Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Only UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Conductor | Ground Wire | ||||||||
No. of Conductors | Size (AWG or kcmil) | No. of Strands | Insulation Thickness (mils) (mm) | Size (AWG) | No. of Strands | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Allowable Ampacity | |
619930 | 12 12 | 14 AWG 14 AWG | 7 7 | 30 0.76 | 667 16.94 | 296 441 | |||
606668 | 2 2 | 12 AWG 12 AWG | 7 7 | 30 0.76 | 400 10.17 | 89 133 | |||
619939 | 9 9 | 12 AWG 12 AWG | 7 7 | 30 0.76 | 659 16.75 | 313 466 | |||
618414 | 12 12 | 12 AWG 12 AWG | 7 7 | 30 0.76 | 732 18.60 | 402 599 | |||
604290 | 2 2 | 10 AWG 10 AWG | 7 7 | 30 0.76 | 440 11.18 | 120 179 | |||
618360 | 3 3 | 10 AWG 10 AWG | 7 7 | 30 0.76 | 459 11.67 | 165 246 | |||
619945 | 4 4 | 10 AWG 10 AWG | 7 7 | 30 0.76 | 510 12.97 | 205 305 | |||
619498 | 8 8 | 10 AWG 10 AWG | 7 7 | 30 0.76 | 694 17.63 | 402 598 | |||
606610 | 12 12 | 10 AWG 10 AWG | 7 7 | 30 0.76 | 879 22.34 | 618 920 |