Armorlite® Type MC Neutral Per Phase

12/2 AWG Copper THHN/THWN Insulated Singles. Dedicated Neutral Conductor for Each Phase Conductor. Green Copper THHN Insulated Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire Armorlite® Type MC Cable –Neutral Per Phase is suitable for use as follows:

  • Applications affected by harmonics generated from non-linear switching loads, such as computers, variable frequency drives, electrical test equipment, and officeequipment.
  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multiresidential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Compliance with NEC 210.7 for multiple branch circuits
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC520.5.
  • Installation in cable tray and approvedraceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 HazardousLocations.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
4 4
14 AWG 14 AWG
1 1
15 0.38
14 14
499 12.69
116 172
More Options
4 4
12 AWG 12 AWG
1 1
15 0.38
12 12
541 13.74
159 236
More Options
6 6
12 AWG 12 AWG
1 1
15 0.38
12 12
578 14.68
210 313
More Options
8 8
12 AWG 12 AWG
1 1
15 0.38
12 12
661 16.80
266 396
More Options
14 14
12 AWG 12 AWG
1 1
15 0.38
12 12
847 21.51
453 674
More Options
4 4
10 AWG 10 AWG
1 1
20 0.51
10 10
670 17.04
274 407
More Options
6 6
10 AWG 10 AWG
1 1
20 0.51
10 10
679 17.26
382 569
More Options
8 8
10 AWG 10 AWG
1 1
20 0.51
10 10
883 22.44
469 698
More Options
10 10
10 AWG 10 AWG
1 1
20 0.51
10 10
883 22.44
506 753
More Options
12 12
10 AWG 10 AWG
1 1
20 0.51
10 10
946 24.05
587 874
More Options
6 6
8 AWG 8 AWG
19 19
30 0.76
8 8
917 23.29
553 823
More Options
8 8
8 AWG 8 AWG
19 19
30 0.76
10 10
1030 26.17
670 997
More Options
4 4
12 AWG 12 AWG
1 1
15 0.38
12 12
659 16.75
240 358

Standards & References

Southwire Armorlite® Type MC Cable – Neutral Per Phase meets or exceeds the following requirements:

  • UL 83
  • UL 1569
  • UL 1685
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Jacketed & Non Jacketed will both pass " UL Test" & "FT4/IEEE 1202" (70,000 Btu/hr) VerticalCable Tray Flame Test
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire Armorlite® Type MC Cable – Neutral Per Phase is constructed with solid soft-drawn copper Type THHN/THWN phase conductors, a dedicated neutral per phase conductor, and an insulated copper grounding conductor. The conductors are cabled together and a binder tape bearing the print legend is applied over the conductors. Aluminum interlocking armor is applied over the cable assembly. An optional overall PVC jacket can be applied over the armor.

Resources

There are no downloadable resources for this product.