Southwire’s Machine Flex® tray power cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Southwire’s machine tray cable is ideal to power CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.
Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Min. Bend Radius (in) (cm) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
More Options |
18 AWG
18 AWG
|
3
3
|
16
16
|
0.044
0.11
|
20
0.51
|
45
1.14
|
0.281
0.71
|
15
22
|
43
64
|
8.613
12.82
|
1.1
2.79
|
-
-
|
14
14
|
More Options |
18 AWG
18 AWG
|
4
4
|
16
16
|
0.044
0.11
|
20
0.51
|
45
1.14
|
0.306
0.78
|
20
30
|
54
80
|
8.613
12.82
|
1.2
3.05
|
-
-
|
11
11
|
More Options |
18 AWG
18 AWG
|
5
5
|
16
16
|
0.044
0.11
|
20
0.51
|
45
1.14
|
0.332
0.84
|
25
37
|
63
94
|
8.613
12.82
|
1.3
3.30
|
-
-
|
11
11
|
More Options |
18 AWG
18 AWG
|
7
7
|
16
16
|
0.044
0.11
|
20
0.51
|
45
1.14
|
0.358
0.91
|
35
52
|
80
119
|
8.613
12.82
|
1.4
3.56
|
-
-
|
9
9
|
More Options |
18 AWG
18 AWG
|
9
9
|
16
16
|
0.044
0.11
|
20
0.51
|
45
1.14
|
0.411
1.04
|
45
67
|
102
152
|
8.613
12.82
|
1.6
4.06
|
-
-
|
9
9
|
More Options |
18 AWG
18 AWG
|
12
12
|
16
16
|
0.044
0.11
|
20
0.51
|
45
1.14
|
0.456
1.16
|
60
89
|
132
196
|
8.613
12.82
|
1.8
4.57
|
-
-
|
7
7
|
More Options |
18 AWG
18 AWG
|
25
25
|
16
16
|
0.044
0.11
|
20
0.51
|
65
1.65
|
0.635
1.61
|
125
186
|
254
378
|
8.613
12.82
|
1.3
3.30
|
-
-
|
6
6
|
More Options |
16 AWG
16 AWG
|
3
3
|
26
26
|
0.059
0.15
|
20
0.51
|
50
1.27
|
0.311
0.79
|
24
36
|
58
86
|
5.406
8.05
|
1.2
3.05
|
-
-
|
18
18
|
More Options |
16 AWG
16 AWG
|
4
4
|
26
26
|
0.059
0.15
|
20
0.51
|
50
1.27
|
0.339
0.86
|
32
48
|
71
106
|
5.406
8.05
|
1.4
3.56
|
-
-
|
14
14
|
More Options |
16 AWG
16 AWG
|
5
5
|
26
26
|
0.059
0.15
|
20
0.51
|
45
1.14
|
0.370
0.94
|
40
60
|
86
128
|
5.406
8.05
|
1.5
3.81
|
-
-
|
14
14
|
More Options |
16 AWG
16 AWG
|
9
9
|
26
26
|
0.059
0.15
|
20
0.51
|
50
1.27
|
0.462
1.17
|
72
107
|
138
205
|
5.406
8.05
|
1.9
4.83
|
-
-
|
12
12
|
More Options |
16 AWG
16 AWG
|
12
12
|
26
26
|
0.059
0.15
|
20
0.51
|
50
1.27
|
0.509
1.29
|
97
144
|
175
260
|
5.406
8.05
|
2.0
5.08
|
-
-
|
9
9
|
More Options |
14 AWG
14 AWG
|
3
3
|
41
41
|
0.073
0.19
|
20
0.51
|
50
1.27
|
0.342
0.87
|
38
57
|
77
115
|
3.391
5.05
|
1.4
3.56
|
20
20
|
25
25
|
More Options |
14 AWG
14 AWG
|
4
4
|
41
41
|
0.073
0.19
|
20
0.51
|
50
1.27
|
0.375
0.95
|
51
76
|
97
144
|
3.391
5.05
|
1.5
3.81
|
16
16
|
20
20
|
More Options |
14 AWG
14 AWG
|
9
9
|
41
41
|
0.073
0.19
|
20
0.51
|
50
1.27
|
0.516
1.31
|
115
171
|
189
281
|
3.391
5.05
|
2.1
5.33
|
14
14
|
17
17
|
More Options |
14 AWG
14 AWG
|
12
12
|
41
41
|
0.073
0.19
|
20
0.51
|
65
1.65
|
0.608
1.54
|
153
228
|
258
384
|
3.391
5.05
|
2.5
6.35
|
10
10
|
12
12
|
More Options |
14 AWG
14 AWG
|
18
18
|
41
41
|
0.073
0.19
|
20
0.51
|
65
1.65
|
0.697
1.77
|
230
342
|
419
624
|
3.391
5.05
|
2.8
7.11
|
10
10
|
12
12
|
More Options |
14 AWG
14 AWG
|
25
25
|
41
41
|
0.073
0.19
|
20
0.51
|
65
1.65
|
0.806
2.05
|
318
473
|
488
726
|
3.391
5.05
|
3.2
8.13
|
9
9
|
11
11
|
More Options |
12 AWG
12 AWG
|
3
3
|
65
65
|
0.094
0.24
|
20
0.51
|
50
1.27
|
0.389
0.99
|
60
89
|
108
161
|
2.137
3.18
|
1.6
4.06
|
25
25
|
30
30
|
More Options |
12 AWG
12 AWG
|
4
4
|
65
65
|
0.094
0.24
|
20
0.51
|
50
1.27
|
0.420
1.07
|
81
121
|
137
204
|
2.137
3.18
|
1.7
4.32
|
20
20
|
24
24
|
More Options |
12 AWG
12 AWG
|
5
5
|
65
65
|
0.094
0.24
|
20
0.51
|
50
1.27
|
0.462
1.17
|
101
150
|
165
246
|
2.137
3.18
|
1.9
4.83
|
20
20
|
24
24
|
More Options |
12 AWG
12 AWG
|
7
7
|
65
65
|
0.094
0.24
|
20
0.51
|
50
1.27
|
0.502
1.28
|
141
210
|
219
326
|
2.137
3.18
|
2.0
5.08
|
17
17
|
21
21
|
More Options |
10 AWG
10 AWG
|
4
4
|
105
105
|
0.117
0.30
|
25
0.64
|
50
1.27
|
0.502
1.28
|
129
192
|
202
301
|
1.339
1.99
|
2.0
5.08
|
28
28
|
32
32
|
More Options |
10 AWG
10 AWG
|
5
5
|
105
105
|
0.117
0.30
|
25
0.64
|
50
1.27
|
0.579
1.47
|
161
240
|
257
382
|
1.339
1.99
|
2.0
5.08
|
28
28
|
32
32
|
More Options |
10 AWG
10 AWG
|
7
7
|
105
105
|
0.117
0.30
|
25
0.64
|
60
1.52
|
0.628
1.60
|
226
336
|
337
502
|
1.339
1.99
|
2.4
6.10
|
24
24
|
28
28
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.