Titan®2 Type HC Liquidtight Flexible Metal Conduit is suitable for the following installations:
Diameter (inches) (centimeters) | |||||
Trade Size (in) (cm) | Inner Diameter (min/max) | Outer Diameter (min/max) | Nominal Total Weight (lbs/1000') (kgs/km) | Min. Bend Radius (in) (cm) | |
552881 | 3/8 0.95 | 4.840 / 5.040 12.29 / 12.80 | 0.690 / 0.710 1.75 / 1.80 | 241 359 | 4 10.16 |
552882 | 1/2 1.27 | 0.622 / 0.642 1.58 / 1.63 | 0.820 / 0.840 2.08 / 2.13 | 305 454 | 6.5 16.51 |
552883 | 3/4 1.91 | 0.820 / 0.840 2.08 / 2.13 | 1.030 / 1.050 2.62 / 2.67 | 410 610 | 8.5 21.59 |
552884 | 1 2.54 | 1.041 / 1.066 2.64 / 2.71 | 1.290 / 1.315 3.28 / 3.34 | 550 818 | 13 33.02 |
552886 | 1 1/4 0.00 | 1.380 / 1.410 3.51 / 3.58 | 1.630 / 1.660 4.14 / 4.22 | 802 1194 | 16 40.64 |
552887 | 1 1/2 0.00 | 1.575 / 1.600 4.00 / 4.06 | 1.865 / 1.900 4.74 / 4.83 | 1130 1682 | 18 45.72 |
552888 | 2 5.08 | 2.020 / 2.045 5.13 / 5.19 | 2.340 / 2.375 5.94 / 6.03 | 1490 2217 | 22.25 56.52 |
552892 | 4 10.16 | 4.000 / 4.040 10.16 / 10.26 | 4.460 / 4.500 11.33 / 11.43 | 3100 4613 | 48 121.92 |
Titan®2 Type HC Liquidtight Flexible Metal Conduit meets or exceeds the following requirements:
Titan®2 Type HC is manufactured with a spiral wound strip of heavy gauge, corrosion-resistant, hot-dipped galvanized steel. For 3/8" through 1-1/4" trade sizes, the core is constructed with a square locked steel strip with an integral copper-bonding strip enclosed within the steel convolutions. A rugged, flame retardant, flexible PVC jacket is extruded over the steel core. The jacket provides protection from liquids, oil, certain chemicals, temperature, extreme weather and sunlight.