features

Suitable for installation in Cable Trays and Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications.

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Inner Layer Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
6 AWG 6 AWG
1.0 1.0
7 7
0.177 0.45
60 1.52
0.300 0.76
81 121
108 161
More Options
2 AWG 2 AWG
1.0 1.0
7 7
0.282 0.72
60 1.52
0.403 1.02
204 304
245 365
More Options
2/0 AWG 2/0 AWG
1.0 1.0
19 19
0.405 1.03
80 2.03
0.574 1.46
410 610
487 725
More Options
4/0 AWG 4/0 AWG
1.0 1.0
19 19
0.512 1.30
80 2.03
0.666 1.69
653 972
745 1109
More Options
350 KCMIL 350 KCMIL
1.0 1.0
37 37
0.661 1.68
95 2.41
0.841 2.14
1080 1607
1218 1813
More Options
500 KCMIL 500 KCMIL
1.0 1.0
37 37
0.789 2.00
95 2.41
0.966 2.45
1543 2296
1705 2537
More Options
750 KCMIL 750 KCMIL
1.0 1.0
61 61
0.968 2.46
110 2.79
1.200 3.05
2315 3445
2549 3793
More Options
1000 KCMIL 1000 KCMIL
1.0 1.0
61 61
1.117 2.84
110 2.79
1.349 3.43
3087 4594
3354 4991
More Options
350 KCMIL 350 KCMIL
1.0 1.0
37 37
0.661 1.68
95 2.41
0.841 2.14
1080 1607
1218 1813

†Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
6 AWG 6 AWG
1.0 1.0
1.2 3.05
209 94.80
0.411 0.61
0.495 0.74
0.051 0.08
65 65
75 75
More Options
2 AWG 2 AWG
1.0 1.0
1.6 4.06
530 240.40
0.162 0.24
0.195 0.29
0.045 0.07
115 115
130 130
More Options
2/0 AWG 2/0 AWG
1.0 1.0
2.2 5.59
1064 482.62
0.081 0.12
0.097 0.14
0.043 0.06
175 175
195 195
More Options
4/0 AWG 4/0 AWG
1.0 1.0
2.6 6.60
1692 767.48
0.051 0.08
0.062 0.09
0.041 0.06
230 230
260 260
More Options
350 KCMIL 350 KCMIL
1.0 1.0
3.3 8.38
2800 1270.06
0.031 0.05
0.039 0.06
0.040 0.06
310 310
350 350
More Options
500 KCMIL 500 KCMIL
1.0 1.0
3.8 9.65
4000 1814.37
0.022 0.03
0.029 0.04
0.039 0.06
380 380
430 430
More Options
750 KCMIL 750 KCMIL
1.0 1.0
6.0 15.24
6000 2721.55
0.014 0.02
0.022 0.03
0.038 0.06
475 475
535 535
More Options
1000 KCMIL 1000 KCMIL
1.0 1.0
6.7 17.02
8000 3628.74
0.011 0.02
0.018 0.03
0.037 0.06
545 545
615 615
More Options
350 KCMIL 350 KCMIL
1.0 1.0
3.3 8.38
2800 1270.06
0.031 0.05
0.039 0.06
0.040 0.06
310 310
350 350

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • CT USE Sizes 1/0 AWG and Larger
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) Type RW90

Resources