SPEC: 45451

CU 2000V XLPE Insulation Three Grounds Cu Tape Shield PVC Jacket. RHH/RHW-2 Variable Frequency Drive (VFD)

Type TC-ER VFD Power Cable 2000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 Polyvinyl Chloride (PVC) Jacket with 3 Symmetrical Bare CU Ground 50% Minimum Tape Shield Overlap. Silicone Free

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 2000 Volt Type TC-ER VFD power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC-ER) per NEC 336.10.

Gland Reference: Glands

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Shield (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
14 AWG 14 AWG
3 3
7 7
0.07 0.18
60 1.52
0.451 1.15
60 1.52
0.571 1.45
93 138
202 301
More Options
12 AWG 12 AWG
3 3
7 7
0.088 0.22
60 1.52
0.486 1.23
60 1.52
0.606 1.54
128 190
244 363
More Options
10 AWG 10 AWG
3 3
7 7
0.113 0.29
60 1.52
0.537 1.36
60 1.52
0.657 1.67
183 272
329 490
More Options
8 AWG 8 AWG
3 3
7 7
0.141 0.36
70 1.78
0.652 1.66
60 1.52
0.772 1.96
270 402
456 679
More Options
6 AWG 6 AWG
3 3
7 7
0.177 0.45
70 1.78
0.723 1.84
80 2.03
0.883 2.24
389 579
624 929
More Options
4 AWG 4 AWG
3 3
7 7
0.225 0.57
70 1.78
0.825 2.10
80 2.03
0.985 2.50
547 814
815 1213
More Options
2 AWG 2 AWG
3 3
7 7
0.282 0.72
70 1.78
0.946 2.40
80 2.03
1.106 2.81
827 1231
1121 1668
More Options
1/0 AWG 1/0 AWG
3 3
19 19
0.361 0.92
90 2.29
1.220 3.10
80 2.03
1.380 3.51
1373 2043
1858 2765
More Options
2/0 AWG 2/0 AWG
3 3
19 19
0.405 1.03
90 2.29
1.311 3.33
80 2.03
1.471 3.74
1640 2441
2164 3220
More Options
3/0 AWG 3/0 AWG
3 3
19 19
0.456 1.16
90 2.29
1.419 3.60
80 2.03
1.579 4.01
2041 3037
2604 3875
More Options
4/0 AWG 4/0 AWG
3 3
19 19
0.512 1.30
90 2.29
1.506 3.83
115 2.92
1.736 4.41
2542 3783
3202 4765
More Options
250 KCMIL 250 KCMIL
3 3
37 37
0.558 1.42
105 2.67
1.665 4.23
115 2.92
1.895 4.81
3150 4688
3995 5945
More Options
350 KCMIL 350 KCMIL
3 3
37 37
0.661 1.68
105 2.67
1.879 4.77
115 2.92
2.109 5.36
4110 6116
5098 7587
More Options
500 KCMIL 500 KCMIL
3 3
37 37
0.789 2.00
105 2.67
2.149 5.46
115 2.92
2.379 6.04
5706 8491
6767 10070
Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Capacitive Reactance (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
14 AWG 14 AWG
3 3
6.9 17.53
98 44.45
2.631 3.92
20 20
25 25
More Options
12 AWG 12 AWG
3 3
7.3 18.54
156 70.76
1.662 2.47
2.002 2.98
0.057 0.08
0.054 0.08
25 25
30 30
More Options
10 AWG 10 AWG
3 3
7.9 20.07
249 112.94
1.040 1.55
1.253 1.86
0.049 0.07
0.050 0.07
35 35
40 40
More Options
8 AWG 8 AWG
3 3
9.3 23.62
396 179.62
0.653 0.97
0.786 1.17
0.046 0.07
0.052 0.08
50 50
55 55
More Options
6 AWG 6 AWG
3 3
10.6 26.92
629 285.31
0.411 0.61
0.495 0.74
0.039 0.06
0.051 0.08
65 65
75 75
More Options
4 AWG 4 AWG
3 3
11.8 29.97
1001 454.05
0.258 0.38
0.310 0.46
0.032 0.05
0.048 0.07
85 85
95 95
More Options
2 AWG 2 AWG
3 3
13.3 33.78
1592 722.12
0.162 0.24
0.195 0.29
0.027 0.04
0.045 0.07
115 115
130 130
More Options
1/0 AWG 1/0 AWG
3 3
16.6 42.16
2534 1149.40
0.102 0.15
0.122 0.18
0.027 0.04
0.044 0.07
150 150
170 170
More Options
2/0 AWG 2/0 AWG
3 3
17.7 44.96
3194 1448.77
0.081 0.12
0.097 0.14
0.025 0.04
0.043 0.06
175 175
195 195
More Options
3/0 AWG 3/0 AWG
3 3
18.9 48.01
4027 1826.61
0.064 0.10
0.078 0.12
0.022 0.03
0.042 0.06
200 200
225 225
More Options
4/0 AWG 4/0 AWG
3 3
20.8 52.83
5078 2303.34
0.051 0.08
0.062 0.09
0.020 0.03
0.041 0.06
230 230
260 260
More Options
250 KCMIL 250 KCMIL
3 3
22.7 57.66
6000 2721.55
0.043 0.06
0.053 0.08
0.021 0.03
0.041 0.06
255 255
290 290
More Options
350 KCMIL 350 KCMIL
3 3
25.3 64.26
8400 3810.17
0.031 0.05
0.039 0.06
0.018 0.03
0.040 0.06
310 310
350 350
More Options
500 KCMIL 500 KCMIL
3 3
28.5 72.39
12000 5443.10
0.022 0.03
0.029 0.04
0.016 0.02
0.039 0.06
380 380
430 430

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) Type RHH/RHW-2
  3. Grounding Conductor: 3 Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8 (Ground size is 100% for sizes 14 - 10 awg and a minimum of 50% of the phase conductor for larger sizes.)
  4. Filler: Fillers as needed to make round
  5. Tape Shield: 5 mil copper tape shield with a minimum of 50% overlap
  6. Overall Jacket: Polyvinyl Chloride (PVC) Jacket. Available in thermoplastic Chlorinated Polyethylene CPE jacket on #4 AWG and larger upon request

Resources