Southwire's CSA-NWMU cables may be used for underground installations, including direct burial. It may also be used for environments exposed to the weather in dry and wet locations. The maximum allowable conductor temperature is 60°C. The minimum recommended installation temperature is -40°C for two-conductor cables (sizes AWG 14 to AWG 6) and -25°C for all other sizes. For three-conductor cables the minimum recommended installation temperature is -10°C (with suitable handling procedures). Material should be properly stored above 0°C for 24 hours prior to installation. The maximum voltage rating for all intended applications is 300 volts. Consult the Canadian Electrical Code for further information related to applications.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Ground Size | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
14 AWG
14 AWG
|
2
2
|
Solid
Solid
|
0.064
0.16
|
60
1.52
|
1 x 14
1 x 14
|
30
0.76
|
0.244
0.62
|
37
55
|
88
131
|
| More Options |
14 AWG
14 AWG
|
3
3
|
Solid
Solid
|
0.064
0.16
|
60
1.52
|
1 x 14
1 x 14
|
30
0.76
|
0.504
1.28
|
50
74
|
117
174
|
| More Options |
12 AWG
12 AWG
|
2
2
|
Solid
Solid
|
0.080
0.20
|
60
1.52
|
1 x 14
1 x 14
|
30
0.76
|
0.261
0.66
|
51
76
|
109
162
|
| More Options |
12 AWG
12 AWG
|
3
3
|
Solid
Solid
|
0.080
0.20
|
60
1.52
|
1 x 14
1 x 14
|
30
0.76
|
0.544
1.38
|
72
107
|
148
220
|
| More Options |
10 AWG
10 AWG
|
2
2
|
Solid
Solid
|
0.101
0.26
|
60
1.52
|
1 x 12
1 x 12
|
30
0.76
|
0.282
0.72
|
82
122
|
146
217
|
| More Options |
10 AWG
10 AWG
|
3
3
|
Solid
Solid
|
0.101
0.26
|
60
1.52
|
1 x 12
1 x 12
|
30
0.76
|
0.595
1.51
|
115
171
|
200
298
|
| More Options |
8 AWG
8 AWG
|
2
2
|
7
7
|
0.143
0.36
|
75
1.91
|
1 x 10
1 x 10
|
45
1.14
|
0.382
0.97
|
133
198
|
253
377
|
| More Options |
8 AWG
8 AWG
|
3
3
|
7
7
|
0.143
0.36
|
75
1.91
|
1 x 10
1 x 10
|
45
1.14
|
0.794
2.02
|
186
277
|
344
512
|
| More Options |
6 AWG
6 AWG
|
2
2
|
7
7
|
0.179
0.45
|
90
2.29
|
1 x 8
1 x 8
|
45
1.14
|
0.448
1.14
|
213
317
|
375
558
|
| More Options |
6 AWG
6 AWG
|
3
3
|
7
7
|
0.179
0.45
|
90
2.29
|
1 x 8
1 x 8
|
45
1.14
|
0.954
2.42
|
297
442
|
513
763
|
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
14 AWG
14 AWG
|
2
2
|
2.000
5.08
|
2.631
3.92
|
3.170
4.72
|
0.058
0.09
|
20
20
|
25
25
|
| More Options |
14 AWG
14 AWG
|
3
3
|
2.016
5.12
|
2.631
3.92
|
3.170
4.72
|
0.058
0.09
|
20
20
|
25
25
|
| More Options |
12 AWG
12 AWG
|
2
2
|
2.400
6.10
|
1.662
2.47
|
2.002
2.98
|
0.054
0.08
|
25
25
|
30
30
|
| More Options |
12 AWG
12 AWG
|
3
3
|
2.176
5.53
|
1.662
2.47
|
2.002
2.98
|
0.054
0.08
|
25
25
|
30
30
|
| More Options |
10 AWG
10 AWG
|
2
2
|
2.300
5.84
|
1.040
1.55
|
1.253
1.86
|
0.050
0.07
|
35
35
|
40
40
|
| More Options |
10 AWG
10 AWG
|
3
3
|
2.380
6.05
|
1.040
1.55
|
1.253
1.86
|
0.050
0.07
|
35
35
|
40
40
|
| More Options |
8 AWG
8 AWG
|
2
2
|
3.100
7.87
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
50
50
|
55
55
|
| More Options |
8 AWG
8 AWG
|
3
3
|
3.176
8.07
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
50
50
|
55
55
|
| More Options |
6 AWG
6 AWG
|
2
2
|
3.600
9.14
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
| More Options |
6 AWG
6 AWG
|
3
3
|
3.816
9.69
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
* Ampacity values based on Canadian Electrical Code, Part 1 2024 Table 2 and do not take into account the overcurrent protection limitations in CEC Rule 14-104(2) of 15 A for 14 AWG Cu, 20 A for 12 AWG Cu, and 30 A for 10 AWG Cu (independent of the conductor temperature rating and stranding). See also CEC Rules 4-004 and 4-006 for additional requirements.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.