SPEC: 45351

CU 600/1000V XLPE Insulation ARMOR-X<SUP>®</SUP> PVC Jacket XHHW-2. VFD Cable - CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type MC-HL Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Continuous Corrugated Welded Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket with 3 Bare CU Ground

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 Volt Type MC-HL ARMOR-X<SUP>®</SUP> power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Shield (in) (cm) Ground (No. x AWG) Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Drain Wire Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Conduit Size (in) (cm)
More Options
8 8
7 7
0.141 0.36
45 1.14
0.750 1.91
50 1.27
0.856 2.17
407 606
396 179.62
6.0 15.24
More Options
6 6
7 7
0.177 0.45
45 1.14
0.840 2.13
50 1.27
0.946 2.40
547 814
629 285.31
6.6 16.76
More Options
4 4
7 7
0.225 0.57
45 1.14
0.920 2.34
50 1.27
1.026 2.61
714 1063
1001 454.05
7.2 18.29
More Options
2 2
7 7
0.282 0.72
45 1.14
1.060 2.69
50 1.27
1.166 2.96
1070 1592
1592 722.12
8.2 20.83
More Options
1/0 1/0
19 19
0.361 0.92
55 1.40
1.350 3.43
50 1.27
1.456 3.70
1745 2597
2534 1149.40
10.2 25.91
More Options
2/0 2/0
19 19
0.405 1.03
55 1.40
1.470 3.73
50 1.27
1.576 4.00
1935 2880
3194 1448.77
11.0 27.94
More Options
3/0 3/0
19 19
0.456 1.16
55 1.40
1.540 3.91
60 1.52
1.666 4.23
2420 3601
4027 1826.61
11.7 29.72
More Options
4/0 4/0
19 19
0.512 1.30
55 1.40
1.590 4.04
60 1.52
1.716 4.36
2837 4222
5078 2303.34
12.0 30.48
More Options
250 250
37 37
0.558 1.42
65 1.65
1.845 4.69
60 1.52
1.971 5.01
3351 4987
6000 2721.55
13.8 35.05
More Options
350 350
37 37
0.661 1.68
65 1.65
2.040 5.18
60 1.52
2.166 5.50
4535 6749
8400 3810.17
15.2 38.61
More Options
500 500
37 37
0.789 2.00
65 1.65
2.290 5.82
75 1.91
2.448 6.22
5990 8914
12000 5443.10
17.1 43.43
More Options
600 600
61 61
0.865 2.20
80 2.03
2.670 6.78
75 1.91
2.828 7.18
7243 10779
14400 6531.72
19.8 50.29
More Options
750 750
61 61
0.968 2.46
80 2.03
3.000 7.62
75 1.91
3.158 8.02
9645 14353
18000 8164.66
22.1 56.13
Cond. Size (AWG/Kcmil) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Capacitive Reactance (Mohms x 1000ft) (Mohms x km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles (amps) Direct Buried Ampacity @ 90C (amps) Direct Buried Ampacity @ 105C (amps) In Duct Ampacity @ 90C (amps) In Duct Ampacity @ 105C (amps) In Air Ampacity @ 90C (amps) In Air Ampacity @ 105C (amps)
More Options
8 8
0.653 0.97
0.786 1.17
0.033 0.05
0.052 0.08
More Options
6 6
0.411 0.61
0.495 0.74
0.027 0.04
0.051 0.08
More Options
4 4
0.258 0.38
0.31 0.46
0.022 0.03
0.048 0.07
More Options
2 2
0.162 0.24
0.195 0.29
0.018 0.03
0.045 0.07
More Options
1/0 1/0
0.102 0.15
0.122 0.18
0.017 0.03
0.044 0.07
More Options
2/0 2/0
0.081 0.12
0.097 0.14
0.016 0.02
0.043 0.06
More Options
3/0 3/0
0.064 0.10
0.078 0.12
0.014 0.02
0.042 0.06
More Options
4/0 4/0
0.051 0.08
0.062 0.09
0.013 0.02
0.041 0.06
More Options
250 250
0.043 0.06
0.053 0.08
0.014 0.02
0.041 0.06
More Options
350 350
0.031 0.05
0.039 0.06
0.012 0.02
0.04 0.06
More Options
500 500
0.022 0.03
0.029 0.04
0.01 0.01
0.039 0.06
More Options
600 600
0.018 0.03
0.025 0.04
0.011 0.02
0.039 0.06
More Options
750 750
0.014 0.02
0.022 0.03
0.01 0.01
0.038 0.06

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA C22.2 No. 123 Metal sheathed cables RA90-HL
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and B8
  2. Insulation: Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor: Class B compressed stranded bare copper per ASTM B3 and B8
  4. Filler: Polypropylene filler
  5. Binder: Polypropylene tape
  6. Armor: ARMOR-X Continuous Corrugated Welded Armor
  7. Overall Jacket: Polyvinyl Chloride (PVC) Jacket