SPEC: 13021

Fire Alarm FPLP Solid Shielded SPEC13021

300V, 75°C, Multi-Conductor, Shielded, Solid Copper as FPLP. Minimum Operating Temperature 0°C, Maximum Operating Temperature 75°C

Download Category Specifications
PDF Excel Table

Application & Features

Fire protective signaling circuits. Also for smoke detectors, voice communications, audio control and initiating circuits. Article 760 of the NEC. For use in plenum spaces. Minimum Operating Temperature 0°C, Maximum Operating Temperature 75°C

Specifications

Select more options below for part numbers, packaging, and color options:
Cable Type Cond. Size Conductor Number Cond. Type Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) Application DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm)
More Options
FPLP FPLP
18 AWG 18 AWG
2 2
Cu Cu
Solid Solid
0.040 0.10
10 0.25
15 0.38
0.152 0.39
11 16
18 27
Fire System Fire System
6.669 9.92
8.035 11.96
0.9 2.29
More Options
FPLP FPLP
18 AWG 18 AWG
4 4
Cu Cu
Solid Solid
0.040 0.10
10 0.25
15 0.38
0.183 0.46
21 31
30 45
6.669 9.92
8.035 11.96
1.1 2.79
More Options
FPLP FPLP
16 AWG 16 AWG
2 2
Cu Cu
Solid Solid
0.050 0.13
10 0.25
15 0.38
0.176 0.45
17 25
24 36
4.181 6.22
5.037 7.50
1.1 2.79
More Options
FPLP FPLP
16 AWG 16 AWG
4 4
Cu Cu
Solid Solid
0.050 0.13
10 0.25
15 0.38
0.206 0.52
32 48
43 64
4.181 6.22
5.037 7.50
1.2 3.05
More Options
FPLP FPLP
14 AWG 14 AWG
2 2
Cu Cu
Solid Solid
0.064 0.16
10 0.25
15 0.38
0.196 0.50
26 39
36 54
2.631 3.92
3.170 4.72
1.2 3.05
More Options
FPLP FPLP
14 AWG 14 AWG
4 4
Cu Cu
Solid Solid
0.064 0.16
10 0.25
15 0.38
0.234 0.59
51 76
64 95
2.631 3.92
3.170 4.72
1.4 3.56
More Options
FPLP FPLP
12 AWG 12 AWG
2 2
Cu Cu
Solid Solid
0.080 0.20
10 0.25
15 0.38
0.231 0.59
41 61
52 77
Fire Alarm Fire Alarm
1.662 2.47
2.002 2.98
1.4 3.56

Standards & References

  • UL 1424 Cables for Power-Limited Fire-Alarm Circuits
  • UL 1424 Listed FPLP
  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • NFPA 70, NFPA 101, and NFPA 502
  • UL 13 Power-Limited Circuit Cables
  • UL 444 Communications Cables (22 AWG - 16 AWG)
  • RoHS-2 (European Directive 2011/65/EU)

Construction

  1. Conductor:Solid bare copper per ASTM B3
  2. Insulation:Low Smoke Polyvinyl Chloride (LS-PVC)
  3. Drain Wire:24 AWG tinned copper drain wire per ASTM B33
  4. Shield:Aluminum foil shield
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Jacket:Red Low Smoke Polyvinyl Chloride (LS-PVC)