Southwire's 600 Volt Power Drop Cables conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays (TC-ER per NEC 336.10), direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC Article 501 and 502. Southwire's 600 Volt Power Drop Cable is ideal for use in power feed drop applications.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
6 AWG
6 AWG
|
3
3
|
273
273
|
0.190
0.48
|
35
0.89
|
60
1.52
|
0.755
1.92
|
297
442
|
461
686
|
| More Options |
4 AWG
4 AWG
|
3
3
|
413
413
|
0.235
0.60
|
35
0.89
|
80
2.03
|
0.957
2.43
|
447
665
|
700
1042
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
1330
1330
|
0.420
1.07
|
60
1.52
|
80
2.03
|
1.451
3.69
|
1326
1973
|
1981
2948
|
| More Options |
373.7 KCMIL
373.7 KCMIL
|
3
3
|
931
931
|
0.710
1.80
|
70
1.78
|
110
2.79
|
2.055
5.22
|
3539
5267
|
4478
6664
|
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
6 AWG
6 AWG
|
3
3
|
3.0
7.62
|
629
285.31
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
| More Options |
4 AWG
4 AWG
|
3
3
|
3.8
9.65
|
1001
454.05
|
0.258
0.38
|
0.310
0.46
|
0.048
0.07
|
85
85
|
95
95
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
7.3
18.54
|
3194
1448.77
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
| More Options |
373.7 KCMIL
373.7 KCMIL
|
3
3
|
12.3
31.24
|
2990
1356.24
|
0.033
0.05
|
0.035
0.05
|
0.040
0.06
|
323
323
|
365
365
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.