Southwire’s 2000 Volt Type TC-ER VFD power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC-ER) per NEC 336.10.
Gland Reference: Glands
Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
More Options |
14 AWG
14 AWG
|
3
3
|
7
7
|
0.07
0.18
|
60
1.52
|
0.451
1.15
|
60
1.52
|
0.571
1.45
|
93
138
|
202
301
|
More Options |
12 AWG
12 AWG
|
3
3
|
7
7
|
0.088
0.22
|
60
1.52
|
0.486
1.23
|
60
1.52
|
0.606
1.54
|
128
190
|
244
363
|
More Options |
10 AWG
10 AWG
|
3
3
|
7
7
|
0.113
0.29
|
60
1.52
|
0.537
1.36
|
60
1.52
|
0.657
1.67
|
183
272
|
329
490
|
More Options |
8 AWG
8 AWG
|
3
3
|
7
7
|
0.141
0.36
|
70
1.78
|
0.652
1.66
|
60
1.52
|
0.772
1.96
|
270
402
|
456
679
|
More Options |
6 AWG
6 AWG
|
3
3
|
7
7
|
0.177
0.45
|
70
1.78
|
0.723
1.84
|
80
2.03
|
0.883
2.24
|
389
579
|
624
929
|
More Options |
4 AWG
4 AWG
|
3
3
|
7
7
|
0.225
0.57
|
70
1.78
|
0.825
2.10
|
80
2.03
|
0.985
2.50
|
547
814
|
815
1213
|
More Options |
2 AWG
2 AWG
|
3
3
|
7
7
|
0.282
0.72
|
70
1.78
|
0.946
2.40
|
80
2.03
|
1.106
2.81
|
827
1231
|
1121
1668
|
More Options |
1/0 AWG
1/0 AWG
|
3
3
|
19
19
|
0.361
0.92
|
90
2.29
|
1.220
3.10
|
80
2.03
|
1.380
3.51
|
1373
2043
|
1858
2765
|
More Options |
2/0 AWG
2/0 AWG
|
3
3
|
19
19
|
0.405
1.03
|
90
2.29
|
1.311
3.33
|
80
2.03
|
1.471
3.74
|
1640
2441
|
2164
3220
|
More Options |
3/0 AWG
3/0 AWG
|
3
3
|
19
19
|
0.456
1.16
|
90
2.29
|
1.419
3.60
|
80
2.03
|
1.579
4.01
|
2041
3037
|
2604
3875
|
More Options |
4/0 AWG
4/0 AWG
|
3
3
|
19
19
|
0.512
1.30
|
90
2.29
|
1.506
3.83
|
115
2.92
|
1.736
4.41
|
2542
3783
|
3202
4765
|
More Options |
250 KCMIL
250 KCMIL
|
3
3
|
37
37
|
0.558
1.42
|
105
2.67
|
1.665
4.23
|
115
2.92
|
1.895
4.81
|
3150
4688
|
3995
5945
|
More Options |
350 KCMIL
350 KCMIL
|
3
3
|
37
37
|
0.661
1.68
|
105
2.67
|
1.879
4.77
|
115
2.92
|
2.109
5.36
|
4110
6116
|
5098
7587
|
More Options |
500 KCMIL
500 KCMIL
|
3
3
|
37
37
|
0.789
2.00
|
105
2.67
|
2.149
5.46
|
115
2.92
|
2.379
6.04
|
5706
8491
|
6767
10070
|
Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
More Options |
14 AWG
14 AWG
|
3
3
|
6.9
17.53
|
98
44.45
|
2.631
3.92
|
|
|
|
20
20
|
25
25
|
More Options |
12 AWG
12 AWG
|
3
3
|
7.3
18.54
|
156
70.76
|
1.662
2.47
|
2.002
2.98
|
0.057
0.08
|
0.054
0.08
|
25
25
|
30
30
|
More Options |
10 AWG
10 AWG
|
3
3
|
7.9
20.07
|
249
112.94
|
1.040
1.55
|
1.253
1.86
|
0.049
0.07
|
0.050
0.07
|
35
35
|
40
40
|
More Options |
8 AWG
8 AWG
|
3
3
|
9.3
23.62
|
396
179.62
|
0.653
0.97
|
0.786
1.17
|
0.046
0.07
|
0.052
0.08
|
50
50
|
55
55
|
More Options |
6 AWG
6 AWG
|
3
3
|
10.6
26.92
|
629
285.31
|
0.411
0.61
|
0.495
0.74
|
0.039
0.06
|
0.051
0.08
|
65
65
|
75
75
|
More Options |
4 AWG
4 AWG
|
3
3
|
11.8
29.97
|
1001
454.05
|
0.258
0.38
|
0.310
0.46
|
0.032
0.05
|
0.048
0.07
|
85
85
|
95
95
|
More Options |
2 AWG
2 AWG
|
3
3
|
13.3
33.78
|
1592
722.12
|
0.162
0.24
|
0.195
0.29
|
0.027
0.04
|
0.045
0.07
|
115
115
|
130
130
|
More Options |
1/0 AWG
1/0 AWG
|
3
3
|
16.6
42.16
|
2534
1149.40
|
0.102
0.15
|
0.122
0.18
|
0.027
0.04
|
0.044
0.07
|
150
150
|
170
170
|
More Options |
2/0 AWG
2/0 AWG
|
3
3
|
17.7
44.96
|
3194
1448.77
|
0.081
0.12
|
0.097
0.14
|
0.025
0.04
|
0.043
0.06
|
175
175
|
195
195
|
More Options |
3/0 AWG
3/0 AWG
|
3
3
|
18.9
48.01
|
4027
1826.61
|
0.064
0.10
|
0.078
0.12
|
0.022
0.03
|
0.042
0.06
|
200
200
|
225
225
|
More Options |
4/0 AWG
4/0 AWG
|
3
3
|
20.8
52.83
|
5078
2303.34
|
0.051
0.08
|
0.062
0.09
|
0.020
0.03
|
0.041
0.06
|
230
230
|
260
260
|
More Options |
250 KCMIL
250 KCMIL
|
3
3
|
22.7
57.66
|
6000
2721.55
|
0.043
0.06
|
0.053
0.08
|
0.021
0.03
|
0.041
0.06
|
255
255
|
290
290
|
More Options |
350 KCMIL
350 KCMIL
|
3
3
|
25.3
64.26
|
8400
3810.17
|
0.031
0.05
|
0.039
0.06
|
0.018
0.03
|
0.040
0.06
|
310
310
|
350
350
|
More Options |
500 KCMIL
500 KCMIL
|
3
3
|
28.5
72.39
|
12000
5443.10
|
0.022
0.03
|
0.029
0.04
|
0.016
0.02
|
0.039
0.06
|
380
380
|
430
430
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.