SPEC: 45047

Southwire® Machine Flex® CU 600/1000V THHN Insulation Black TPE Jacket. Silicone-Free SPEC45047

Type TC-ER Machine Tray Power Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4. Silicone-Free

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s Machine Flex® tray power cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Southwire’s machine tray cable is ideal to power CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) AC Resistance at 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
8 AWG 8 AWG
3 3
168 168
0.153 0.39
30 0.76
65 1.65
0.627 1.59
157 234
316 470
0.861 1.28
2.5 6.35
50 50
55 55
More Options
8 AWG 8 AWG
4 4
168 168
0.153 0.39
30 0.76
65 1.65
0.700 1.78
210 313
375 558
0.861 1.28
2.8 7.11
40 40
44 44
More Options
8 AWG 8 AWG
5 5
168 168
0.153 0.39
30 0.76
65 1.65
0.766 1.95
263 391
451 671
0.861 1.28
3.0 7.62
40 40
44 44
More Options
6 AWG 6 AWG
4 4
259 259
0.198 0.50
30 0.76
65 1.65
0.817 2.08
358 533
564 839
0.541 0.81
3.2 8.13
52 52
60 60
More Options
4 AWG 4 AWG
4 4
420 420
0.235 0.60
40 1.02
80 2.03
0.969 2.46
532 792
832 1238
0.340 0.51
3.8 9.65
68 68
76 76
More Options
2 AWG 2 AWG
3 3
651 651
0.302 0.77
40 1.02
100 2.54
1.064 2.70
637 948
987 1469
0.216 0.32
5.3 13.46
115 115
130 130
More Options
2 AWG 2 AWG
4 4
651 651
0.302 0.77
40 1.02
100 2.54
1.196 3.04
849 1263
1267 1886
0.216 0.32
5.9 14.99
92 92
104 104
More Options
1/0 AWG 1/0 AWG
3 3
1064 1064
0.354 0.90
60 1.52
80 2.03
1.318 3.35
1230 1830
1694 2521
0.126 0.19
6.6 16.76
150 150
170 170
More Options
2/0 AWG 2/0 AWG
3 3
1330 1330
0.400 1.02
60 1.52
80 2.03
1.418 3.60
1485 2210
2021 3008
0.101 0.15
7.1 18.03
175 175
195 195
More Options
350 KCMIL 350 KCMIL
3 3
893 893
0.809 2.05
70 1.78
110 2.79
2.019 5.13
3497 5204
4461 6639
0.041 0.06
12.1 30.73
310 310
350 350
More Options
600 KCMIL 600 KCMIL
3 3
1480 1480
1.125 2.86
80 2.03
140 3.56
2.709 6.88
5841 8692
7207 10725
0.026 0.04
16.3 41.40
420 420
475 475

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Power-Limited Circuit Cables
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 AWM Style 2587
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2250 Instrumentation Tray Cable
  • UL 2277 Type WTTC
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Exceeds Ecolab PM-40-1 Material Resistance Test With 30-day Exposure, UL Verified V747862
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conductor:Class K or I flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN
  3. Ground:One Green Ground with Yellow Stripe Type THHN
  4. Jacket:Black Thermoplastic Elastomer (TPE) (other jacket colors available upon request)