SIS VW-1 or XHHW-2 LW93

90°C Wet or Dry, 600 Volts. Flexible Stranded Tinned Copper Conductor. XLPE Insulation.

Download Category Specifications
PDF Excel Table

Application & Features

For use in internal wiring of electrical equipment, control panels, switchboards, and appliances or for use as motor leads. For use as permitted in NEC Article 310.

Specifications

Select a set of products below for more information:
Conductor
Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
14 AWG 14 AWG
41 41
30 0.76
127 3.23
18 27
More Options
12 AWG 12 AWG
65 65
155 3.94
28 42
More Options
10 AWG 10 AWG
105 105
170 4.32
40 60
More Options
8 AWG 8 AWG
133 133
45 1.14
247 6.27
71 105
More Options
6 AWG 6 AWG
133 133
45 1.14
294 7.47
111 165
More Options
4 AWG 4 AWG
133 133
45 1.14
338 8.59
159 236
More Options
2 AWG 2 AWG
133 133
45 1.14
388 9.86
241 359
More Options
1/0 AWG 1/0 AWG
1064 1064
55 1.40
485 12.32
383 570

Standards & References

  • ASTM B33
  • UL 44 - Type SIS
  • CSA C22.2 No. 38 - Type SIS
  • CSA C22.2 No. 38 - Type RW90
  • Voltage Rating: 600V
  • Oil Resistant I/II
  • Gasoline and gasoline vapor resistant I/II
  • Sunlight Resistant
  • Rated UL & CSA VW-1
  • RoHS-2 Compliant

Construction

  1. Conductors: Flexible stranded tinned copper; See Table 1 for Stranding Details
  2. Insulation: Crosslinked Polyethylene (XLPE)
  3. Colors: All Colors available; Stripes available on special order