600V ROYAL® SOOW Cord with Black Jacket 90°C PCORD18

600 Volt 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation, Heat, Moisture and Oil Resistant Flexible CPE Jacket.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire Type SOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. The cable is rated -40°C to 90°C, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications

Select a set of products below for more information:
Conductor
Size (AWG or kcmil) (mm2) No. of Conductors No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity Nom. DC Resistance (Conductor) Conductor Colors
More Options
18 AWG 18 AWG
5 5
16 16
465 11.81
127 189
5.5 5.5
6.59 6.59
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
16 AWG 16 AWG
3 3
26 26
395 10.03
96 143
13 13
4.05 4.05
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
16 AWG 16 AWG
4 4
26 26
420 10.67
111 165
10 10
4.05 4.05
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
16 AWG 16 AWG
5 5
26 26
514 13.06
167 249
8 8
4.05 4.05
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
14 AWG 14 AWG
3 3
41 41
530 13.46
169 252
18 18
2.55 2.55
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
14 AWG 14 AWG
4 4
41 41
570 14.48
204 303
15 15
2.55 2.55
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
14 AWG 14 AWG
5 5
41 41
655 16.64
264 392
12 12
2.55 2.55
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
12 AWG 12 AWG
3 3
65 65
608 15.44
230 342
25 25
1.61 1.61
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
12 AWG 12 AWG
4 4
65 65
650 16.51
273 406
20 20
1.61 1.61
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
12 AWG 12 AWG
5 5
65 65
719 18.26
338 503
16 16
1.61 1.61
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
10 AWG 10 AWG
3 3
104 104
665 16.89
297 442
30 30
0.98 0.98
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
10 AWG 10 AWG
4 4
104 104
702 17.83
347 517
25 25
0.98 0.98
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
10 AWG 10 AWG
5 5
104 104
775 19.69
426 634
20 20
0.98 0.98
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
8 AWG 8 AWG
3 3
133 133
848 21.54
427 635
40 40
0.63 0.63
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
8 AWG 8 AWG
4 4
133 133
954 24.23
596 887
35 35
0.63 0.63
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
8 AWG 8 AWG
5 5
133 133
1036 26.31
717 1067
28 28
0.63 0.63
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
6 AWG 6 AWG
3 3
133 133
990 25.15
675 1005
55 55
0.4 0.4
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
6 AWG 6 AWG
4 4
133 133
1075 27.31
830 1235
45 45
0.4 0.4
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
6 AWG 6 AWG
5 5
133 133
1192 30.28
1030 1533
36 36
0.4 0.4
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
4 AWG 4 AWG
3 3
427 427
1137 28.88
893 1329
70 70
0.25 0.25
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
4 AWG 4 AWG
4 4
427 427
1257 31.93
1156 1721
60 60
0.25 0.25
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
4 AWG 4 AWG
5 5
427 427
1395 35.45
1461 2174
48 48
0.25 0.25
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
2 AWG 2 AWG
4 4
168 168
1480 37.59
1723 2564
80 80
0.016 0.016
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
2 AWG 2 AWG
5 5
168 168
1716 43.59
2090 3110
64 64
0.16 0.16
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE

Standards & References

  • UL 62
  • CSA Standard 22.2 No. 49
  • NEC 400
  • NEC 501.140 Class I Division 2
  • Passes CSA FT2 Flame Test
  • MSHA
  • Federal and Military Specification JC-580B
  • RoHS-2 (European Directive 2011/65/EU )

Construction

  1. Conductors: Class K stranded bare copper per ASTM B-174
  2. Insulation: EPDM
  3. Jacket: Black CPE (Other colors available upon request)