SPEC: 13002

Circuit Defender™ 2 Hour Rated Circuit Integrity Shielded SPEC13002

300V, 90°C, Shielded, UL Certified and listed Two-Hour Fire Resistive Fire Alarm Power Limited Cables

Download Category Specifications
PDF Excel Table

Application & Features

Circuit Defender™ cables have been qualified and listed to the demanding requirements of UL 2196 and CAN/ULC-S139 Test for Fire Resistive Cables, and are UL listed Types FPLR/CMR and CSA Certified FAS. Circuit Defender™ Cables meet various industry code requirements (NFPA 70, NFPA 101, NFPA 130, and NFPA 502) for Fire Resistance according to UL 2196 when selected and installed per applicable codes including federal, state, and local and municipal rules, laws, and regulations.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Color Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
18 AWG 18 AWG
2 2
Solid Solid
0.040 0.10
BK, RD BK, RD
30 0.76
25 0.64
0.338 0.86
41 61
6.669 9.92
8.035 11.96
- -
14 14
More Options
16 AWG 16 AWG
2 2
Solid Solid
0.050 0.13
BK, RD BK, RD
30 0.76
25 0.64
0.364 0.92
56 83
4.181 6.22
5.037 7.50
More Options
14 AWG 14 AWG
2 2
Solid Solid
0.064 0.16
BK, RD BK, RD
30 0.76
25 0.64
0.388 0.99
68 101
2.631 3.92
3.170 4.72

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Standards & References

  • UL 1424 Cables for Power-Limited Fire-Alarm Circuits
  • CSA C22.2 No.208 FAS
  • NFPA 70 NFPA 101, NFPA 130, and NFPA 502
  • UL Listed File #E75610 & #E118871
  • UL 2196 and CAN/ULC-S139, UL Electrical Circuit Integrity System #44 (FHIT/7 44)
  • UL 444 Communications Cables (22 AWG - 16 AWG)
  • RoHS-3 Complies with Latest Directive

Construction

  1. Conductor:18, 16 or 14 AWG solid bare oxygen-free copper (OFC) or oxygen-free high thermal conductivity (OFHC)
  2. Tape:Mica
  3. Insulation:Silicone Rubber, Color: black and red
  4. Shield:100% coverage aluminum/polyester foil shield with a drain wire
  5. Jacket:PVC, Color: red