Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -40°C for cold bend. Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
2 AWG
2 AWG
|
7
7
|
0.282
0.72
|
0.755
1.92
|
220
5.59
|
0.815
2.07
|
80
2.03
|
0.995
2.53
|
604
899
|
530
240.40
|
11.9
30.23
|
3.0
7.62
|
| More Options |
1 AWG
1 AWG
|
19
19
|
0.322
0.82
|
0.800
2.03
|
220
5.59
|
0.860
2.18
|
80
2.03
|
1.040
2.64
|
683
1016
|
669
303.45
|
12.4
31.50
|
3.0
7.62
|
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.361
0.92
|
0.840
2.13
|
220
5.59
|
0.900
2.29
|
80
2.03
|
1.080
2.74
|
774
1152
|
844
382.83
|
12.9
32.77
|
3.0
7.62
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
0.884
2.25
|
220
5.59
|
0.944
2.40
|
80
2.03
|
1.124
2.85
|
888
1321
|
1064
482.62
|
13.4
34.04
|
3.5
8.89
|
| More Options |
3/0 AWG
3/0 AWG
|
19
19
|
0.456
1.16
|
0.934
2.37
|
220
5.59
|
0.994
2.52
|
80
2.03
|
1.174
2.98
|
1021
1519
|
1342
608.72
|
14.0
35.56
|
3.5
8.89
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
0.990
2.51
|
220
5.59
|
1.050
2.67
|
80
2.03
|
1.230
3.12
|
1189
1769
|
1692
767.48
|
14.7
37.34
|
3.5
8.89
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
1.044
2.65
|
220
5.59
|
1.104
2.80
|
80
2.03
|
1.284
3.26
|
1342
1997
|
2000
907.18
|
15.4
39.12
|
4.0
10.16
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
1.147
2.91
|
220
5.59
|
1.207
3.07
|
80
2.03
|
1.387
3.52
|
1711
2546
|
2800
1270.06
|
16.6
42.16
|
4.0
10.16
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.252
3.18
|
220
5.59
|
1.312
3.33
|
80
2.03
|
1.492
3.79
|
2237
3329
|
4000
1814.37
|
17.9
45.47
|
4.5
11.43
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
1.464
3.72
|
220
5.59
|
1.524
3.87
|
110
2.79
|
1.764
4.48
|
3239
4820
|
6000
2721.55
|
21.1
53.59
|
5.0
12.70
|
* Conduit size based on 3 phase 40% fill-factor without ground
§ CSA listed
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
| More Options |
2 AWG
2 AWG
|
0.162
0.24
|
0.204
0.30
|
0.067
0.10
|
0.051
0.08
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
2571
2571
|
155
155
|
165
165
|
195
195
|
215
215
|
| More Options |
1 AWG
1 AWG
|
0.128
0.19
|
0.162
0.24
|
0.061
0.09
|
0.049
0.07
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
2695
2695
|
175
175
|
185
185
|
225
225
|
250
250
|
| More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.128
0.19
|
0.057
0.08
|
0.047
0.07
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
2816
2816
|
200
200
|
215
215
|
260
260
|
290
290
|
| More Options |
2/0 AWG
2/0 AWG
|
0.081
0.12
|
0.102
0.15
|
0.053
0.08
|
0.045
0.07
|
0.529 + j0.445
0.529 + j0.445
|
0.162 + j0.049
0.162 + j0.049
|
2952
2952
|
230
230
|
245
245
|
300
300
|
335
335
|
| More Options |
3/0 AWG
3/0 AWG
|
0.064
0.10
|
0.081
0.12
|
0.048
0.07
|
0.043
0.06
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
3110
3110
|
260
260
|
275
275
|
345
345
|
385
385
|
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.065
0.10
|
0.044
0.07
|
0.042
0.06
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
3284
3284
|
295
295
|
315
315
|
400
400
|
445
445
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.056
0.08
|
0.042
0.06
|
0.041
0.06
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
3451
3451
|
325
325
|
345
345
|
445
445
|
495
495
|
| More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.041
0.06
|
0.037
0.06
|
0.039
0.06
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
3770
3770
|
390
390
|
415
415
|
550
550
|
610
610
|
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.030
0.04
|
0.032
0.05
|
0.037
0.06
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
4167
4167
|
465
465
|
500
500
|
685
685
|
765
765
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.023
0.03
|
0.028
0.04
|
0.035
0.05
|
0.378 + j0.289
0.378 + j0.289
|
0.030 + j0.035
0.030 + j0.035
|
4752
4752
|
565
565
|
610
610
|
885
885
|
990
990
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.