Southwire’s 600 Volt SOLONONplus® Type RHH/RHW-2 USE-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) (mm2) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
643665 |
1
1
|
14 AWG
14 AWG
|
7
7
|
45
1.14
|
|
|
164
4.19
|
24
36
|
|
643666 |
1
1
|
12 AWG
12 AWG
|
7
7
|
45
1.14
|
|
|
183
4.65
|
33
50
|
|
643667 |
1
1
|
10 AWG
10 AWG
|
7
7
|
45
1.14
|
|
|
207
5.26
|
48
71
|
|
643668 |
1
1
|
8 AWG
8 AWG
|
7
7
|
60
1.52
|
|
|
268
6.81
|
78
116
|
|
643669 |
1
1
|
6 AWG
6 AWG
|
7
7
|
60
1.52
|
|
|
304
7.72
|
113
168
|
|
643670 |
1
1
|
4 AWG
4 AWG
|
7
7
|
60
1.52
|
|
|
351
8.92
|
167
249
|
|
646618 |
1
1
|
3 AWG
3 AWG
|
7
7
|
60
1.52
|
|
|
378
9.60
|
204
304
|
|
643671 |
1
1
|
2 AWG
2 AWG
|
7
7
|
60
1.52
|
|
|
409
10.39
|
251
374
|
|
643672 |
1
1
|
1 AWG
1 AWG
|
19
19
|
80
2.03
|
|
|
490
12.45
|
330
491
|
|
643673 |
1
1
|
1/0 AWG
1/0 AWG
|
19
19
|
80
2.03
|
|
|
530
13.46
|
405
603
|
|
643674 |
1
1
|
2/0 AWG
2/0 AWG
|
19
19
|
80
2.03
|
|
|
574
14.58
|
498
741
|
|
643675 |
1
1
|
3/0 AWG
3/0 AWG
|
19
19
|
80
2.03
|
|
|
624
15.85
|
614
914
|
|
643677 |
1
1
|
4/0 AWG
4/0 AWG
|
19
19
|
80
2.03
|
|
|
680
17.27
|
760
1131
|
|
643678 |
1
1
|
250 KCMIL
250 KCMIL
|
37
37
|
95
2.41
|
|
|
758
19.25
|
910
1354
|
|
643679 |
1
1
|
350 KCMIL
350 KCMIL
|
37
37
|
95
2.41
|
|
|
841
21.36
|
1236
1840
|
|
557136 |
1
1
|
500 KCMIL
500 KCMIL
|
37
37
|
95
2.41
|
|
|
995
25.27
|
1733
2580
|
|
647653 |
1
1
|
600 KCMIL
600 KCMIL
|
61
61
|
110
2.79
|
|
|
1072
27.23
|
2084
3102
|
|
643826 |
1
1
|
750 KCMIL
750 KCMIL
|
61
61
|
110
2.79
|
|
|
1200
30.48
|
2579
3839
|
|
643827 |
1
1
|
1000 KCMIL
1000 KCMIL
|
61
61
|
110
2.79
|
|
|
1349
34.26
|
3388
5042
|
|