MCAP® Type MC All Purpose MC58

14 AWG through 8 AWG Copper THHN Insulated Conductors. Full-Sized Aluminum Equipment Grounding/ Bonding Conductor. UL Listed. 600 Volt. Rated VW1. Lightweight Aluminum Interlocked Armor is Part of Equipment Bonding/Grounding Path.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire MCAP ® Type MC Cable - All Purpose is suitable for use as follows:

  • Wherever standard AC or MC Cable is permitted.
  • Branch circuit wiring in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
  • Use UL Listed Type MCI-A connectors

Specifications

Select a set of products below for more information:
Conductor Ground Wire Neutral Wire
Size (AWG or kcmil) (mm2) No. of Conductors Stranding Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Size (AWG) Ground Size UOM Size (AWG) Conductor Colors
More Options
12 AWG 12 AWG
2 2
Solid Solid
481 12.22
92 137
10 10
AWG AWG
BLK, RED BLK, RED
More Options
12 AWG 12 AWG
2 2
Stranded Stranded
447 11.37
90 134
10 10
12 12
PUR, WHT PUR, WHT
More Options
12 AWG 12 AWG
3 3
Solid Solid
512 13.03
118 176
10 10
AWG AWG
12 12
ORG, YLW, GRY ORG, YLW, GRY
More Options
12 AWG 12 AWG
3 3
Stranded Stranded
468 11.89
116 173
10 10
12 12
RED, PUR, WHT RED, PUR, WHT
More Options
12 AWG 12 AWG
4 4
Stranded Stranded
568 14.43
152 226
12 12
BLK, RED, WHT-BLK, WHT-RED BLK, RED, WHT-BLK, WHT-RED
More Options
12 AWG 12 AWG
6 6
Solid Solid
610 15.49
199 297
12 12
BLK, RED, BLU, WHT-BLK, WHT-RED, WHT-BLU BLK, RED, BLU, WHT-BLK, WHT-RED, WHT-BLU
More Options
12 AWG 12 AWG
8 8
Solid Solid
648 16.46
251 374
12 12
BLK, BLK-WHT, RED, RED-WHT, BLU, BLU-WHT, WHT, WHT-BLK BLK, BLK-WHT, RED, RED-WHT, BLU, BLU-WHT, WHT, WHT-BLK
More Options
10 AWG 10 AWG
2 2
Solid Solid
561 14.27
132 197
8 8
AWG AWG
10 10
RED, WHT RED, WHT
More Options
10 AWG 10 AWG
2 2
Stranded Stranded
570 14.48
135 201
8 8
AWG AWG
10 10
BRN, GRY BRN, GRY
More Options
10 AWG 10 AWG
4 4
Solid Solid
619 15.74
210 313
10 10
BLK, RED, WHT-BLK, WHT-RED BLK, RED, WHT-BLK, WHT-RED
More Options
10 AWG 10 AWG
4 4
Stranded Stranded
636 16.17
216 322
8 8
10 10
BLK, WHT, RED, BLU BLK, WHT, RED, BLU
More Options
10 AWG 10 AWG
6 6
Solid Solid
709 18.03
293 436
8 8
AWG AWG
10 10
BLK, BLK-WHT, RED, RED-WHT, WHT, WHT-BLK BLK, BLK-WHT, RED, RED-WHT, WHT, WHT-BLK
More Options
10 AWG 10 AWG
6 6
Stranded Stranded
731 18.57
325 484
10 10
BLK, RED, BLU, WHT-BLK, WHT-RED, WHT-BLU BLK, RED, BLU, WHT-BLK, WHT-RED, WHT-BLU
More Options
8 AWG 8 AWG
2 2
Stranded Stranded
688 17.48
199 296
8 8
AWG AWG
8 8
BLK, WHT BLK, WHT
More Options
8 AWG 8 AWG
3 3
Stranded Stranded
722 18.36
266 395
8 8
AWG AWG
8 8
BLK, RED, WHT BLK, RED, WHT

Standards & References

Southwire MCAP® Type MC Cable meets or exceeds the following:

  • UL 83 • UL 1569 • UL 1063
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • NFPA 70 (National Electrical Code), Article 330 • Federal Specification A-A59544 (formerly J-C-30B)
  • FT4/IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Firestop Systems
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire MCAP ® Type MC Cable is constructed with solid soft-drawn copper Type THHN circuit conductors rated 90ºC dry and a full-sized bare 8000 Series aluminum grounding/bonding conductor. This cable is available in sizes 14-8 AWG. The insulated conductors are cabled together and wrapped with a binder tape bearing the print legend. The bare aluminum grounding/bonding conductor is located outside the binding tape and has the same lay as the insulated conductors. Aluminum interlocking armor is snugly applied over the assembly. The aluminum armor and bare aluminum conductor are in intimate contact and together form the equipment ground path. To ensure proper installation, refer to the installation instructions provided with every reel and coil.

  1. An armor assembly that is an equipment grounding conductor per NEC 250.118(10)(b).
  2. Installation instructions included with every reel and coil.
  3. Simplified product application and installation over other armored products.
  4. Faster conductor make-up, wiring device installation and trim-out when grounding bonding conductor is terminated per installation instructions.
  5. Reduces installation costs up to 50% over pipe and wire.
  6. UL Classified 1, 2, and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113, W-L-3117, W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173, C-AJ-3202, C-AJ-4065, C-AJ-4066, F-C-3038.
  7. Cable reverse wound on reel for ease of pulling and installation. When pulling from coils, pull from inside to ensure ease of installation.
  8. Anti-short bushings are not required for use with MC cable per the NEC and UL