SPEC: 45443

Southwire® Machine Flex® TCU 1000V XLPE Insulation Three Symmetrical Grounds Shielded TPE Jacket. XHHW-2 Flexible Variable Frequency Drive (VFD). Silicone-Free SPEC45443

Reduced Diameter Type TC-ER Variable Frequency Drive Cable 600 Volt Tinned Copper Conductors, Cross­linked Insulation Type XHHW-2. Thermoplastic Elastomer Jacket. Rated 90C Dry or Wet, -40C Cold Impact, Identification Method 4, 1000 Volt Flexible Motor Supply. CSA CIC/TC FT4 Flame. Silicone-Free

Download Category Specifications
PDF Excel Table

Application & Features

Power supply cable for VFDs and motors, suitable for cable tray (TC-ER rated), conduit, raceways, and machine tool wiring conforming to NFPA 79 2018. Suitable for free air and direct burial. It's flexible design is ideal or use on operation processes in accordance with he NEC® Articles 336, 501 and 502 including, but not limited to: fans, pumps, conveyors, compressors, elevators and lifts, extruders, crushers and presses, assembly lines, food and beverage, wind energy and data centers. Cable is rated for -40C Cold Bend and Impact. Multiple approvals for multiple applications.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Ground Size Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
12 AWG 12 AWG
3 3
65 65
0.094 0.24
30 0.76
3x16 3x16
45 1.14
0.470 1.19
112 167
173 257

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
12 AWG 12 AWG
3 3
5.6 14.22
156 70.76
1.774 2.64
2.137 3.18
0.054 0.08
25 25
30 30

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

Cable Size Max Motor Size Dia Over Shield
(AWG/Kcmil) (AWG/Kcmil)
230V(HP) 230V(HP)
460V(HP) 460V(HP)
475V(HP) 475V(HP)
(mils) (mils)
16 16
- -
5 5
5 5
0.535 0.535
14 14
5 5
7.5 7.5
10 10
0.567 0.567
12 12
5 5
10 10
10 10
0.608 0.608
10 10
7.5 7.5
15 15
20 20
0.671 0.671
8 8
7.5 7.5
30 30
30 30
0.837 0.837
6 6
15 15
40 40
50 50
0.898 0.898
4 4
20 20
50 50
60 60
0.995 0.995
2 2
30 30
60 60
75 75
1.135 1.135
1 1
40 40
75 75
100 100
1.22 1.22

Standards & References

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Type TC-ER Standard Power and Control Cables (1000V 14AWG and Larger)
  • UL 2277 Flexible Motor Supply Cable and Wind Turbine Tray Cable
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-138-738 Power Cables Rated 2000 Volts or Less for use Between Variable Frequency Drives and Motors
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conductor:Class K flexible stranded tinned annealed copper per ASTM B33 and B172 or B174
  2. Insulation:Cross Linked Insulation Type XHHW-2
  3. Ground:Three tinned grounds laid within insulated phase conductor interstices
  4. Filler:Filler as needed to make round.
  5. Shielding:100% coverage aluminum/mylar/aluminum foil laminate under 85% coverage tinned copper braid
  6. Jacket:Black Thermoplastic Elastomer (TPE)