SPEC: 22061

RW90 Copper Circuit Sizes (14, 12 & 10 AWG) SPEC22061

Copper Conductor, 600V, 90°C MAX, -40°C MIN. Sunlight Resistant in Black Only.

Download Category Specifications
PDF Excel Table

Application & Features

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Sunlight Resistant in black only. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
14 AWG 14 AWG
1 1
Solid Solid
0.064 0.16
30 0.76
0.128 0.33
12 18
16 24
More Options
14 AWG 14 AWG
1 1
7 7
0.070 0.18
30 0.76
0.135 0.34
12 18
17 25
More Options
12 AWG 12 AWG
1 1
Solid Solid
0.080 0.20
30 0.76
0.144 0.37
19 28
24 36
More Options
12 AWG 12 AWG
1 1
7 7
0.088 0.22
30 0.76
0.153 0.39
20 30
25 37
More Options
10 AWG 10 AWG
1 1
Solid Solid
0.101 0.26
30 0.76
0.165 0.42
31 46
37 55
More Options
10 AWG 10 AWG
1 1
7 7
0.113 0.29
30 0.76
0.177 0.45
32 48
39 58

†Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
14 AWG 14 AWG
1 1
0.500 1.27
32 14.51
2.631 3.92
3.170 4.72
0.058 0.09
20 20
25 25
More Options
14 AWG 14 AWG
1 1
0.500 1.27
32 14.51
2.631 3.92
3.170 4.72
0.058 0.09
20 20
25 25
More Options
12 AWG 12 AWG
1 1
0.600 1.52
52 23.59
1.662 2.47
2.002 2.98
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
1 1
0.600 1.52
52 23.59
1.662 2.47
2.002 2.98
0.054 0.08
25 25
30 30
More Options
10 AWG 10 AWG
1 1
0.700 1.78
83 37.65
1.040 1.55
1.253 1.86
0.050 0.07
35 35
40 40
More Options
10 AWG 10 AWG
1 1
0.700 1.78
83 37.65
1.040 1.55
1.253 1.86
0.050 0.07
35 35
40 40

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size (Strand) Black Red Blue White Brown Orange Yellow Green
14 (Solid) 14 (Solid)
956110
956177
956235
956144
956250
557917
956276
956201
14 (7) 14 (7)
951731
955245
955666
955351
955682
557924
955708
955617
12 (Solid) 12 (Solid)
956102
956169
956227
956136
956243
557861
956268
956193
12 (7) 12 (7)
951749
955237
955658
955344
955674
557923
955690
955609
10 (Solid) 10 (Solid)
956094
956151
956219
956128
557929
557930
557931
956185
10 (7) 10 (7)
951756
955229
955641
955336
557920
557921
557922
955591

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating

Construction

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)